Plan Review Notes
Plan Review Notes For Permit 08070320
Permit Number 08070320
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-08 15:09:20****PRIVATE PROVIDER AUDIT****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1. THE OWNER'S ACKNOWLEDGEMENT IS REQUIRED,
 FS553.791(4)(C).
  
 2.THE PRIVATE PROVIDER AFFIDAVIT IS TO IDENTIFY THE
 PLANS REVIEWED.THERE WAS A LOG PROVIDED, BUT THIS LOG
 IS NOT A PART OF THE AFFIDAVIT.THE AFFIDAVIT STATES
 "77 PAGES - ATTACHED" BUT NOTHING WAS ATTACHED; THE LOG
 WAS SUBMITTED SEPARATELY.THE LOG DOES NOT PROPERLY
 IDENTIFY EACH SHEET (SOME SHEETS HAVE DIFFERENT PAGE,
 FOR INSTANCE E106CR1, M104C, M014C) AND THE LOG DOES
 NOT IDENTIFY THE PLAN SHEETS BY DATE.NOT ALL SHEETS
 WERE STAMPED BY GFA (E106CR1, S101CR1).IT APPEARS
 THAT THE FIRE PROTECTION PLANS WERE NOT REVIEWED, OR
 THE C SHEETS (WHICH SHOW COMPLIANCE WITH FBC11 AND FBC5
 REQUIREMENTS), BUT THIS IS REQUIRED BY
 FBC*106.3.5.1.1(5), FS553.79 (2).NOTE THAT THE
 FOUNDATION PERMIT HAS NOT YET BEEN ISSUED, SO CANNOT BE
 USED TO SHOW CODE COMPLIANCE FOR THIS PLAN.
  
 3. FIRE SPRINKLER PLANS REQUIRED.AT A MINIMUM, A HEAD
 LAYOUT IS TO BE SUBMITTED, SEE FBC*106.3.5.1.1(5),
 FS553.79(2), LETTER FROM DCA (AVAILABLE UPON REQUEST).
  
 4. M SHEETS, THE SEAL IS TO INCLUDE THE DATE,
 FAC61G15-23.002, FS471.
  
 5. PLEASE NOTE THAT AN INDEX SHEET IS USEFUL WITH A
 PLAN OF THIS SIZE.THIS IS NOT A REQUIREMENT, BUT A
 SUGGESTION TO ASSIST WITH PLAN REVIEW.PROVIDING AN
 INDEX SHEET WILL ENABLE PLAN REVIEWERS TO OBTAIN
 NECESSARY INFORMATION MORE QUICKLY, WHICH WILL HELP TO
 EXPEDITE THE PLAN REVIEW PROCESS AND CUT DOWN ON PLAN
 REVIEW TIME.
  
 6. TWO 8 1/2 X 11 SHEETS WERE SUBMITTED.NEITHER ARE
 SEALED, ONE HAS THE DESIGNER'S TITLE BLOCK BUT IS
 LACKING SOME OF THE INFORMATION REQUIRED BY
 FAC61G15-23.002; THE OTHER IS NOT SEALED.PLEASE
 INCORPORATE THESE CHANGES INTO THE SIGNED AND SEALED
 PLAN.
  
 7. N/A.
  
 8. FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD,
 561-805-6666.A RESIDENT INSPECTOR PROGRAM IS
 REQUIRED, ON THIS PROJECT (STEEL STRUCTURE ONLY), DUE
 TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH KEN CONRAD (CHIEF BUILDING
 INSPECTOR - TEL: 561 805 6666), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB INSPECTOR, CONTRACTOR
 AND ENGINEER.THIS MUST BE DONE PRIOR TO PERMIT
 ISSUANCE.THREE ORIGINAL SETS OF ALL DOCUMENTS ARE
 REQUIRED FOR PERMITTING.
  
