Plan Review Notes
Plan Review Notes For Permit 08070320
Permit Number 08070320
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-01 08:26:49** NOTE ADDED
  
  
 ** ALL CIRCUITING FOR EMEGENCY LIGHTING SHALL MEET
 700.12F. MANY LOCATIONS ON PLANS DO NOT MEET THE
 EXCEPTIONS IN THE CODE.
2008-07-30 16:29:24 
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 ** DENIEDAUDIT **
  
 *** IT IS IMPORTANT TO KNOW THAT INFORMATION AND
 DOCUMENTATION NOT SUBMITTED DOES NOT COMPLETE PACKAGE
 FOR AUDIT AND DOES NOT PROVIDE THE MINIMUM REQUIRED BY
 THE FLORIDA BUILDING CODE AND ALL OTHER APPLICABLE LAWS
 AND ORDINANCES.
  
 1) NOTE: *** PLEASE KNOW ALL PLANS AND DOCUMENTS WILL
 BE RETAINED BY THIS OFFICE. PLANS AND SUPPORTING
 DOCUMENTS MAY BE FORWARDED TO THE LICENSING BOARD FOR
 BUILDING CODE ADMINISTRATORS AND INSPECTORS BOARD ALONG
 WITH FLORIDA BOARD OF ENGINEERS FOR REVIEW OF SAID
 PLANS AND DOCUMENTS.
  
 2) NOTE: PLEASE SEE THERE ARE SEVERAL DOCUMENTS IN
 PACKAGE SUBMITTED IN WHICH RAISED SEALS ARE PLACED OVER
 PHOTO-COPIED SIGNATURES AND DATES. THIS IS NOT
 PERMITTED UNDER FAC 61G15-23.002 AND FS 471.025. PLEASE
 KNOW THIS SAME COMPANY IN WHICH MANY OF THESE DOCUMENTS
 WERE DONE THIS MANOR HAS BEEN NOTIFIED ON PREVIOUS
 PROJECTS THAT THIS IS NOT ACCEPTABLE UNDER FLORIDA LAW
 HOWEVER THIS IS STILL BEING DONE.
  
 3) NOTE:PLEASE PROVIDE AFFIDAVITS AS REQUIRED PER FS
 553.791 FOR EACH TRADE WHERE EACH AFFIDAVIT ACTUALLY
 DOES LIST THE SHEETS.
 PLACING ONE AND NOTING SEE ATTACHED IS NOT ACCEPTABLE.
  
  
 4 NOTE: PLEASE PROVIDE NOTICE TO BUILDING OFFICIAL AS
 REQUIRED. FS553.791
  
 5) NOTE: PLEASE DO NOT SUBMIT REVISION TO THE STAMPED
 PLANS WHEN THE
  
 6) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS/LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2.ABC.1.1, .1.2 AND
 .1.3.
 *** IT IS IMPORTANT TO KNOW THAT INFORMATION AND
 DOCUMENTATION IS NOT COMPLETE.
  
 7) NOTE: PLEASE KNOW THE LIGHTING PROTECTION SYSTEM
 WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS AND SHALL
 CONTAIN NOTES AND DESIGN PER NFPA-780.
  
 8) NOTE: AN AUDIT OF SIGNED, DATED AND SEALED
 ELECTRICAL PLANS WAS NOT DONE AS NONE OF THESE CONTAIN
 ANY STAMPS FROM THE PRIVATE PROVIDER.
 FS 553.791
  
 9) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3. PLEASE
 PROVIDE ALL MINIMUM LEVELS FOR FIRE ALARM DEVICES TO
 MEET ADA REQUIREMENTS. PLEASE BE SURE TO STATE THE
 LEVELS OF DEVICES.
  
 10) NOTE: THE PLANS AND NOTES MENTIONS AUTOMATE
 LIGHTING CONTROL SYSTEMS WITH CONTACTORS HOWEVER
 COMPLETE DETAILS OF SYSTEMS, OVER RIDES, OVER RIDE
 TIMES ETC ARE NOT LOCATED ON PLANS.
 PLEASE SEE THERE ARE SEVERAL LOCATIONS INCLUDING
 MEZZANINE LIGHTING WHICH DO NOT INDICATE ANY LIGHTING
 CONTROLS FOR AUTOMATED SYSTEMS. THESE AREAS DO INDICATE
 STANDARD SWITCHING DEVICES WHICH DO NO MEET
 13-415.1.ABC.1.1,.1.2, .1.3.
 PLEASE ALSO SEE OTHER LOCATIONS ON E-112
 ** THIS IS NOT ALL LOCATIONS AS THERE ARE SEVERAL
 SECTIONS ON PLANS WHICH DO NOT MEET MINIMUM CODE
  
 11) NOTE: PLEASE PROVIDE COMPLETE INFORMATION ON
 LIGHTING CONTROLS FOR EXTERIOR LIGHTING MEETING FBC
 13-415.1.ABC.1.4
  
 11) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1.ABC.1.1, .1.2
  
 12) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.1.ABC.2.1,.2.2.
  
