| 2008-08-01 08:26:49 | ** NOTE ADDED |
| | |
| | |
| | ** ALL CIRCUITING FOR EMEGENCY LIGHTING SHALL MEET |
| | 700.12F. MANY LOCATIONS ON PLANS DO NOT MEET THE |
| | EXCEPTIONS IN THE CODE. |
| 2008-07-30 16:29:24 | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | ** DENIEDAUDIT ** |
| | |
| | *** IT IS IMPORTANT TO KNOW THAT INFORMATION AND |
| | DOCUMENTATION NOT SUBMITTED DOES NOT COMPLETE PACKAGE |
| | FOR AUDIT AND DOES NOT PROVIDE THE MINIMUM REQUIRED BY |
| | THE FLORIDA BUILDING CODE AND ALL OTHER APPLICABLE LAWS |
| | AND ORDINANCES. |
| | |
| | 1) NOTE: *** PLEASE KNOW ALL PLANS AND DOCUMENTS WILL |
| | BE RETAINED BY THIS OFFICE. PLANS AND SUPPORTING |
| | DOCUMENTS MAY BE FORWARDED TO THE LICENSING BOARD FOR |
| | BUILDING CODE ADMINISTRATORS AND INSPECTORS BOARD ALONG |
| | WITH FLORIDA BOARD OF ENGINEERS FOR REVIEW OF SAID |
| | PLANS AND DOCUMENTS. |
| | |
| | 2) NOTE: PLEASE SEE THERE ARE SEVERAL DOCUMENTS IN |
| | PACKAGE SUBMITTED IN WHICH RAISED SEALS ARE PLACED OVER |
| | PHOTO-COPIED SIGNATURES AND DATES. THIS IS NOT |
| | PERMITTED UNDER FAC 61G15-23.002 AND FS 471.025. PLEASE |
| | KNOW THIS SAME COMPANY IN WHICH MANY OF THESE DOCUMENTS |
| | WERE DONE THIS MANOR HAS BEEN NOTIFIED ON PREVIOUS |
| | PROJECTS THAT THIS IS NOT ACCEPTABLE UNDER FLORIDA LAW |
| | HOWEVER THIS IS STILL BEING DONE. |
| | |
| | 3) NOTE:PLEASE PROVIDE AFFIDAVITS AS REQUIRED PER FS |
| | 553.791 FOR EACH TRADE WHERE EACH AFFIDAVIT ACTUALLY |
| | DOES LIST THE SHEETS. |
| | PLACING ONE AND NOTING SEE ATTACHED IS NOT ACCEPTABLE. |
| | |
| | |
| | 4 NOTE: PLEASE PROVIDE NOTICE TO BUILDING OFFICIAL AS |
| | REQUIRED. FS553.791 |
| | |
| | 5) NOTE: PLEASE DO NOT SUBMIT REVISION TO THE STAMPED |
| | PLANS WHEN THE |
| | |
| | 6) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS/LIGHTING |
| | PERFORMANCE CALCULATIONS PER 13-415.2.ABC.1.1, .1.2 AND |
| | .1.3. |
| | *** IT IS IMPORTANT TO KNOW THAT INFORMATION AND |
| | DOCUMENTATION IS NOT COMPLETE. |
| | |
| | 7) NOTE: PLEASE KNOW THE LIGHTING PROTECTION SYSTEM |
| | WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS AND SHALL |
| | CONTAIN NOTES AND DESIGN PER NFPA-780. |
| | |
| | 8) NOTE: AN AUDIT OF SIGNED, DATED AND SEALED |
| | ELECTRICAL PLANS WAS NOT DONE AS NONE OF THESE CONTAIN |
| | ANY STAMPS FROM THE PRIVATE PROVIDER. |
| | FS 553.791 |
| | |
| | 9) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3. PLEASE |
| | PROVIDE ALL MINIMUM LEVELS FOR FIRE ALARM DEVICES TO |
| | MEET ADA REQUIREMENTS. PLEASE BE SURE TO STATE THE |
| | LEVELS OF DEVICES. |
| | |
| | 10) NOTE: THE PLANS AND NOTES MENTIONS AUTOMATE |
| | LIGHTING CONTROL SYSTEMS WITH CONTACTORS HOWEVER |
