| 2009-06-25 20:16:41 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN (561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2004 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | SUBMITTAL ON 6/22/09 FOR STRUCTURAL WIND LOAD INTEGRITY |
| | OF PACKAGE UNITS. |
| | |
| | 1) FBCM 301.13 MECHANICAL UNITS EXPOSED TO WIND. FOR |
| | THE SANYO OUTDOOR UNITS THE FIFTH PAGE (UNNUMBERED) OF |
| | THE CALCULATION REPORT ONLY ADDRESSES AND SPECIFIES THE |
| | SCREWS REQUIRED FOR ATTACHMENT OF THE UNIT TO IT'S |
| | "BOTTOM PLATE ASSEMBLY". THE REPORT GOES ON TO SHOW |
| | EXPLODED VIEWS OF THE UNIT CONSTRUCTION BUT THE |
| | CALCULATIONS DO NOT ADDRESS THE REQUIREMENT TO SHOW |
| | THAT THE EXTERNAL (VERTICAL AND HORIZONTAL) PANELS OF |
| | THE UNIT WILL RETAIN THEIR INTEGRITY AND REMAIN |
| | ATTACHED TO THE UNIT WHEN SUBJECT TO THE WIND PRESSURES |
| | RESULTING FROM 140 MPH WIND SPEED (3 SECOND GUST). |
| | THERE ARE NO CALCULATIONS FOR THE SCREWS/FASTENERS |
| | HOLDING THE PANELS TOGETHER, AND THERE ARE NO |
| | CALCULATIONS FOR THE PANELS THEMSELVES (SHEAR AT HOLES |
| | BASED ON HOLE SIZE AND EDGE DISTANCE , ETC.). AS SUCH |
| | THE SUBMITTED CALCULATIONS DO NOT ADDRESS THE 12/17/08 |
| | PROVISO GIVEN BY RON REGUEIRO, MECHANICAL PLANS |
| | EXAMINER II. THE MECHANICAL CODE SECTION REQUIRES THAT |
| | THE APPLIANCE ITSELF BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES. SUBMIT MANUFACTURER'S TEST |
| | DATA OR STRUCTURAL CALCULATIONS TO SHOW THAT THE |
| | PACKAGE UNIT HAS BEEN TESTED OR DESIGNED FOR THE WIND |
| | PRESSURES RESULTING FROM 140 MPH WIND SPEED (3 SECOND |
| | GUST). THE PROVISO GIVEN BY THE MECHANICAL PLANS |
| | EXAMINER ON 12/17/08 STATED THIS SAME REQUIREMENT, |
| | QUOTE: "PROVIDE MANUFACTURER'S SUBMITTAL DATA SHOWING |
| | OUTDOOR APPLIANCES ARE DESIGNED TO RESIST WIND |
| | PRESSURES IN ACCORDANCE WITH FBCM 301.13." |
| | |
| | 2) 471.025 F.S. AND 61G15-23.002 FL. ADMINISTRATIVE |
| | CODE. ONLY THE COVER PAGE OF BOTH CALCULATION REPORTS |
| | IS SIGNED AND SEALED. WHEN SUBMITTING CALCULATION |
| | REPORTS THE ENGINEER MUST EITHER SIGN AND SEAL EACH |
| | SHEET OR PROVIDE A SIGNED AND SEALED CONTENTS PAGE |
| | WHICH REFERENCES THE SHEET NUMBER OF EACH SHEET IN THE |
| | CALCULATION REPORT. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6652 ROBERT BROWN |
| | E-MAIL: [email protected] |