 9. A901C, SECTION 507.2 UNLIMITED AREA NOT APPLICABLE
 TO THIS PROJECT AS THIS IS A MIXED USE, A3 AND S1
 DECLARED.FBC507.9 UNLIMITED AREA FOR A4 OCCUPANCY
 REQUIRES THAT THE FINISHED FLOOR BE 12? FROM GRADE
 LEVEL AND HAS OTHER REQUIREMENTS FOR EXITING.I WAS
 UNABLE TO LOCATE AN ALLOWANCE FOR A3 UNLIMITED AREA,
 TYPE IIB.SEE FBC TABLE 503 AND CHAPTER 5.
  
 10. SEE FBC302.3; THIS IS A MIXED OCCUPANCY BUILDING.
 PLEASE SEE FBC302.3.2 REGARDING BUILDING RATIOS.IT
 APPEARS THAT THIS BUILDING HAS BEEN DESIGNED IN
 ACCORDANCE WITH FBC302.3.1 BUT DOES NOT COMPLY WITH THE
 MORE STRINGENT REQUIREMENT OF A3, TYPE IIB.SEE OTHER
 COMMENTS.
  
 11. IF AREA MODIFICATIONS ARE USED FOR SPRINKLERS OR
 OPEN AREA, PLEASE INCLUDE ALL CALCULATIONS ON THE PLAN.
 FBC506.
  
 12. A901C STATES THAT THE MEZZANINE COMPLIES WITH
 FBC505.PLEASE SHOW COMPLIANCE BY STATING THE TOTAL
 SQUARE FOOT AREA OF THE MEZZANINE, FBC505.2.
  
 13. A901C, S1 AND A3 DECLARED, EMPLOYEE BREAK ROOM
 SHOWN AS ACCESSORY, BUT THE ADMINISTRATION (BUSINESS)
 AREAS, FIRST FLOOR AND MEZZANINE, WERE NOT ADDRESSED.
 DECLARE TOTAL SF AREA FOR ADMINISTRATION AND SHOW
 COMPLIANCE WITH FBC302.FIRE RESISTIVE RATED
 CONSTRUCTION MAY BE REQUIRED BETWEEN THE B AND S AND B,
 S AND A OCCUPANCIES (MEZZANINE).
  
 14. A901C, DECLARE SQUARE FOOT AREA FOR THE ASSEMBLY
 AND S1 OCCUPANCIES, ACCESSORY BREAK ROOM, FBC1004,
 FBC302.ALSO SEE OTHER COMMENT; DECLARE SF AREA FOR
 THE BUSINESS (ADMINISTRATION) AREA SHOWN ON THE FIRST
 FLOOR AS WELL AS THE OFFICE IN THE MEZZANINE.IT IS
 NOT CLEAR IF THIS IS ACCESSORY OR INCIDENTAL OR MIXED
 OCCUPANCY, FBC302.
  
 15. IS THE LUBE & OIL ROOM USED AS A REPAIR GARAGE,
 FBC406.6, MAINTENANCE OR REPAIR OF AUTOMOTIVE OR
 SIMILAR EQUIPMENT?SHOW COMPLIANCE ON THE PLAN WITH
 SPECIAL REQUIREMENTS, IF ANY.
  
 16. DO ANY OF THE AREAS INCLUDE HIGH PILED OR RACK
 STORAGE OF COMBUSTIBLES, FBC413.3?SHOW COMPLIANCE ON
 THE PLAN FOR ANY SPECIAL REQUIREMENTS, IF ANY.
 17. THERE ARE SEVERAL STORAGE AREAS SHOWN ON THE PLAN.
 PLEASE NOTE MATERIALS TO BE STORED IN EACH AREA,
 HAZARDOUS MATERIALS AND AMOUNTS, AS WELL AS COMPLIANCE
 WITH ANY SPECIAL REQUIREMENTS, IF ANY, FBC413.
  
 18. SHOW ACCESSIBLE EXITS, FBC11-4.1.3(9), A901C.
  
 19. A901C, SEE THE EXIT AT THE BALED STORAGE AREA.
 PLEASE SHOW THAT THIS IS NOT A REQUIRED ACCESSIBLE EXIT
 DUE TO TRAVEL DISTANCE AS THIS EXIT DOES NOT PROVIDE
 VERTICAL ACCESSIBILITY, FBC11-4.1.3(9).
  