 13) NOTE: PLEASE SEE SOME AREAS AS NOTED ON SHEET E102
 MENTION TO SEE E112, HOWEVER THESE SAME AREAS WHICH
 MENTION TO SEE ENLARGED PLANS ARE NOT SHOWN. PLEASE SEE
 SOME OF THESE AREAS ARE BREAK ROOM, BATHROOMS ETC WHICH
 ARE NOT ON E112.
  
 14) NOTE: PLEASE COMPLETE AND COORDINATE ALL SYMBOLS ON
 PLANS. THIS INCLUDES ALL DEVICES SHOWN FOR LIGHTING
 CONTROLS WHICH ARE NOT ON SYMBOL LEGEND. AN EXAMPLE OF
 THIS IS SM.
 FBC 13-415, NEC ALL
 FBC 106.1.1 FOR CLARITY OF PLANS AND MINIMUM
 INFORMATION. 106.3.5.1.2
  
 15) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS TO MEET
 THE MINIMUM FOR LIFE SAFETY FOR ALL EGRESS PATHS.
 PLEASE SEE SOME AREAS SUCH AS STAIRS INCLUDING THAT OF
 EXTERIOR STAIRS DO NOT SHOW ANY BATTERY BACK UP
 LIGHTING AS REQUIRED.
 PLEASE SEE SECTIONS 7.8.1.3,7.9.2.1,79.2.2.
 FAC 61G15-33.004
 ** EGRESS LIGHTING SHALL BE PROVIDED UNDER NORMAL AND
 EMERGENCY CONDITIONS OUT OF THE BUILDING. PLEASE BE
 SURE TO SEE THE LEVELS DID INCREASE UNDER THE 2003
 NFPA-101
  
 16) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON ELECTRICAL PLANS AT A MINIMUM FOR THIS TRADE. FBC
 2004 W/2007 REVISIONS.
 2003 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-20
 2002 NFPA-110
  
 17) NOTE: PLEASE COMPLETE ALL INFORMATION ON PLANS FOR
 FIRE PUMP, FIRE PUMP CONTROLLER. PLEASE KNOW AS THE
 INFORMATION ON THE FP IS NOT COMPLETE PLEASE SUBMIT
 COMPLETE PLANS FOR MINIMUM. PLEASE KNOW THAT CHAPTERS
 OF THEN CODES WILL BE CITED NOT SECTIONS AS THERE TOO
 MANY SECTIONS OF THE CODE MISSING.
 PLEASE INDICATE LOCK ROTOR MAXIMUM OVER CURRENT
 PROTECTION.
 PLEASE SEE NFPA-70 695.4B1 (1) OVER-CURRENT DEVICE
 SELECTION THE OVER-CURRENT PROTECTIVE DEVICE(S) SHALL
 BE SELECTED OR SET TO CARRY INDEFINITELY THE SUM OF THE
 LOCKED-ROTOR CURRENT OF THE FIRE PUMP MOTOR(S) AND THE
 PRESSURE MAINTENANCE PUMP MOTOR(S) AND THE FULL-LOAD
 CURRENT OF THE ASSOCIATED FIRE PUMP ACCESSORY EQUIPMENT
 WHEN CONNECTED TO THIS POWER SUPPLY. THE REQUIREMENT TO
 CARRY THE LOCKED-ROTOR CURRENTS INDEFINITELY SHALL NOT
 APPLY TO CONDUCTORS OR DEVICES OTHER THAN OVER-CURRENT
 DEVICES IN THE FIRE PUMP MOTOR CIRCUIT(S).
  