| | COMPLETE DETAILS OF SYSTEMS, OVER RIDES, OVER RIDE |
| | TIMES ETC ARE NOT LOCATED ON PLANS. |
| | PLEASE SEE THERE ARE SEVERAL LOCATIONS INCLUDING |
| | MEZZANINE LIGHTING WHICH DO NOT INDICATE ANY LIGHTING |
| | CONTROLS FOR AUTOMATED SYSTEMS. THESE AREAS DO INDICATE |
| | STANDARD SWITCHING DEVICES WHICH DO NO MEET |
| | 13-415.1.ABC.1.1,.1.2, .1.3. |
| | PLEASE ALSO SEE OTHER LOCATIONS ON E-112 |
| | ** THIS IS NOT ALL LOCATIONS AS THERE ARE SEVERAL |
| | SECTIONS ON PLANS WHICH DO NOT MEET MINIMUM CODE |
| | |
| | 11) NOTE: PLEASE PROVIDE COMPLETE INFORMATION ON |
| | LIGHTING CONTROLS FOR EXTERIOR LIGHTING MEETING FBC |
| | 13-415.1.ABC.1.4 |
| | |
| | 11) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP PER |
| | 13-413.1.ABC.1.1, .1.2 |
| | |
| | 12) NOTE: PLEASE PROVIDE NOTES ON PLANS PER |
| | 13-413.1.ABC.2.1,.2.2. |
| | |
| | 13) NOTE: PLEASE SEE SOME AREAS AS NOTED ON SHEET E102 |
| | MENTION TO SEE E112, HOWEVER THESE SAME AREAS WHICH |
| | MENTION TO SEE ENLARGED PLANS ARE NOT SHOWN. PLEASE SEE |
| | SOME OF THESE AREAS ARE BREAK ROOM, BATHROOMS ETC WHICH |
| | ARE NOT ON E112. |
| | |
| | 14) NOTE: PLEASE COMPLETE AND COORDINATE ALL SYMBOLS ON |
| | PLANS. THIS INCLUDES ALL DEVICES SHOWN FOR LIGHTING |
| | CONTROLS WHICH ARE NOT ON SYMBOL LEGEND. AN EXAMPLE OF |
| | THIS IS SM. |
| | FBC 13-415, NEC ALL |
| | FBC 106.1.1 FOR CLARITY OF PLANS AND MINIMUM |
| | INFORMATION. 106.3.5.1.2 |
| | |
| | 15) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS TO MEET |
| | THE MINIMUM FOR LIFE SAFETY FOR ALL EGRESS PATHS. |
| | PLEASE SEE SOME AREAS SUCH AS STAIRS INCLUDING THAT OF |
| | EXTERIOR STAIRS DO NOT SHOW ANY BATTERY BACK UP |
| | LIGHTING AS REQUIRED. |
| | PLEASE SEE SECTIONS 7.8.1.3,7.9.2.1,79.2.2. |
| | FAC 61G15-33.004 |
| | ** EGRESS LIGHTING SHALL BE PROVIDED UNDER NORMAL AND |
| | EMERGENCY CONDITIONS OUT OF THE BUILDING. PLEASE BE |
| | SURE TO SEE THE LEVELS DID INCREASE UNDER THE 2003 |
| | NFPA-101 |
| | |
| | 16) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON ELECTRICAL PLANS AT A MINIMUM FOR THIS TRADE. FBC |
| | 2004 W/2007 REVISIONS. |
| | 2003 NFPA-101 |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-20 |
| | 2002 NFPA-110 |
| | |
| | 17) NOTE: PLEASE COMPLETE ALL INFORMATION ON PLANS FOR |
| | FIRE PUMP, FIRE PUMP CONTROLLER. PLEASE KNOW AS THE |
| | INFORMATION ON THE FP IS NOT COMPLETE PLEASE SUBMIT |
| | COMPLETE PLANS FOR MINIMUM. PLEASE KNOW THAT CHAPTERS |
| | OF THEN CODES WILL BE CITED NOT SECTIONS AS THERE TOO |
| | MANY SECTIONS OF THE CODE MISSING. |
| | PLEASE INDICATE LOCK ROTOR MAXIMUM OVER CURRENT |
| | PROTECTION. |
| | PLEASE SEE NFPA-70 695.4B1 (1) OVER-CURRENT DEVICE |