 20. THE LIFE SAFETY PLAN DOES NOT CORRELATE WITH A001C.
 THERE ARE SEVERAL AREAS IN THE PROCESSING FLOOR WITH
 DOORS AND WHAT APPEAR TO BE WALLS OR SOME OTHER
 OBSTRUCTION PREVENTING PASSAGE.TRAVEL DISTANCE,
 COMMON PATH OF TRAVEL, AND DEAD END CORRIDOR
 REQUIREMENTS (FBC1015, FBC1016.3) CANNOT BE DETERMINED
 UNLESS THESE OBSTRUCTIONS AS WELL AS THE EQUIPMENT IS
 PLACED ON THE LIFE SAFETY PLAN.CONVEYOR BELTS,
 CATWALKS, AND OTHER EQUIPMENT WHICH ARE SHOWN ON A001C
 BUT WHICH DO NOT AFFECT THE PATH OF TRAVEL NEED NOT BE
 SHOWN ON THE LIFE SAFETY PLAN, A901C.
  
 21. S1 DECLARED, BUT CODE ANALYSIS ITEM 5, FIRE
 PROTECTION SYSTEM, REFERS TO 903.2.3, REQUIREMENTS FOR
 F1 OCCUPANCY.PLEASE REVISE CODE REFERENCE.
  
 22. TO AVOID FIELD ISSUES AND TO ASSIST TRADES AND
 INSPECTORS, ON SHEET A901C, PLEASE SHOW HORIZONTAL FIRE
 RESISTANCE REQUIRED BETWEEN 1ST FLOOR AND MEZZANINE.
  
 23. PLEASE CLARIFY .15IN FOR EGRESS COMPONENTS, A901C.
 IT IS UNCLEAR WHERE THIS COMES FROM.SEE FBC TABLE
 1005.1.
  
 24. STAIRWAYS ARE TO BE .3 PER OCCUPANT, NOT .2, FBC
 TABLE 1005.1.REVISE A901C.
  
 25. OTHER COMPONENTS IN THE MEANS OF EGRESS ARE TO BE
 .2 PER OCCUPANT, NOT .15, REVISE A901C.THE DOORS DO
 NOT COMPLY WITH THE MINIMUM REQUIREMENTS WHEN THE
 OCCUPANT LOAD IS MULTIPLIED BY .2 RATHER THAN .15; FOR
 INSTANCE, SEE STAIR 2 EXIT DOOR, 39.4INCHES REQUIRED
 BUT ONLY 32 INCHES PROVIDED.CHECK ALL.
  
 26. DECLARE OCCUPANT LOAD FOR THE SCALE HOUSE,
 FBC1004.
  
 27. SHOPS/ENGINEERING FOR THE STEEL CONTAINMENT WALL
 PROVIDED BY CP MANUFACTURING A001C REVIEWED BY ENGINEER
 AND PRIVATE PROVIDER WILL BE REQUIRED PRIOR TO
 INSTALLATION; PROVISO ITEM.
  
 28. A004C, SECTION 2, DOES NOT APPEAR TO SHOW THE DOOR
 AND STAIR.
  
 29. A003C AND OTHER SHEETS, PLANS SHOW SEVERAL LADDERS,
 STAIRS, EQUIPMENT PLATFORMS, AND CATWALKS.SEE
 FBC505.5.1, FBC505.5.2, 505.5.3, FBC CHAPTER 10. PLEASE
 PROVIDE SHOPS WHICH SHOW CODE COMPLIANCE OR CONTACT ME
 TO DISCUSS AT WHAT POINT DESIGNER/CONTRACTOR PROPOSES
 TO SUBMIT THE DRAWINGS FOR THESE COMPONENTS.
  
 30.SHOW LOCATION OF ANY ROOFTOP MECHANICAL EQUIPMENT
 INCLUDING DISTANCE FROM EDGE, A006C.SEE FBC1012.5 AND
 SHOW ANY REQUIRED GUARDS, LOCATION AND A DETAIL,
 FBC1012.
  