 PLEASE SEE NFPA-20 CHAPTERS 9, 10 ETC
 PLEASE SUBMIT MANUFACTURES SPEC/CUT SHEETS FOR THE FIRE
 PUMP AND FIRE PUMP CONTROLLER.
 110.3,90.7, NFPA-20.
 ** AS PLANS AND INFORMATION IS NOT COMPLETE MANY ITEMS
 FOR MINIMUM CODE COMPLIANCE CAN NOT BE DETERMINED AT
 THIS TIME.
  
 18) NOTE: PLEASE SEE 230.2 AS THE NUMBER OF SERVICES
 SHOWN ON PLANS ARE NOT PERMITTED AND NOT ALL MEET THE
 EXCEPTIONS IN THE CODE AT THIS TIME.
 PLEASE LOOK AT RISER AS THE EQUIPMENT FED FROM MSB ARE
 BEING NOTED AS *MAINS*.
  
 19) NOTE: PLEASE SEE 230.95, 240.13 AS THE 3000AMP MAIN
 INDICATE GFIC PROTECTION. SHOULD THIS NOT BE GFP FOR
 GROUND FAULT PROTECTION? GFCI IS FOR PERSONNEL.
  
 20) NOTE: PLEASE SUBMIT AND SHOW A COMPLETE GROUNDING
 ELECTRODE RISER FOR ALL TRANSFORMERS AND COMMON
 SYSTEM.
 250.58, 250.66
  
 21) NOTE: PLEASE SEE THERE ARE LOCATIONS WHERE
 EQUIPMENT GROUNDING CONDUCTORS ARE BEING SHOWN BEFORE
 THE FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE CLARIFY THE #4 TO FIRE PUMP CONTROLLER. PLEASE
 BE SURE TO SIZE THE NEUTRAL (GROUNDED CONDUCTOR) AS
 THIS IS REQUIRED TO CONTAIN A NEUTRAL TO THE FIRST
 MEANS OF DISCONNECT. IN NO CASE MAY THIS BE SMALLER
 THAN THE GROUNDING ELECTRODE
 CONDUCTOR.250.4,250.6,250.50,ETC
 THIS IS ALSO NOTED FOR THE 3000AMP MAIN AS AN EQUIPMENT
 GROUNDING CONDUCTOR IS ALSO SHOWN BEFORE THE FIRST
 MEANS OF DISCONNECT WHICH IS NOT PERMITTED. THIS
 CREATES OBJECTIONABLE CURRENTS.
  
 22) NOTE: PLEASE SEE 230.95, 240.13, 700.7D, 700.26,
 NFPA-110 6.2.1.5
 AS THE TRANSFER SWITCH ON PLANS DOES NOT INDICATE HOW
 MANY POLES. BASED ON THE CODE SECTIONS GIVEN THIS IS
 REQUIRED TO BE A FOUR POLE UNIT. THE FOLLOWING TEXT MAY
 BE OF USE FOR THE TRANSFER SWITCH. THIS WORDING IS FROM
 ONE WHITE PAPER FROM ONE MANUFACTURE AND THERE ARE
 SEVERAL OTHERS AVAILABLE.
  
 *WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE CODE
 AND AN ALTERNATE POWER SUPPLY IS INCLUDED, SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT SHOWN ABOVE
 ILLUSTRATES SUCH A CIRCUMSTANCE.
 THE SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY,
 GROUND FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR IS FEEDING
 THE LOAD WILL CAUSE THE MAIN SERVICE DISCONNECT TO
 OPEN. THIS WILL NOT DISCONNECT THE ARCING FAULT FROM
 THE GENERATOR. COORDINATION IS THUS LOST.*
  
 THIS WAS FROM ASCO WHITE PAPER PAGE #5. OTHERS SUCH AS
 CATERPILLAR ETC HAVE MUCH OF THE SAME.
  
  
 23) NOTE: PLEASE SEE NFPA-110 9.6.2.2 AND INDICATE THE
 MINIMUM TIMES FOR ON-SITE FUEL AS REQUIRED FOR POWER
 FOR FIRE PUMP ALONG WITH OTHER EMERGENCY LOADS. 9.6.2.2
 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT TO PROVIDE
 8 HOURS OF FIRE PUMP OPERATION AT 100 PERCENT OF THE
 RATED PUMP CAPACITY IN ADDITION TO THE SUPPLY REQUIRED
 FOR OTHER DEMANDS.
  
