| 2009-05-14 20:09:33 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN (561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2004 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | SUBMITTAL ON 4/27/09 FOR TIE DOWN CABLES ON PACKAGE |
| | UNIT. |
| | |
| | 1) FBCM 301.13 MECHANICAL UNITS EXPOSED TO WIND. ONLY |
| | TIE DOWN CABLES ARE BEING PROPOSED. THAT DOES NOT |
| | ADDRESS THE 12/17/08 PROVISO GIVEN BY RON REGUEIRO, |
| | MECHANICAL PLANS EXAMINER II. THE MECHANICAL CODE |
| | SECTION REQUIRES THAT THE APPLIANCE ITSELF BE DESIGNED |
| | AND INSTALLED TO RESIST THE WIND PRESSURES. SUBMIT |
| | MANUFACTURER'S TEST DATA OR STRUCTURAL CALCULATIONS TO |
| | SHOW THAT THE PACKAGE UNIT HAS BEEN TESTED OR DESIGNED |
| | FOR THE WIND PRESSURES RESULTING FROM 140 MPH WIND |
| | SPEED (3 SECOND GUST). THE PROVISO GIVEN BY THE |
| | MECHANICAL PLANS EXAMINER ON 12/17/08 STATED THIS SAME |
| | REQUIREMENT, QUOTE: "PROVIDE MANUFACTURER'S SUBMITTAL |
| | DATA SHOWING OUTDOOR APPLIANCES ARE DESIGNED TO RESIST |
| | WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13." |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6652 ROBERT BROWN |