 31. THE STRUCTURAL CALCULATIONS (VP BUILDINGS), SCALE
 HOUSE SHOP DRAWINGS, AND STRUCTURAL PLAN FOR THE MAIN
 BUILDING HAS A PHOTOCOPY OF THE ENGINEER?S SIGNATURE.
 AN ORIGINAL WET SIGNATURE IS REQUIRED AS WELL AS A
 TITLE BLOCK WITH ALL INFORMATION REQUIRED BY
 FAC61G15-23.002.ALSO PLEASE NOTE THE FOLLOWING AND
 ADDRESS:
  
 A. THE STRUCTURAL CALCULATIONS AND PLANS FOR THE VP
 BUILDING STRUCTURE WERE NOT REVIEWED BY THE PRIVATE
 PROVIDER OR BY THE DESIGNER FOR THE BUILDING.
  
 B. THE CALCS AND PLANS STATE NOT FOR CONSTRUCTION;
 PLEASE PROVIDE CONSTRUCTION SET.PLEASE ALSO SEE
 FAC61G15; PRELIMINARY PLANS SHOULD NOT BE SIGNED AND
 SEALED BY THE ENGINEER.
  
 C. PAGE 4 OF THE CALCULATIONS, OTHER SHEETS, PLANS,
 REFER TO 2004 FLORIDA STATE BUILDING CODE; PLEASE
 REVISE TO GOVERNING CODE WHICH IS FLORIDA BUILDING CODE
 2004 WITH 2007 REVISIONS/SUPPLEMENTS.
  
 D. PAGE 4 CALCULATIONS, OTHER SHEETS, AISC89 SHOULD
 INCLUDE SUPPLEMENT 1, FBC35.
  
 E. ALL SIGNED AND SEALED SHEETS ARE TO INCLUDE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.IN THE PAST,
 THIS ISSUE AS WELL AS THE PHOTOCOPIED SIGNATURE HAS
 CAUSED PERMIT DELAYS.PLEASE ONLY SUBMIT PLANS WHICH
 COMPLY, ESPECIALLY AS THE ENGINEER HAS BEEN ADVISED OF
 THESE REQUIREMENTS ON AT LEAST TWO OTHER PROJECTS IN
 THE PAST.THE ENGINEER?S COOPERATION WILL HELP TO
 EXPEDITE PLAN REVIEW AND PERMIT ISSUANCE.
  
 32. FLORIDA STATE OR LOCAL PRODUCT APPROVAL OR
 MIAMIDADE NOA REQUIRED FOR THE ROOF PANELS, FAC9B72.
  
 33. PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER OF
 RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.AS THEY ARE A PART OF THE BUILDING
 ENVELOPE AND REQUIRED TO DETERMINE CODE COMPLIANCE, THE
 PRODUCT APPROVALS ARE ALSO TO BE REVIEWED BY THE
 PRIVATE PROVIDER.
  
 34. THE PRODUCT APPROVALS SUBMITTED HAVE NOT YET BEEN
 REVIEWED AS DESIGN PRESSURES HAVE NOT BEEN SPECIFIED.
 HOWEVER PLEASE NOTE THAT THE COIL DOOR PRODUCT APPROVAL
 IS FOR A 16FT WIDE DOOR MAXIMUM, BUT A 20FT DOOR IS
 SHOWN ON A002C.
  
 35. FOR FL4553, CECO DOOR, PROVIDE THE EVALUATION
 REPORT AND INSTALLATION INSTRUCTIONS FROM THE WEBSITE,
 WWW.FLORIDABUILDING.ORG.
  
 36. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.THIS IS
 REQUIRED FOR THE STRUCTURE, AND COMPONENT AND CLADDING
 PRESSURES REQUIRED BUT NOT PROVIDED.
  
 37. FOR THE PEERLESS HORIZONTAL SLIDER, PROVIDE FLORIDA
 STATE PRODUCT APPROVAL OR MIAMIDADE NOA, FAC9B72.A
 TEST REPORT WAS PROVIDED BUT ADDITIONAL INFORMATION IS
 REQUIRED.
  
 38. THE VACRO PRUDEN BUILDINGS MIAMIDADE NOA SUBMITTED
 FOR THE WALL PANELS IS EXPIRED AS OF 7/1/08.PLEASE
 PROVIDE A CURRENT PRODUCT APPROVAL, FAC9B72.
  
 39. CALCULATIONS FOR VERSAKING BUILDINGS WERE
 SUBMITTED.PLEASE NOTE THE FOLLOWING:
  
 A. THE CALCS ARE TO BE REVIEWED BY THE PRIVATE PROVIDER
 AND BY THE DESIGNER OF RECORD.
  
 B. CALCS REFER TO PORTAKING DRAWINGS.PLEASE SUBMIT.
 DRAWINGS ARE TO BE REVIEWED BY DESIGNER OF RECORD AND
 THE PRIVATE PROVIDER.
  
 C. IT APPEARS THAT THE STRUCTURES WILL BE INSTALLED
 INSIDE OF THE VP BUILDING AS NO WIND LOADS WERE
 PROVIDED.PLEASE CLARIFY ON THE PLAN; SHOW LOCATION OF
 THE PROPOSED PORTAKING STRUCTURES ON THE FLOOR PLAN.
  
 D. INCLUDE THE DOORS FOR THE STRUCTURES ON A DOOR
 SCHEDULE OR PROVIDE INFORMATION IN ANOTHER FORMAT TO
 SHOW COMPLIANCE WITH ACCESSIBILITY FBC11 AND OTHER
 REQUIREMENTS FBC10.
  
 E. CALCULATIONS ARE TO BE EITHER SIGNED, SEALED AND
 DATED WITH A TITLE BLOCK ON EACH SHEET, OR AN INDEX
 SHEET IN ACCORDANCE WITH FAC61G15-23 USED.PLEASE
 ADDRESS.
  
 F. GOVERNING CODE IS TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.
  
 40. THE 3 RING BINDER ENTITLED TECHNICAL SPECIFICATIONS
 HAS NOT BEEN REVIEWED BY THE PRIVATE PROVIDER.ALSO IT
 WAS NOT PREPARED IN ACCORDANCE WITH FAC61G1-16.002,
 003; EITHER EVERY SHEET SIGNED AND SEALED OR AN INDEX
 SHEET USED.THIS BINDER MAY BE REMOVED IF ALL
 INFORMATION REQUIRED TO SHOW CODE COMPLIANCE IS
 INCLUDED IN THE PLANS.OTHERWISE, PLEASE SUBMIT
 REVIEWED AND IN COMPLIANCE WITH FAC RULES.PLEASE NOTE
 THAT NORMALLY THE ENTIRE DOCUMENT IS NOT REVIEWED; IT
 WILL BE INCLUDED WITH THE RECORD SET WITH THE PROVISO
 IN ACCORDANCE WITH FBC2004 AND PLAN.
  
 41. THE DOOR SCHEDULE IN THE TECHNICAL SPECIFICATIONS
 BINDER DOES NOT INCLUDE ALL OF THE DOORS ON THE DOOR
 SCHEDULE IN THE PLAN; FOR INSTANCE, DOORS 102 1, 124 5,
 205 2.IF THE TECHNICAL SPECIFICATIONS BINDER REMAINS
 A PART OF THE PERMIT SET, PLEASE CORRELATE.
  
 42. THE WALL AT DOOR 132 1 IS NOT SHOWN AS A FIRE
 RESISTANCE RATED WALL ALTHOUGH SPECIFIED AS FIRE
 RESISTANCE RATED ON THE LIFE SAFETY PLAN A901C.
  
 43. STAIR 1 OPENS INTO THE ELEVATOR LOBBY.SEE
 FBC1019.1.1.NO OPENINGS PERMITTED IN THE STAIR
 ENCLOSURE OTHER THAN THOSE REQUIRED FOR ACCESS, AND
 THOSE OPENINGS ARE TO BE RATED.
  