  
 24) NOTE: PLEASE KNOW BATTERY BACK UP LIGHTING SHALL BE
 REQUIRED FOR THE EGRESS LIGHTING PATHS PER NFPA-7.8,
 7.9.PLEASE KNOW THIS BUILDING SHALL NOT RELY ON THE
 SINGLE TRIPPING OF A BREAKER, SWITCHING OF A DEVICE TO
 LEAVE ANY ONE ARE IN TOTAL DARKNESS.
 PLEASE BE SURE OTHER LOCATIONS SUCH AS THE MAIN
 ELECTRICAL ROOM, FIRE PUMP ROOM, ELEVATOR EQUIPMENT
 ROOM ALSO CONTAIN BATTERY BACK UP LIGHTING.
  
 25) NOTE: PLEASE SUBMIT THE PLANS WITH THE COMPLETED
 INFORMATION FOR LOCATION OF THE GENERATOR. THE RISER
 SHOWS A GENERATOR HOWEVER WHERE IS THIS UNIT GOING TO
 BE INSTALLED? PLEASE SEE OTHER PLANS SUCH AS SITE,
 MECHANICAL, BUILDING ETC DO NOT SHOW ANY LOCATIONS.
  
 26) NOTE: PLEASE SEE NEC 645.,23AS THE MINIMUM
 REQUIRED DEDICATED CIRCUITS ARE NOT LOCATED ON PLANS.
 IN FACT ONE EXAMPLE OF NON-COMPLIANCE IS THE FACT THE
 LIGHTING IN THE MACHINE ROOM WHICH IS REQUIRED TO BE ON
 A DEDICATED CIRCUIT PER 620.23 IS SHOWN CIRCUITED TO
 OTHER NORMAL LIGHTING OUTSIDE OF THIS ROOM.
 PANEL SCHEDULE INDICATES OTHERS PER 620.22, 620.24
 HOWEVER PLANS DO NOT SHOW SOME OF THESE CIRCUITS,
 LIGHTS, PIT LIGHTING, GFI RECEPTACLES ETC. RECEPT SHOWN
 HOWEVER SECTIONS AS NOTED REQUIRE GFCI PROTECTION. THIS
 IS NO ON PLANS OR ON PANEL SCHEDULE
 IF THE PANEL SCHEDULE ONLY INDICATES *RECEPTACLES FOR
 EXAMPLE ON RP1-16 THE DEDICATE CIRCUIT IS NOT
 DETERMINED
  
  
 27) NOTE: PLEASE SEE NFPA-110 CHAPTER 7, 7.3.3 AS THE
 MINIMUM LIGHTING IN ANY GENERATOR ROOM SHALL MEET THIS
 MINIMUM.
 PLEASE KEEP IN MIND AS THE GENERATOR IS NOT SHOWN THIS
 IS GIVEN FOR INFORMATION ONLY.
 PLEASE SEE THE FOLLOWING FOR LOCATION AS THIS WAS NOT
 SHOWN AT THIS TIME.
  
 7.2 LOCATION.
 7.2.1 THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR
 LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE
 PERMITTED TO BE INSTALLED IN THIS ROOM.
 7.2.1.1 THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE
 RATING OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED
 OUTSIDE THE BUILDING CAPABLE OF RESISTING THE ENTRANCE
 OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY
 LOCAL BUILDING CODES.
 7.2.1.2 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
 7.2.2 EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME
 ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS
 INSTALLED.
 7.2.2.1 TRANSFER SWITCHES SHALL BE PERMITTED TO BE
 INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE
 TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF
 NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN
 EQUIPMENT ENCLOSURES.
 7.2.3*THE ROOMS, SHELTERS, OR SEPARATE BUILDINGS
 HOUSING LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE
 DESIGNED AND LOCATED TO MINIMIZE THE DAMAGE FROM
 FLOODING, INCLUDING THAT CAUSED BY THE FOLLOWING: (1)
 FLOODING RESULTING FROM FIRE FIGHTING
 (2)SEWER WATER BACKUP
 (3)SIMILAR DISASTERS OR OCCURRENCES
 7.2.4*MINIMIZING THE POSSIBILITY OF DAMAGE RESULTING
 FROM INTERRUPTIONS OF THE EMERGENCY SOURCE SHALL BE A
 DESIGN CONSIDERATION FOR LEVEL 1 AND LEVEL 2 EPSS
 EQUIPMENT.
 7.2.5 THE EPS EQUIPMENT SHALL BE INSTALLED IN A
 LOCATION THAT PERMITS READY ACCESSIBILITY AND A MINIMUM
 OF 76 CM (30 IN.) FROM THE SKID RAILS' OUTERMOST POINT
 IN THE DIRECTION OF ACCESS FOR INSPECTION, REPAIR,
 MAINTENANCE, CLEANING, OR REPLACEMENT. THIS REQUIREMENT
 SHALL NOT APPLY TO UNITS IN OUTDOOR HOUSINGS.
  
