| 2008-08-08 11:24:15 | ***DENIED*** |
| | |
| | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE |
| | SAFETY TO COMPLY WITH NFPA 101, 2003. |
| | |
| | 2) ADDRESS ON BUILDING SHALL BE MINIMUM 6" IN HEIGHT, |
| | 1" WIDTH AND CONTRASTING WITH BACKGROUND. PLEASE ADD TO |
| | ELEVATIONS. |
| | |
| | 3) KNOX BOX TO BE LOCATED AT WHAT IS CONSIDERED TO BE |
| | FRONT ENTRANCE TO BUILDING. CONTACT WPBFR BUREAU OF |
| | FIRE PREVENTION AT (561) 804-4724 FOR ASSISTANCE. |
| | |
| | 4) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR |
| | HANDRAILS AND GUARDS. |
| | |
| | 5) EMERGENCY VEHICLE ACCESS AND WATER SUPPLY TO COMPLY |
| | WITH NFPA 1, 2003, CHAPTER-18. |
| | |
| | 6) ELEVATOR SHALL COMPLY WITH REQUIREMENTS OF ASME |
| | A17.1. |
| | |
| | 7) FIRE RATED DOORS SHALL BE PROVIDED WITH UL LISTED |
| | DOOR CLOSERS TO CREATE POSITIVE LATCH. DOOR SCHEDULE ON |
| | SHEET A118C. |
| | |
| | 8) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR |
| | WALLS AND CEILING. |
| | |
| | 9) A FACTOR OF .2" PER PERSON HAS BEEN CALCULATED ON |
| | SHEET A901C FOR STAIRWAYS. PLEASE NOTE THAT TABLE |
| | 7.3.3.1 NFPA 101 USES A FACTOR OF 0.2" FOR LEVEL |
| | COMPONENTS AND RAMPS AND 0.3" FOR STAIRWAYS. THIS WILL |
| | HAVE AN OVERALL IMPACT ON CALCULATIONS. |
| | |
| | 10) PLEASE EXPLAIN FACTOR OF .15 FOR DOOR EGRESS. |
| | PLEASE NOTE LAST COMMENT REGARDING LEVEL COMPONENTS. |
| | |
| | 11) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY |
| | WITH REQUIREMENTS OF NFPA 241. |
| | |
| | 12) CLARIFY OCCUPANT CLASSIFICATION FOR EACH AREA. |
| | MODERATE HAZARD IS INDICATED IN CODE ANALYSIS UNDER USE |
| | OF OCCUPANCY. ADDITIONALLY, PLANS INDICATE VARIOUS |
| | PROCESSING AREAS WHICH SEEMS TO SUGGEST INDUSTRIAL |
| | USE. |
| | |
| | |
| | 13) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR |
| | FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
| | |
| | 14) FIRE ALRM SHALL BE UL CERTIFICATED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 15) PENETRATIONS INTO EXIT ENCLOSURES SHALL BE LIMITED |
| | AND IN COMPLIANCE WITH SEC. 7.1.3.2 (6), NFPA 101. |
| | SHEET M102C |
| | |
| | 16) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. |
| | |
| | 17) NEW FIRE DAMPERS TO BE TESTED FOR CLOSURE IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF UL 555. |
| | |
| | 18) PROVIDE MANUFACTURER SPECIFICATION SHEETS FOR |
| | PROPOSED FIRE PUMP. |
| | |
| | 19) KNOX LOCKING CAPS ARE REQUIRED FOR FIRE DEPARTMENT |
| | CONNECTION. SHEET FP 103C |
| | |
| | 20) PROVIDE DETAIL FOR DOUBLE CHECK DETECTOR ASSEMBLY. |
| | IN ADDITION TO ELECTRONIC SUPERVISION, CONTROL VALVES |
| | TO BE SECURED WITH CHAIN AND LOCK. |
| | |
| | 21) PROVIDE LOCATION OF AND MANUFACTURER SPECIFICATIONS |
| | FOR GENERATOR. |
| | |
| | 22) PLEASE SHOW LOCATION OF NEW FIRE HYDRANTS THAT |
| | SHALL BE OPERATIONAL PRIOR TO, DURING AND AFTER |
| | CONSTRUCTION. |
| | |
| | 23) EXIT SIGN IS MISSING AT EXTERIOR CORRIDOR DOOR |
| | BETWEEN THE LOCKERS AND TOOL/EQUIPMENT ROOM. ELECTRICAL |
| | LIGHTING SHEET |
| | |
| | 24) FIRE ALARM RISER DOES NOT APPEAR TO ILLUSTRATE |
| | SMOKE DETCTION DEVICES WITH EXCEPTION OF AIR DUCTS. |
| | |
| | |
| | A RESPONSE LETTER INDICATING HOW AND WHERE ON EACH |
| | SHEET EACH COMMENT WAS ADDRESSED WILL HELP EXPEDITE THE |
| | PLAN REVIEW PROCESS. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |