Plan Review Notes
Plan Review Notes For Permit 08070320
Permit Number 08070320
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-08 11:24:15***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003.
  
 2) ADDRESS ON BUILDING SHALL BE MINIMUM 6" IN HEIGHT,
 1" WIDTH AND CONTRASTING WITH BACKGROUND. PLEASE ADD TO
 ELEVATIONS.
  
 3) KNOX BOX TO BE LOCATED AT WHAT IS CONSIDERED TO BE
 FRONT ENTRANCE TO BUILDING. CONTACT WPBFR BUREAU OF
 FIRE PREVENTION AT (561) 804-4724 FOR ASSISTANCE.
  
 4) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS.
  
 5) EMERGENCY VEHICLE ACCESS AND WATER SUPPLY TO COMPLY
 WITH NFPA 1, 2003, CHAPTER-18.
  
 6) ELEVATOR SHALL COMPLY WITH REQUIREMENTS OF ASME
 A17.1.
  
 7) FIRE RATED DOORS SHALL BE PROVIDED WITH UL LISTED
 DOOR CLOSERS TO CREATE POSITIVE LATCH. DOOR SCHEDULE ON
 SHEET A118C.
  
 8) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 9) A FACTOR OF .2" PER PERSON HAS BEEN CALCULATED ON
 SHEET A901C FOR STAIRWAYS. PLEASE NOTE THAT TABLE
 7.3.3.1 NFPA 101 USES A FACTOR OF 0.2" FOR LEVEL
 COMPONENTS AND RAMPS AND 0.3" FOR STAIRWAYS. THIS WILL
 HAVE AN OVERALL IMPACT ON CALCULATIONS.
  
 10) PLEASE EXPLAIN FACTOR OF .15 FOR DOOR EGRESS.
 PLEASE NOTE LAST COMMENT REGARDING LEVEL COMPONENTS.
  
 11) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH REQUIREMENTS OF NFPA 241.
  
 12) CLARIFY OCCUPANT CLASSIFICATION FOR EACH AREA.
 MODERATE HAZARD IS INDICATED IN CODE ANALYSIS UNDER USE
 OF OCCUPANCY. ADDITIONALLY, PLANS INDICATE VARIOUS
 PROCESSING AREAS WHICH SEEMS TO SUGGEST INDUSTRIAL
 USE.
  
  
 13) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 14) FIRE ALRM SHALL BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE.
  
 15) PENETRATIONS INTO EXIT ENCLOSURES SHALL BE LIMITED
 AND IN COMPLIANCE WITH SEC. 7.1.3.2 (6), NFPA 101.
 SHEET M102C
  
 16) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 17) NEW FIRE DAMPERS TO BE TESTED FOR CLOSURE IN
 ACCORDANCE WITH THE REQUIREMENTS OF UL 555.
  
 18) PROVIDE MANUFACTURER SPECIFICATION SHEETS FOR
 PROPOSED FIRE PUMP.
  
 19) KNOX LOCKING CAPS ARE REQUIRED FOR FIRE DEPARTMENT
 CONNECTION. SHEET FP 103C
  
 20) PROVIDE DETAIL FOR DOUBLE CHECK DETECTOR ASSEMBLY.
 IN ADDITION TO ELECTRONIC SUPERVISION, CONTROL VALVES
 TO BE SECURED WITH CHAIN AND LOCK.
  
 21) PROVIDE LOCATION OF AND MANUFACTURER SPECIFICATIONS
 FOR GENERATOR.
  
 22) PLEASE SHOW LOCATION OF NEW FIRE HYDRANTS THAT
 SHALL BE OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 23) EXIT SIGN IS MISSING AT EXTERIOR CORRIDOR DOOR
 BETWEEN THE LOCKERS AND TOOL/EQUIPMENT ROOM. ELECTRICAL
 LIGHTING SHEET
  
 24) FIRE ALARM RISER DOES NOT APPEAR TO ILLUSTRATE
 SMOKE DETCTION DEVICES WITH EXCEPTION OF AIR DUCTS.
  
  
 A RESPONSE LETTER INDICATING HOW AND WHERE ON EACH
 SHEET EACH COMMENT WAS ADDRESSED WILL HELP EXPEDITE THE
 PLAN REVIEW PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  
  
  