 28) NOTE: PLEASE SEE 450.3 AS THE MAXIMUM OVER CURRENT
 PROTECTION ON THE TRANSFORMER TRP1 SHALL BE 125% UNLESS
 MEETING EXCEPTIONS. AS THE PLANS DO NOT INDICATE WHAT
 TYPE OF UNIT THIS IS PLEASE SEE SECTION AS NOTED.
  
 29) NOTE: PLEASE SEE 408.4 AS THE CIRCUITS SHOWN ON
 PANEL SCHEDULES SHALL BE SPECIFIC TO ROOMS AND AREAS IN
 WHICH THEY FEED. STATING *RECEPTACLES* OR *LIGHTING* IS
 NOT ACCEPTABLE. PLEASE KNOW A NUMERICAL OR ALPHA
 DESIGNATION MAY BE USED.
  
 30) NOTE: PLEASE INCLUDE FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 250.50.
  
 31) NOTE: PLEASE SEE RISER AS ERP1 INDICATES A FEED TO
 PANEL ERPSH HOWEVER THE PANEL SCHEDULE FOR ERP1 DOES
 NOT INDICATE ANY SUB FEED FOR PANEL ERPSH.
 PLEASE COMPLETE WITH OCP, CONDUCTORS, LOADS ETC.
 408.4,310.16,240.4,220,ETC
  
 32) NOTE: PLEASE SUBMIT AND SHOW COMPLETE LOAD
 CALCULATIONS PER NEC 220.
 PLEASE BE SURE ALL CONTINUOUS LOADS ALONG WITH LARGEST
 MOTOR LOADS ARE FIGURED SHOWN AT 125%.
 PLEASE BE SURE THE WATER HEATER LOADS ARE FIGURED AND
 SHOWN AT 125%. 220,12,220.14,220.42,,220.44,220.50, ETC
 215.3,230.42, 422.13 FOR CONTINUOUS LOADS.
 FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND MINIMUM
 REQUIRED ON PLANS.
  
 33) NOTE: PLEASE SEER RISER AS LPSH INDICATES A FEED TO
 PANEL RPSH YET THERE IS NO BREAKER, LOAD, CIRCUIT
 LISTED ON PANEL LPSH FOR THIS NEW PANEL.
 PLEASE COMPLETE.
 240.4,220,310.16 ETC
  
 34) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE
 RISER/DIAGRAM FOR SCALE HOUSE PER
 250.50,250.30,250.32.
  
 35) NOTE: PLEASE SEE THE RISER SHOWS THE TRANSFORMER AT
 THE SCALE HOUSE AS TRP-SH WHICH BY THE TRANSFORMER
 CALLS FOR THIS UNIT AS A 30KVA UNIT YET THE LEGEND AND
 PLANS ON SHEET E-112 INDICATES THIS SAME UNIT AT THE
 SCALE HOUSE IS SHOWN AS 15KVA.
 PLEASE KNOW AS BOTH UNITS ARE SHOWN WITH TWO DIFFERENT
 SIZES THE OVER CURRENT PROTECTION ETC CAN NOT BE
 DETERMINED AS CODE COMPLIANT.
 PLEASE COORDINATE
 450.3, 240.21, 310.16, 240.4 ETC.
  
 36) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM PART ROOM
 PLAN WHICH INDICATES ANOTHER 15KVA TRANSFORMER YET THE
 ELECTRICAL TRANSFORMER LEGEND ON SHEET ON E-107 DOES
 NOT INDICATE ANY 15K TRANSFORMERS. AS THESE DOE NOT
 COORDINATE DETERMINATION FOR CODE COMPLIANCE CAN NOT BE
 DONE.
 240.21,450.3,310.16 ETC
 FBC 106.1.1 FOR COORDINATION AND CLARITY OF PLANS.
  
 37) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE ATS, GENERATOR, AS NOTED ABOVE FOR OTHER
 EQUIPMENT. 110.3,90.7
  
  
 ** PLEASE KNOW AS THERE IS INFORMATION AND
 DOCUMENTATION NOT YET SUBMITTED FOR AUDIT THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING AUDIT WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]