 43. DOOR 201 1, ASSEMBLY TO STORAGE, DOES NOT SHOW FIRE
 RESISTANCE, SEE FBC715.3.
  
 44. SEE FBC TABLE 1016.1, CORRIDORS 203 AND 205 FROM
 VISITOR?S GALLERY TO STAIRS TO HAVE 1 HOUR FIRE
 RESISTIVE RATING AND THEREFORE DOORS 203 1, 204 1, 205
 1, 206 1, 200 1, TO BE RATED IN ACCORDANCE WITH
 FBC715.3.
  
 45. A FIRE RATED WALL IS SHOWN BETWEEN TOOL & EQUIPMENT
 ROOM AND THE PROCESSING AREA, BUT NO RATING IS SHOWN
 FOR DOOR 124 3.PLEASE CLARIFY DESIGN CRITERIA.
  
 46. SEE FBC715.3, DOOR 201 1 AND WINDOWS W5 TO HAVE
 FIRE PROTECTION IN ACCORDANCE WITH FBC TABLE 715.3 IF
 AN OCCUPANCY SEPARATION IS REQUIRED.PLEASE SEE OTHER
 REQUIREMENTS REGARDING FBC302, FBC 5, REGARDING
 BUILDING HEIGHT AND AREA.AN UNLIMITED BUILDING SIZE
 WAS DECLARED BUT THIS BUILDING DOES NOT COMPLY
 (ASSEMBLY LIMITATIONS).DEPENDING ON HOW COMPLIANCE IS
 SHOWN, VERTICAL AND HORIZONTAL OCCUPANCY SEPARATION MAY
 BE REQUIRED.
  
 47. STAIR 2 SPECIFIES A 1 HOUR WALL ON THE EXTERIOR
 SIDE OF THE STAIR, A101C, BUT NO FIRE RATING FOR THE
 DOOR 136 1.CLARIFY DESIGN INTENT.
  
 48. A114C, 2 HOUR BLOCK SPECIFIED.PLEASE PROVIDE SPEC
 SHEETS AS 2 HOUR IS PROPRIETARY.
  
 49. UL905 SPECIFIED A114C, PROVIDE A COMPLETE DETAIL
 FOR THIS AND ANY OTHER UL ASSEMBLIES SPECIFIED ON THE
 PLAN.
  
 50. PROVIDE PENETRATION DETAILS, FBC712.
  
 51. SEE STAIR SHAFT DETAILS A114C, DOES THIS GO TO THE
 UNDERSIDE OF THE DECK?SEE FBC706.4, 1019.1, PROVIDE A
 DETAIL SHOWING COMPLIANCE.
  
 52. A112C SPECIFIES PLYWOOD.PLEASE CLARIFY USE OF
 COMBUSTIBLE IN THIS TYPE IIB BUILDING, FBC603.
  
 53. SPECIFY INTERIOR FINISH CLASSIFICATION, FBC TABLE
 803.5.
  
 54.THE WALL BETWEEN THE VISITOR?S GALLERY AND THE
 OTHER ADJACENT MEZZANINE AREAS DOES NOT SHOW ANY FIRE
 RESISTIVE RATING.PLEASE SEE OTHER COMMENTS; IS THIS
 ALL ASSEMBLY OCCUPANCY, OR DOES IT REQUIRE AN OCCUPANCY
 SEPARATION?DESIGN INTENT IS NOT CLEAR.
  
 55. FBC13-101.1, ENERGY CALCS REQUIRED FOR BOTH THE
 MAIN BUILDING AND FOR THE SCALE HOUSE.
  
 56. JANITOR?S ROOM 138 IS TO BE ACCESSIBLE
 FBC11-4.1.1(3), WORK AREAS ARE TO BE DESIGNED SO THAT
 EMPLOYEES CAN APPROACH, ENTER, AND EXIT THE AREAS. SHOW
 TURNING RADIUS.
  
 57. PROVIDE INFORMATION (SPEC SHEETS SUGGESTED) FOR THE
 DOOR AT THE VESTIBULE, 112 2 TO SHOW COMPLIANCE WITH
 FBC11-4.13 AND FBC10.
 58. PROVIDE THE ANTICIPATED OCCUPANT LOAD FOR THE AREA
 AT THE BOTTOM OF THE COMMUNICATING NON EGRESS STAIR.
 THIS APPEARS TO BE 3FT4IN.10 OCCUPANTS SHOWN FOR DOOR
 134 1, PLEASE CLARIFY HOW YOU HAVE DETERMINED
 ANTICIPATED OCCUPANTS PER DOOR.
  