| | SELECTION THE OVER-CURRENT PROTECTIVE DEVICE(S) SHALL |
| | BE SELECTED OR SET TO CARRY INDEFINITELY THE SUM OF THE |
| | LOCKED-ROTOR CURRENT OF THE FIRE PUMP MOTOR(S) AND THE |
| | PRESSURE MAINTENANCE PUMP MOTOR(S) AND THE FULL-LOAD |
| | CURRENT OF THE ASSOCIATED FIRE PUMP ACCESSORY EQUIPMENT |
| | WHEN CONNECTED TO THIS POWER SUPPLY. THE REQUIREMENT TO |
| | CARRY THE LOCKED-ROTOR CURRENTS INDEFINITELY SHALL NOT |
| | APPLY TO CONDUCTORS OR DEVICES OTHER THAN OVER-CURRENT |
| | DEVICES IN THE FIRE PUMP MOTOR CIRCUIT(S). |
| | |
| | PLEASE SEE NFPA-20 CHAPTERS 9, 10 ETC |
| | PLEASE SUBMIT MANUFACTURES SPEC/CUT SHEETS FOR THE FIRE |
| | PUMP AND FIRE PUMP CONTROLLER. |
| | 110.3,90.7, NFPA-20. |
| | ** AS PLANS AND INFORMATION IS NOT COMPLETE MANY ITEMS |
| | FOR MINIMUM CODE COMPLIANCE CAN NOT BE DETERMINED AT |
| | THIS TIME. |
| | |
| | 18) NOTE: PLEASE SEE 230.2 AS THE NUMBER OF SERVICES |
| | SHOWN ON PLANS ARE NOT PERMITTED AND NOT ALL MEET THE |
| | EXCEPTIONS IN THE CODE AT THIS TIME. |
| | PLEASE LOOK AT RISER AS THE EQUIPMENT FED FROM MSB ARE |
| | BEING NOTED AS *MAINS*. |
| | |
| | 19) NOTE: PLEASE SEE 230.95, 240.13 AS THE 3000AMP MAIN |
| | INDICATE GFIC PROTECTION. SHOULD THIS NOT BE GFP FOR |
| | GROUND FAULT PROTECTION? GFCI IS FOR PERSONNEL. |
| | |
| | 20) NOTE: PLEASE SUBMIT AND SHOW A COMPLETE GROUNDING |
| | ELECTRODE RISER FOR ALL TRANSFORMERS AND COMMON |
| | SYSTEM. |
| | 250.58, 250.66 |
| | |
| | 21) NOTE: PLEASE SEE THERE ARE LOCATIONS WHERE |
| | EQUIPMENT GROUNDING CONDUCTORS ARE BEING SHOWN BEFORE |
| | THE FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED. |
| | PLEASE CLARIFY THE #4 TO FIRE PUMP CONTROLLER. PLEASE |
| | BE SURE TO SIZE THE NEUTRAL (GROUNDED CONDUCTOR) AS |
| | THIS IS REQUIRED TO CONTAIN A NEUTRAL TO THE FIRST |
| | MEANS OF DISCONNECT. IN NO CASE MAY THIS BE SMALLER |
| | THAN THE GROUNDING ELECTRODE |
| | CONDUCTOR.250.4,250.6,250.50,ETC |
| | THIS IS ALSO NOTED FOR THE 3000AMP MAIN AS AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS ALSO SHOWN BEFORE THE FIRST |
| | MEANS OF DISCONNECT WHICH IS NOT PERMITTED. THIS |
| | CREATES OBJECTIONABLE CURRENTS. |
| | |
| | 22) NOTE: PLEASE SEE 230.95, 240.13, 700.7D, 700.26, |
| | NFPA-110 6.2.1.5 |
| | AS THE TRANSFER SWITCH ON PLANS DOES NOT INDICATE HOW |
| | MANY POLES. BASED ON THE CODE SECTIONS GIVEN THIS IS |
| | REQUIRED TO BE A FOUR POLE UNIT. THE FOLLOWING TEXT MAY |
| | BE OF USE FOR THE TRANSFER SWITCH. THIS WORDING IS FROM |
| | ONE WHITE PAPER FROM ONE MANUFACTURE AND THERE ARE |
| | SEVERAL OTHERS AVAILABLE. |
| | |
| | *WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE CODE |
| | AND AN ALTERNATE POWER SUPPLY IS INCLUDED, SWITCHING OF |
| | THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT SHOWN ABOVE |
| | ILLUSTRATES SUCH A CIRCUMSTANCE. |
| | THE SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, |
| | GROUND FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE |
| | DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND |
| | THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID |
| | CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT |
| | WHEN THE GENERATOR IS FEEDING |
| | THE LOAD WILL CAUSE THE MAIN SERVICE DISCONNECT TO |
| | OPEN. THIS WILL NOT DISCONNECT THE ARCING FAULT FROM |
| | THE GENERATOR. COORDINATION IS THUS LOST.* |
| | |
| | THIS WAS FROM ASCO WHITE PAPER PAGE #5. OTHERS SUCH AS |
| | CATERPILLAR ETC HAVE MUCH OF THE SAME. |
| | |
| | |
| | 23) NOTE: PLEASE SEE NFPA-110 9.6.2.2 AND INDICATE THE |
| | MINIMUM TIMES FOR ON-SITE FUEL AS REQUIRED FOR POWER |
| | FOR FIRE PUMP ALONG WITH OTHER EMERGENCY LOADS. 9.6.2.2 |
| | THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT TO PROVIDE |
| | 8 HOURS OF FIRE PUMP OPERATION AT 100 PERCENT OF THE |
| | RATED PUMP CAPACITY IN ADDITION TO THE SUPPLY REQUIRED |
| | FOR OTHER DEMANDS. |
| | |
| | |
| | 24) NOTE: PLEASE KNOW BATTERY BACK UP LIGHTING SHALL BE |
| | REQUIRED FOR THE EGRESS LIGHTING PATHS PER NFPA-7.8, |
| | 7.9.PLEASE KNOW THIS BUILDING SHALL NOT RELY ON THE |
| | SINGLE TRIPPING OF A BREAKER, SWITCHING OF A DEVICE TO |
| | LEAVE ANY ONE ARE IN TOTAL DARKNESS. |
| | PLEASE BE SURE OTHER LOCATIONS SUCH AS THE MAIN |
| | ELECTRICAL ROOM, FIRE PUMP ROOM, ELEVATOR EQUIPMENT |
| | ROOM ALSO CONTAIN BATTERY BACK UP LIGHTING. |
| | |
| | 25) NOTE: PLEASE SUBMIT THE PLANS WITH THE COMPLETED |
| | INFORMATION FOR LOCATION OF THE GENERATOR. THE RISER |
| | SHOWS A GENERATOR HOWEVER WHERE IS THIS UNIT GOING TO |
| | BE INSTALLED? PLEASE SEE OTHER PLANS SUCH AS SITE, |
| | MECHANICAL, BUILDING ETC DO NOT SHOW ANY LOCATIONS. |
| | |
| | 26) NOTE: PLEASE SEE NEC 645.,23AS THE MINIMUM |
| | REQUIRED DEDICATED CIRCUITS ARE NOT LOCATED ON PLANS. |
| | IN FACT ONE EXAMPLE OF NON-COMPLIANCE IS THE FACT THE |
| | LIGHTING IN THE MACHINE ROOM WHICH IS REQUIRED TO BE ON |
| | A DEDICATED CIRCUIT PER 620.23 IS SHOWN CIRCUITED TO |
| | OTHER NORMAL LIGHTING OUTSIDE OF THIS ROOM. |
| | PANEL SCHEDULE INDICATES OTHERS PER 620.22, 620.24 |
| | HOWEVER PLANS DO NOT SHOW SOME OF THESE CIRCUITS, |
| | LIGHTS, PIT LIGHTING, GFI RECEPTACLES ETC. RECEPT SHOWN |
| | HOWEVER SECTIONS AS NOTED REQUIRE GFCI PROTECTION. THIS |
| | IS NO ON PLANS OR ON PANEL SCHEDULE |
| | IF THE PANEL SCHEDULE ONLY INDICATES *RECEPTACLES FOR |
| | EXAMPLE ON RP1-16 THE DEDICATE CIRCUIT IS NOT |
| | DETERMINED |
