Plan Review Notes
Plan Review Notes For Permit 08070320
Permit Number 08070320
Review Stop B
Sequence Number 14
Notes
Date Text
2009-06-25 20:16:41BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2004
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 SUBMITTAL ON 6/22/09 FOR STRUCTURAL WIND LOAD INTEGRITY
 OF PACKAGE UNITS.
  
 1) FBCM 301.13 MECHANICAL UNITS EXPOSED TO WIND. FOR
 THE SANYO OUTDOOR UNITS THE FIFTH PAGE (UNNUMBERED) OF
 THE CALCULATION REPORT ONLY ADDRESSES AND SPECIFIES THE
 SCREWS REQUIRED FOR ATTACHMENT OF THE UNIT TO IT'S
 "BOTTOM PLATE ASSEMBLY". THE REPORT GOES ON TO SHOW
 EXPLODED VIEWS OF THE UNIT CONSTRUCTION BUT THE
 CALCULATIONS DO NOT ADDRESS THE REQUIREMENT TO SHOW
 THAT THE EXTERNAL (VERTICAL AND HORIZONTAL) PANELS OF
 THE UNIT WILL RETAIN THEIR INTEGRITY AND REMAIN
 ATTACHED TO THE UNIT WHEN SUBJECT TO THE WIND PRESSURES
 RESULTING FROM 140 MPH WIND SPEED (3 SECOND GUST).
 THERE ARE NO CALCULATIONS FOR THE SCREWS/FASTENERS
 HOLDING THE PANELS TOGETHER, AND THERE ARE NO
 CALCULATIONS FOR THE PANELS THEMSELVES (SHEAR AT HOLES
 BASED ON HOLE SIZE AND EDGE DISTANCE , ETC.). AS SUCH
 THE SUBMITTED CALCULATIONS DO NOT ADDRESS THE 12/17/08
 PROVISO GIVEN BY RON REGUEIRO, MECHANICAL PLANS
 EXAMINER II. THE MECHANICAL CODE SECTION REQUIRES THAT
 THE APPLIANCE ITSELF BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES. SUBMIT MANUFACTURER'S TEST
 DATA OR STRUCTURAL CALCULATIONS TO SHOW THAT THE
 PACKAGE UNIT HAS BEEN TESTED OR DESIGNED FOR THE WIND
 PRESSURES RESULTING FROM 140 MPH WIND SPEED (3 SECOND
 GUST). THE PROVISO GIVEN BY THE MECHANICAL PLANS
 EXAMINER ON 12/17/08 STATED THIS SAME REQUIREMENT,
 QUOTE: "PROVIDE MANUFACTURER'S SUBMITTAL DATA SHOWING
 OUTDOOR APPLIANCES ARE DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13."
  
 2) 471.025 F.S. AND 61G15-23.002 FL. ADMINISTRATIVE
 CODE. ONLY THE COVER PAGE OF BOTH CALCULATION REPORTS
 IS SIGNED AND SEALED. WHEN SUBMITTING CALCULATION
 REPORTS THE ENGINEER MUST EITHER SIGN AND SEAL EACH
 SHEET OR PROVIDE A SIGNED AND SEALED CONTENTS PAGE
 WHICH REFERENCES THE SHEET NUMBER OF EACH SHEET IN THE
 CALCULATION REPORT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]