 59. SEE FBC1016.4, AIR MOVEMENT IN CORRIDORS.PLEASE
 REMOVE SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION
 AIR DUCTS FROM EXIT ACCESS CORRIDORS, SEE OTHER
 COMMENTS.PLEASE NOTE THAT THERE ARE TWO HALLS IN THE
 MEZZANINE WHICH SERVE AS CORRIDORS.
  
 60. SEE FBC1019.1.2, PENETRATIONS INTO THE STAIRS ARE
 PROHIBITED EXCEPT AS PERMITTED BY THIS CODE SECTION.
 PLEASE REVISE PLANS.
  
 61. DETAIL 1 A007C STATES TO SEE STRUCTURAL DRAWINGS
 FOR THE STAIR RAIL DETAIL.PLEASE SPECIFY DETAIL,
 NUMBER AND PAGE. THERE ARE MANY REFERENCES THROUGHOUT
 THE A SHEETS TO SEE STRUCTURAL DWGS.PLEASE REVISE ALL
 TO REFER SPECIFICALLY TO A DETAIL.
  
 62. A114C, SPECIFY GUARD PICKET SPACING FBC1012.
  
 63. GUARDRAILS AND HANDRAILS, SPECIFY DESIGN STRENGTH
 TO COMPLY WITH FBC1607.7.
  
 64. SEE 3 A007C, THE HANDRAIL IS NOT CONTINUOUS. A106C
 HANDRAIL EXTENSIONS AT BOTTOM NOT SHOWN. PLEASE PROVIDE
 DETAILS AND CORRELATE A SHEETS.
  
 65. 2 A107 IS LOCATED ON SHEET A102 RATHER THAN 101. IS
 ACCESSIBILITY REQUIRED?PLEASE CONFIRM THAT ALL
 DETAILS ARE REFERRED TO PROPERLY ON THE PLAN.
  
 66. IT APPEARS THAT THE CHAIN LINK FENCE AND GATE
 OBSTRUCT THE MEANS OF EGRESS CONTINUITY, FBC1003.1. THE
 GATE AND COIL DOOR DO NOT MEET ANY OF THE REQUIREMENTS
 AS A MEANS OF EGRESS COMPONENT OF CHAPTER 10.
  
 67. PROVIDE A SITE PLAN AND A SURVEY TO BE INCORPORATED
 INTO THIS PLAN TO SHOW COMPLIANCE WITH THE OPEN SPACE
 REQUIREMENT FBC507.2, REVIEWED BY PRIVATE PROVIDER, AS
 WELL AS ACCESSIBILITY REQUIREMENTS FOR PARKING AND
 ACCESSIBLE ROUTE, SEE OTHER COMMENTS.PLANS WERE
 SUBMITTED WHICH WERE PREPARED BY THE LANDSCAPE
 ARCHITECT; IT IS NOT CLEAR IF THE LANDSCAPE PLAN IS TO
 BE USED TO SHOW CODE COMPLIANCE WITH LIFE SAFETY, FBC
 CHAPTER 5, AND ACCESSIBILITY.PLEASE PROVIDE A PLAN TO
 BE USED FOR THAT PURPOSE OR INCORPORATE THE REQUIRED
 INFORMATION INTO THE C SHEETS.
  
 68. THE SITE PLAN IS TO DECLARE TOTAL NUMBER OF PARKING
 SPACES AND TOTAL NUMBER OF ACCESSIBLE PARKING SPACES
 FBC11-4.1.2(5)(A).
  
 69. THE ACCESSIBLE PARKING SPACES ARE TO BE DISPERSED
 FBC11-4.6.2.PLEASE SHOW THE DOORS ON THE SITE PLAN IN
 RELATION TO THE PROPOSED ACCESSIBLE PARKING SPACES AND
 ALSO SHOW ACCESSIBLE ENTRANCES.
  
 70. SHOW THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY TO
 THE ACCESSIBLE BUILDING ENTRANCE FBC11-4.3.2.1(1).
  
 71. PROVIDE A DETAIL FOR THE ACCESSIBLE PARKING SPACE
 FBC11-4.6 AND SHOW WIDTH OF ACCESSIBLE ROUTE, NO LESS
 THAN 44INCHES, FBC11-4.6.2(1).
  
 72. PLEASE NOTE THAT THE FOUNDATION PERMIT HAS NOT BEEN
 ISSUED; THEREFORE, ANY INFORMATION INCLUDED IN THAT
 PERMIT CANNOT BE USED TO SHOW CODE COMPLIANCE FOR THIS
 PERMIT AT THIS TIME.
  
 73. SHOW LOCATION OF STROBES, FBC11-4.28.1.
  
 74. ELEVATOR SIGNAGE TO COMPLY WITH FBC11-4.10.5, CALL
 BUTTONS WITH FBC11-4.10.3.
  
 75. SEE FC1009.4, STAIR LANDINGS, INTERMEDIATE LANDING
 IS 44 IN, 48 INCHES REQUIRED, A113C.
  
 76. PROVIDE A SPECIFICATION FOR ATTACHMENT OF THE GRAB
 BARS TO THE SHEET METAL TO SHOW COMPLIANCE WITH
 FBC1607.7.1.1, FBC11-4.26.3.
  
 77. PROVIDE A SPECIFICATION FOR ATTACHMENT OF THE
 BACKING FOR THE GRAB BARS (A111C) TO SHOW COMPLIANCE
 WITH FBC1607.7.1.1, FBC11-4.26.3.DETAIL STATES
 SCREWED TO STUD BUT DOES NOT SPECIFY SIZE OF SCREWS OR
 DISTANCE APART, DOES NOT SPECIFY A WIDTH FOR THE 22G
 SHEET METAL BACKING.
  
 78. SEE FBC1006 AND SHOW COMPLIANCE.IT IS NOT CLEAR
 WHAT ILLUMINATION WILL BE PROVIDED FOR THE EQUIPMENT
 PLATFORMS, STAIRS.
  
 79. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR
 SIGNS.THEY ARE USUALLY APPLIED FOR BY THE SIGN
 CONTRACTOR PRIOR TO INSTALLATION.
  
 80. PLEASE SHOW COMPLIANCE WITH FBC910, SMOKE AND HEAT
 VENTS.PROVIDE CALCULATIONS ON THE PLAN AND SHOW
 COMPLIANCE WITH ALL REQUIREMENTS.
  
 81. FBC505.5.2, FP101C DOES NOT MAKE REFERENCE TO
 SPRINKLERS ABOVE AND BELOW PLATFORMS.ON THE SPRINKLER
 HEAD LAYOUT PLAN, SHOW COMPLIANCE.
  
 82. SEE OTHER COMMENTS.IT IS NOT CLEAR WHETHER THE
 EXIT LIGHTS PROVIDED ARE ADEQUATE, FBC1006.3; CANNOT
 DETERMINE WHETHER OR NOT EQUIPMENT OBSTRUCTS THE EXIT
 LIGHTS.PLEASE ADDRESS ON THE PLAN, PREFERABLY THE
 LIFE SAFETY PLAN.
  
 83. SEE FBC1503.6, PROVIDE A DETAIL FOR CONDENSATE
 LINES AND ROOF DOWNSPOUTS.
  
 84. WHEN RESUBMITTING, PLEASE INCLUDE A DETAILED
 RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED,
 INCLUDING PAGE NUMBER(S) IF POSSIBLE.THIS WILL HELP
 TO EXPEDITE PLAN REVIEW.
  
 85. SOME OF THE PLANS HAVE BEEN RETAINED.WHEN
 RESUBMITTING, PLEASE SUBMIT THREE COMPLETE SETS. THE
 PLANS WHICH HAVE BEEN RETAINED WILL NOT BE RELEASED FOR
 PERMITTING PURPOSES.CONTACT DEWEY PALMER IF YOU HAVE
 QUESTIONS REGARDING THIS ISSUE.