| | |
| | |
| | 27) NOTE: PLEASE SEE NFPA-110 CHAPTER 7, 7.3.3 AS THE |
| | MINIMUM LIGHTING IN ANY GENERATOR ROOM SHALL MEET THIS |
| | MINIMUM. |
| | PLEASE KEEP IN MIND AS THE GENERATOR IS NOT SHOWN THIS |
| | IS GIVEN FOR INFORMATION ONLY. |
| | PLEASE SEE THE FOLLOWING FOR LOCATION AS THIS WAS NOT |
| | SHOWN AT THIS TIME. |
| | |
| | 7.2 LOCATION. |
| | 7.2.1 THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR |
| | LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE |
| | PERMITTED TO BE INSTALLED IN THIS ROOM. |
| | 7.2.1.1 THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE |
| | RATING OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED |
| | OUTSIDE THE BUILDING CAPABLE OF RESISTING THE ENTRANCE |
| | OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY |
| | LOCAL BUILDING CODES. |
| | 7.2.1.2 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL |
| | APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE, |
| | SHALL BE PERMITTED IN THIS ROOM. |
| | 7.2.2 EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME |
| | ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS |
| | INSTALLED. |
| | 7.2.2.1 TRANSFER SWITCHES SHALL BE PERMITTED TO BE |
| | INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE |
| | TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF |
| | NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN |
| | EQUIPMENT ENCLOSURES. |
| | 7.2.3*THE ROOMS, SHELTERS, OR SEPARATE BUILDINGS |
| | HOUSING LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE |
| | DESIGNED AND LOCATED TO MINIMIZE THE DAMAGE FROM |
| | FLOODING, INCLUDING THAT CAUSED BY THE FOLLOWING: (1) |
| | FLOODING RESULTING FROM FIRE FIGHTING |
| | (2)SEWER WATER BACKUP |
| | (3)SIMILAR DISASTERS OR OCCURRENCES |
| | 7.2.4*MINIMIZING THE POSSIBILITY OF DAMAGE RESULTING |
| | FROM INTERRUPTIONS OF THE EMERGENCY SOURCE SHALL BE A |
| | DESIGN CONSIDERATION FOR LEVEL 1 AND LEVEL 2 EPSS |
| | EQUIPMENT. |
| | 7.2.5 THE EPS EQUIPMENT SHALL BE INSTALLED IN A |
| | LOCATION THAT PERMITS READY ACCESSIBILITY AND A MINIMUM |
| | OF 76 CM (30 IN.) FROM THE SKID RAILS' OUTERMOST POINT |
| | IN THE DIRECTION OF ACCESS FOR INSPECTION, REPAIR, |
| | MAINTENANCE, CLEANING, OR REPLACEMENT. THIS REQUIREMENT |
| | SHALL NOT APPLY TO UNITS IN OUTDOOR HOUSINGS. |
| | |
| | 28) NOTE: PLEASE SEE 450.3 AS THE MAXIMUM OVER CURRENT |
| | PROTECTION ON THE TRANSFORMER TRP1 SHALL BE 125% UNLESS |
| | MEETING EXCEPTIONS. AS THE PLANS DO NOT INDICATE WHAT |
| | TYPE OF UNIT THIS IS PLEASE SEE SECTION AS NOTED. |
| | |
| | 29) NOTE: PLEASE SEE 408.4 AS THE CIRCUITS SHOWN ON |
| | PANEL SCHEDULES SHALL BE SPECIFIC TO ROOMS AND AREAS IN |
| | WHICH THEY FEED. STATING *RECEPTACLES* OR *LIGHTING* IS |
| | NOT ACCEPTABLE. PLEASE KNOW A NUMERICAL OR ALPHA |
| | DESIGNATION MAY BE USED. |
| | |
| | 30) NOTE: PLEASE INCLUDE FOOTER STEEL AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 250.50. |
| | |
| | 31) NOTE: PLEASE SEE RISER AS ERP1 INDICATES A FEED TO |
| | PANEL ERPSH HOWEVER THE PANEL SCHEDULE FOR ERP1 DOES |
| | NOT INDICATE ANY SUB FEED FOR PANEL ERPSH. |
| | PLEASE COMPLETE WITH OCP, CONDUCTORS, LOADS ETC. |
| | 408.4,310.16,240.4,220,ETC |
| | |
| | 32) NOTE: PLEASE SUBMIT AND SHOW COMPLETE LOAD |
| | CALCULATIONS PER NEC 220. |
| | PLEASE BE SURE ALL CONTINUOUS LOADS ALONG WITH LARGEST |
| | MOTOR LOADS ARE FIGURED SHOWN AT 125%. |
| | PLEASE BE SURE THE WATER HEATER LOADS ARE FIGURED AND |
| | SHOWN AT 125%. 220,12,220.14,220.42,,220.44,220.50, ETC |
| | 215.3,230.42, 422.13 FOR CONTINUOUS LOADS. |
| | FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND MINIMUM |
| | REQUIRED ON PLANS. |
| | |
| | 33) NOTE: PLEASE SEER RISER AS LPSH INDICATES A FEED TO |
| | PANEL RPSH YET THERE IS NO BREAKER, LOAD, CIRCUIT |
| | LISTED ON PANEL LPSH FOR THIS NEW PANEL. |
| | PLEASE COMPLETE. |
| | 240.4,220,310.16 ETC |
| | |
| | 34) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE |
| | RISER/DIAGRAM FOR SCALE HOUSE PER |
| | 250.50,250.30,250.32. |
| | |
| | 35) NOTE: PLEASE SEE THE RISER SHOWS THE TRANSFORMER AT |
| | THE SCALE HOUSE AS TRP-SH WHICH BY THE TRANSFORMER |
| | CALLS FOR THIS UNIT AS A 30KVA UNIT YET THE LEGEND AND |
| | PLANS ON SHEET E-112 INDICATES THIS SAME UNIT AT THE |
| | SCALE HOUSE IS SHOWN AS 15KVA. |
| | PLEASE KNOW AS BOTH UNITS ARE SHOWN WITH TWO DIFFERENT |
| | SIZES THE OVER CURRENT PROTECTION ETC CAN NOT BE |
| | DETERMINED AS CODE COMPLIANT. |
| | PLEASE COORDINATE |
| | 450.3, 240.21, 310.16, 240.4 ETC. |
| | |
| | 36) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM PART ROOM |
| | PLAN WHICH INDICATES ANOTHER 15KVA TRANSFORMER YET THE |
| | ELECTRICAL TRANSFORMER LEGEND ON SHEET ON E-107 DOES |
| | NOT INDICATE ANY 15K TRANSFORMERS. AS THESE DOE NOT |
| | COORDINATE DETERMINATION FOR CODE COMPLIANCE CAN NOT BE |
| | DONE. |
| | 240.21,450.3,310.16 ETC |
| | FBC 106.1.1 FOR COORDINATION AND CLARITY OF PLANS. |
| | |
| | 37) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS ON THE ATS, GENERATOR, AS NOTED ABOVE FOR OTHER |
| | EQUIPMENT. 110.3,90.7 |
| | |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION AND |
| | DOCUMENTATION NOT YET SUBMITTED FOR AUDIT THERE MAY |
| | VERY WELL BE NEW COMMENTS ON THE FOLLOWING AUDIT WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE |
| | NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |