| Date |
Text |
| 2008-08-08 15:09:20 | ****PRIVATE PROVIDER AUDIT**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1. THE OWNER'S ACKNOWLEDGEMENT IS REQUIRED, |
| | FS553.791(4)(C). |
| | |
| | 2.THE PRIVATE PROVIDER AFFIDAVIT IS TO IDENTIFY THE |
| | PLANS REVIEWED.THERE WAS A LOG PROVIDED, BUT THIS LOG |
| | IS NOT A PART OF THE AFFIDAVIT.THE AFFIDAVIT STATES |
| | "77 PAGES - ATTACHED" BUT NOTHING WAS ATTACHED; THE LOG |
| | WAS SUBMITTED SEPARATELY.THE LOG DOES NOT PROPERLY |
| | IDENTIFY EACH SHEET (SOME SHEETS HAVE DIFFERENT PAGE, |
| | FOR INSTANCE E106CR1, M104C, M014C) AND THE LOG DOES |
| | NOT IDENTIFY THE PLAN SHEETS BY DATE.NOT ALL SHEETS |
| | WERE STAMPED BY GFA (E106CR1, S101CR1).IT APPEARS |
| | THAT THE FIRE PROTECTION PLANS WERE NOT REVIEWED, OR |
| | THE C SHEETS (WHICH SHOW COMPLIANCE WITH FBC11 AND FBC5 |
| | REQUIREMENTS), BUT THIS IS REQUIRED BY |
| | FBC*106.3.5.1.1(5), FS553.79 (2).NOTE THAT THE |
| | FOUNDATION PERMIT HAS NOT YET BEEN ISSUED, SO CANNOT BE |
| | USED TO SHOW CODE COMPLIANCE FOR THIS PLAN. |
| | |
| | 3. FIRE SPRINKLER PLANS REQUIRED.AT A MINIMUM, A HEAD |
| | LAYOUT IS TO BE SUBMITTED, SEE FBC*106.3.5.1.1(5), |
| | FS553.79(2), LETTER FROM DCA (AVAILABLE UPON REQUEST). |
| | |
| | 4. M SHEETS, THE SEAL IS TO INCLUDE THE DATE, |
| | FAC61G15-23.002, FS471. |
| | |
| | 5. PLEASE NOTE THAT AN INDEX SHEET IS USEFUL WITH A |
| | PLAN OF THIS SIZE.THIS IS NOT A REQUIREMENT, BUT A |
| | SUGGESTION TO ASSIST WITH PLAN REVIEW.PROVIDING AN |
| | INDEX SHEET WILL ENABLE PLAN REVIEWERS TO OBTAIN |
| | NECESSARY INFORMATION MORE QUICKLY, WHICH WILL HELP TO |
| | EXPEDITE THE PLAN REVIEW PROCESS AND CUT DOWN ON PLAN |
| | REVIEW TIME. |
| | |
| | 6. TWO 8 1/2 X 11 SHEETS WERE SUBMITTED.NEITHER ARE |
| | SEALED, ONE HAS THE DESIGNER'S TITLE BLOCK BUT IS |
| | LACKING SOME OF THE INFORMATION REQUIRED BY |
| | FAC61G15-23.002; THE OTHER IS NOT SEALED.PLEASE |
| | INCORPORATE THESE CHANGES INTO THE SIGNED AND SEALED |
| | PLAN. |
| | |
| | 7. N/A. |
| | |
| | 8. FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD, |
| | 561-805-6666.A RESIDENT INSPECTOR PROGRAM IS |
| | REQUIRED, ON THIS PROJECT (STEEL STRUCTURE ONLY), DUE |
| | TO ONE OR MORE OF THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQFT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS |
| | OF CONSTRUCTION |
| | |
| | ALSO, PLEASE ARRANGE WITH KEN CONRAD (CHIEF BUILDING |
| | INSPECTOR - TEL: 561 805 6666), A MEETING INVOLVING THE |
| | OWNER, RESIDENT INSPECTOR, JOB INSPECTOR, CONTRACTOR |
| | AND ENGINEER.THIS MUST BE DONE PRIOR TO PERMIT |
| | ISSUANCE.THREE ORIGINAL SETS OF ALL DOCUMENTS ARE |
| | REQUIRED FOR PERMITTING. |
| | |
| | 9. A901C, SECTION 507.2 UNLIMITED AREA NOT APPLICABLE |
| | TO THIS PROJECT AS THIS IS A MIXED USE, A3 AND S1 |
| | DECLARED.FBC507.9 UNLIMITED AREA FOR A4 OCCUPANCY |
| | REQUIRES THAT THE FINISHED FLOOR BE 12? FROM GRADE |
| | LEVEL AND HAS OTHER REQUIREMENTS FOR EXITING.I WAS |
| | UNABLE TO LOCATE AN ALLOWANCE FOR A3 UNLIMITED AREA, |
| | TYPE IIB.SEE FBC TABLE 503 AND CHAPTER 5. |
| | |
| | 10. SEE FBC302.3; THIS IS A MIXED OCCUPANCY BUILDING. |
| | PLEASE SEE FBC302.3.2 REGARDING BUILDING RATIOS.IT |
| | APPEARS THAT THIS BUILDING HAS BEEN DESIGNED IN |
| | ACCORDANCE WITH FBC302.3.1 BUT DOES NOT COMPLY WITH THE |
| | MORE STRINGENT REQUIREMENT OF A3, TYPE IIB.SEE OTHER |
| | COMMENTS. |
| | |
| | 11. IF AREA MODIFICATIONS ARE USED FOR SPRINKLERS OR |
| | OPEN AREA, PLEASE INCLUDE ALL CALCULATIONS ON THE PLAN. |
| | FBC506. |
| | |
| | 12. A901C STATES THAT THE MEZZANINE COMPLIES WITH |
| | FBC505.PLEASE SHOW COMPLIANCE BY STATING THE TOTAL |
| | SQUARE FOOT AREA OF THE MEZZANINE, FBC505.2. |
| | |
| | 13. A901C, S1 AND A3 DECLARED, EMPLOYEE BREAK ROOM |
| | SHOWN AS ACCESSORY, BUT THE ADMINISTRATION (BUSINESS) |
| | AREAS, FIRST FLOOR AND MEZZANINE, WERE NOT ADDRESSED. |
| | DECLARE TOTAL SF AREA FOR ADMINISTRATION AND SHOW |
| | COMPLIANCE WITH FBC302.FIRE RESISTIVE RATED |
| | CONSTRUCTION MAY BE REQUIRED BETWEEN THE B AND S AND B, |
| | S AND A OCCUPANCIES (MEZZANINE). |
| | |
| | 14. A901C, DECLARE SQUARE FOOT AREA FOR THE ASSEMBLY |
| | AND S1 OCCUPANCIES, ACCESSORY BREAK ROOM, FBC1004, |
| | FBC302.ALSO SEE OTHER COMMENT; DECLARE SF AREA FOR |
| | THE BUSINESS (ADMINISTRATION) AREA SHOWN ON THE FIRST |
| | FLOOR AS WELL AS THE OFFICE IN THE MEZZANINE.IT IS |
| | NOT CLEAR IF THIS IS ACCESSORY OR INCIDENTAL OR MIXED |
| | OCCUPANCY, FBC302. |
| | |
| | 15. IS THE LUBE & OIL ROOM USED AS A REPAIR GARAGE, |
| | FBC406.6, MAINTENANCE OR REPAIR OF AUTOMOTIVE OR |
| | SIMILAR EQUIPMENT?SHOW COMPLIANCE ON THE PLAN WITH |
| | SPECIAL REQUIREMENTS, IF ANY. |
| | |
| | 16. DO ANY OF THE AREAS INCLUDE HIGH PILED OR RACK |
| | STORAGE OF COMBUSTIBLES, FBC413.3?SHOW COMPLIANCE ON |
| | THE PLAN FOR ANY SPECIAL REQUIREMENTS, IF ANY. |
| | 17. THERE ARE SEVERAL STORAGE AREAS SHOWN ON THE PLAN. |
| | PLEASE NOTE MATERIALS TO BE STORED IN EACH AREA, |
| | HAZARDOUS MATERIALS AND AMOUNTS, AS WELL AS COMPLIANCE |
| | WITH ANY SPECIAL REQUIREMENTS, IF ANY, FBC413. |
| | |
| | 18. SHOW ACCESSIBLE EXITS, FBC11-4.1.3(9), A901C. |
| | |
| | 19. A901C, SEE THE EXIT AT THE BALED STORAGE AREA. |
| | PLEASE SHOW THAT THIS IS NOT A REQUIRED ACCESSIBLE EXIT |
| | DUE TO TRAVEL DISTANCE AS THIS EXIT DOES NOT PROVIDE |
| | VERTICAL ACCESSIBILITY, FBC11-4.1.3(9). |
| | |
| | 20. THE LIFE SAFETY PLAN DOES NOT CORRELATE WITH A001C. |
| | THERE ARE SEVERAL AREAS IN THE PROCESSING FLOOR WITH |
| | DOORS AND WHAT APPEAR TO BE WALLS OR SOME OTHER |
| | OBSTRUCTION PREVENTING PASSAGE.TRAVEL DISTANCE, |
| | COMMON PATH OF TRAVEL, AND DEAD END CORRIDOR |
| | REQUIREMENTS (FBC1015, FBC1016.3) CANNOT BE DETERMINED |
| | UNLESS THESE OBSTRUCTIONS AS WELL AS THE EQUIPMENT IS |
| | PLACED ON THE LIFE SAFETY PLAN.CONVEYOR BELTS, |
| | CATWALKS, AND OTHER EQUIPMENT WHICH ARE SHOWN ON A001C |
| | BUT WHICH DO NOT AFFECT THE PATH OF TRAVEL NEED NOT BE |
| | SHOWN ON THE LIFE SAFETY PLAN, A901C. |
| | |
| | 21. S1 DECLARED, BUT CODE ANALYSIS ITEM 5, FIRE |
| | PROTECTION SYSTEM, REFERS TO 903.2.3, REQUIREMENTS FOR |
| | F1 OCCUPANCY.PLEASE REVISE CODE REFERENCE. |
| | |
| | 22. TO AVOID FIELD ISSUES AND TO ASSIST TRADES AND |
| | INSPECTORS, ON SHEET A901C, PLEASE SHOW HORIZONTAL FIRE |
| | RESISTANCE REQUIRED BETWEEN 1ST FLOOR AND MEZZANINE. |
| | |
| | 23. PLEASE CLARIFY .15IN FOR EGRESS COMPONENTS, A901C. |
| | IT IS UNCLEAR WHERE THIS COMES FROM.SEE FBC TABLE |
| | 1005.1. |
| | |
| | 24. STAIRWAYS ARE TO BE .3 PER OCCUPANT, NOT .2, FBC |
| | TABLE 1005.1.REVISE A901C. |
| | |
| | 25. OTHER COMPONENTS IN THE MEANS OF EGRESS ARE TO BE |
| | .2 PER OCCUPANT, NOT .15, REVISE A901C.THE DOORS DO |
| | NOT COMPLY WITH THE MINIMUM REQUIREMENTS WHEN THE |
| | OCCUPANT LOAD IS MULTIPLIED BY .2 RATHER THAN .15; FOR |
| | INSTANCE, SEE STAIR 2 EXIT DOOR, 39.4INCHES REQUIRED |
| | BUT ONLY 32 INCHES PROVIDED.CHECK ALL. |
| | |
| | 26. DECLARE OCCUPANT LOAD FOR THE SCALE HOUSE, |
| | FBC1004. |
| | |
| | 27. SHOPS/ENGINEERING FOR THE STEEL CONTAINMENT WALL |
| | PROVIDED BY CP MANUFACTURING A001C REVIEWED BY ENGINEER |
| | AND PRIVATE PROVIDER WILL BE REQUIRED PRIOR TO |
| | INSTALLATION; PROVISO ITEM. |
| | |
| | 28. A004C, SECTION 2, DOES NOT APPEAR TO SHOW THE DOOR |
| | AND STAIR. |
| | |
| | 29. A003C AND OTHER SHEETS, PLANS SHOW SEVERAL LADDERS, |
| | STAIRS, EQUIPMENT PLATFORMS, AND CATWALKS.SEE |
| | FBC505.5.1, FBC505.5.2, 505.5.3, FBC CHAPTER 10. PLEASE |
| | PROVIDE SHOPS WHICH SHOW CODE COMPLIANCE OR CONTACT ME |
| | TO DISCUSS AT WHAT POINT DESIGNER/CONTRACTOR PROPOSES |
| | TO SUBMIT THE DRAWINGS FOR THESE COMPONENTS. |
| | |
| | 30.SHOW LOCATION OF ANY ROOFTOP MECHANICAL EQUIPMENT |
| | INCLUDING DISTANCE FROM EDGE, A006C.SEE FBC1012.5 AND |
| | SHOW ANY REQUIRED GUARDS, LOCATION AND A DETAIL, |
| | FBC1012. |
| | |
| | 31. THE STRUCTURAL CALCULATIONS (VP BUILDINGS), SCALE |
| | HOUSE SHOP DRAWINGS, AND STRUCTURAL PLAN FOR THE MAIN |
| | BUILDING HAS A PHOTOCOPY OF THE ENGINEER?S SIGNATURE. |
| | AN ORIGINAL WET SIGNATURE IS REQUIRED AS WELL AS A |
| | TITLE BLOCK WITH ALL INFORMATION REQUIRED BY |
| | FAC61G15-23.002.ALSO PLEASE NOTE THE FOLLOWING AND |
| | ADDRESS: |
| | |
| | A. THE STRUCTURAL CALCULATIONS AND PLANS FOR THE VP |
| | BUILDING STRUCTURE WERE NOT REVIEWED BY THE PRIVATE |
| | PROVIDER OR BY THE DESIGNER FOR THE BUILDING. |
| | |
| | B. THE CALCS AND PLANS STATE NOT FOR CONSTRUCTION; |
| | PLEASE PROVIDE CONSTRUCTION SET.PLEASE ALSO SEE |
| | FAC61G15; PRELIMINARY PLANS SHOULD NOT BE SIGNED AND |
| | SEALED BY THE ENGINEER. |
| | |
| | C. PAGE 4 OF THE CALCULATIONS, OTHER SHEETS, PLANS, |
| | REFER TO 2004 FLORIDA STATE BUILDING CODE; PLEASE |
| | REVISE TO GOVERNING CODE WHICH IS FLORIDA BUILDING CODE |
| | 2004 WITH 2007 REVISIONS/SUPPLEMENTS. |
| | |
| | D. PAGE 4 CALCULATIONS, OTHER SHEETS, AISC89 SHOULD |
| | INCLUDE SUPPLEMENT 1, FBC35. |
| | |
| | E. ALL SIGNED AND SEALED SHEETS ARE TO INCLUDE ALL |
| | INFORMATION REQUIRED BY FAC61G15-23.002.IN THE PAST, |
| | THIS ISSUE AS WELL AS THE PHOTOCOPIED SIGNATURE HAS |
| | CAUSED PERMIT DELAYS.PLEASE ONLY SUBMIT PLANS WHICH |
| | COMPLY, ESPECIALLY AS THE ENGINEER HAS BEEN ADVISED OF |
| | THESE REQUIREMENTS ON AT LEAST TWO OTHER PROJECTS IN |
| | THE PAST.THE ENGINEER?S COOPERATION WILL HELP TO |
| | EXPEDITE PLAN REVIEW AND PERMIT ISSUANCE. |
| | |
| | 32. FLORIDA STATE OR LOCAL PRODUCT APPROVAL OR |
| | MIAMIDADE NOA REQUIRED FOR THE ROOF PANELS, FAC9B72. |
| | |
| | 33. PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER OF |
| | RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| | FBC*106.3.3.AS THEY ARE A PART OF THE BUILDING |
| | ENVELOPE AND REQUIRED TO DETERMINE CODE COMPLIANCE, THE |
| | PRODUCT APPROVALS ARE ALSO TO BE REVIEWED BY THE |
| | PRIVATE PROVIDER. |
| | |
| | 34. THE PRODUCT APPROVALS SUBMITTED HAVE NOT YET BEEN |
| | REVIEWED AS DESIGN PRESSURES HAVE NOT BEEN SPECIFIED. |
| | HOWEVER PLEASE NOTE THAT THE COIL DOOR PRODUCT APPROVAL |
| | IS FOR A 16FT WIDE DOOR MAXIMUM, BUT A 20FT DOOR IS |
| | SHOWN ON A002C. |
| | |
| | 35. FOR FL4553, CECO DOOR, PROVIDE THE EVALUATION |
| | REPORT AND INSTALLATION INSTRUCTIONS FROM THE WEBSITE, |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 36. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.THIS IS |
| | REQUIRED FOR THE STRUCTURE, AND COMPONENT AND CLADDING |
| | PRESSURES REQUIRED BUT NOT PROVIDED. |
| | |
| | 37. FOR THE PEERLESS HORIZONTAL SLIDER, PROVIDE FLORIDA |
| | STATE PRODUCT APPROVAL OR MIAMIDADE NOA, FAC9B72.A |
| | TEST REPORT WAS PROVIDED BUT ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 38. THE VACRO PRUDEN BUILDINGS MIAMIDADE NOA SUBMITTED |
| | FOR THE WALL PANELS IS EXPIRED AS OF 7/1/08.PLEASE |
| | PROVIDE A CURRENT PRODUCT APPROVAL, FAC9B72. |
| | |
| | 39. CALCULATIONS FOR VERSAKING BUILDINGS WERE |
| | SUBMITTED.PLEASE NOTE THE FOLLOWING: |
| | |
| | A. THE CALCS ARE TO BE REVIEWED BY THE PRIVATE PROVIDER |
| | AND BY THE DESIGNER OF RECORD. |
| | |
| | B. CALCS REFER TO PORTAKING DRAWINGS.PLEASE SUBMIT. |
| | DRAWINGS ARE TO BE REVIEWED BY DESIGNER OF RECORD AND |
| | THE PRIVATE PROVIDER. |
| | |
| | C. IT APPEARS THAT THE STRUCTURES WILL BE INSTALLED |
| | INSIDE OF THE VP BUILDING AS NO WIND LOADS WERE |
| | PROVIDED.PLEASE CLARIFY ON THE PLAN; SHOW LOCATION OF |
| | THE PROPOSED PORTAKING STRUCTURES ON THE FLOOR PLAN. |
| | |
| | D. INCLUDE THE DOORS FOR THE STRUCTURES ON A DOOR |
| | SCHEDULE OR PROVIDE INFORMATION IN ANOTHER FORMAT TO |
| | SHOW COMPLIANCE WITH ACCESSIBILITY FBC11 AND OTHER |
| | REQUIREMENTS FBC10. |
| | |
| | E. CALCULATIONS ARE TO BE EITHER SIGNED, SEALED AND |
| | DATED WITH A TITLE BLOCK ON EACH SHEET, OR AN INDEX |
| | SHEET IN ACCORDANCE WITH FAC61G15-23 USED.PLEASE |
| | ADDRESS. |
| | |
| | F. GOVERNING CODE IS TO INCLUDE 2007 |
| | REVISIONS/SUPPLEMENTS. |
| | |
| | 40. THE 3 RING BINDER ENTITLED TECHNICAL SPECIFICATIONS |
| | HAS NOT BEEN REVIEWED BY THE PRIVATE PROVIDER.ALSO IT |
| | WAS NOT PREPARED IN ACCORDANCE WITH FAC61G1-16.002, |
| | 003; EITHER EVERY SHEET SIGNED AND SEALED OR AN INDEX |
| | SHEET USED.THIS BINDER MAY BE REMOVED IF ALL |
| | INFORMATION REQUIRED TO SHOW CODE COMPLIANCE IS |
| | INCLUDED IN THE PLANS.OTHERWISE, PLEASE SUBMIT |
| | REVIEWED AND IN COMPLIANCE WITH FAC RULES.PLEASE NOTE |
| | THAT NORMALLY THE ENTIRE DOCUMENT IS NOT REVIEWED; IT |
| | WILL BE INCLUDED WITH THE RECORD SET WITH THE PROVISO |
| | IN ACCORDANCE WITH FBC2004 AND PLAN. |
| | |
| | 41. THE DOOR SCHEDULE IN THE TECHNICAL SPECIFICATIONS |
| | BINDER DOES NOT INCLUDE ALL OF THE DOORS ON THE DOOR |
| | SCHEDULE IN THE PLAN; FOR INSTANCE, DOORS 102 1, 124 5, |
| | 205 2.IF THE TECHNICAL SPECIFICATIONS BINDER REMAINS |
| | A PART OF THE PERMIT SET, PLEASE CORRELATE. |
| | |
| | 42. THE WALL AT DOOR 132 1 IS NOT SHOWN AS A FIRE |
| | RESISTANCE RATED WALL ALTHOUGH SPECIFIED AS FIRE |
| | RESISTANCE RATED ON THE LIFE SAFETY PLAN A901C. |
| | |
| | 43. STAIR 1 OPENS INTO THE ELEVATOR LOBBY.SEE |
| | FBC1019.1.1.NO OPENINGS PERMITTED IN THE STAIR |
| | ENCLOSURE OTHER THAN THOSE REQUIRED FOR ACCESS, AND |
| | THOSE OPENINGS ARE TO BE RATED. |
| | |
| | 43. DOOR 201 1, ASSEMBLY TO STORAGE, DOES NOT SHOW FIRE |
| | RESISTANCE, SEE FBC715.3. |
| | |
| | 44. SEE FBC TABLE 1016.1, CORRIDORS 203 AND 205 FROM |
| | VISITOR?S GALLERY TO STAIRS TO HAVE 1 HOUR FIRE |
| | RESISTIVE RATING AND THEREFORE DOORS 203 1, 204 1, 205 |
| | 1, 206 1, 200 1, TO BE RATED IN ACCORDANCE WITH |
| | FBC715.3. |
| | |
| | 45. A FIRE RATED WALL IS SHOWN BETWEEN TOOL & EQUIPMENT |
| | ROOM AND THE PROCESSING AREA, BUT NO RATING IS SHOWN |
| | FOR DOOR 124 3.PLEASE CLARIFY DESIGN CRITERIA. |
| | |
| | 46. SEE FBC715.3, DOOR 201 1 AND WINDOWS W5 TO HAVE |
| | FIRE PROTECTION IN ACCORDANCE WITH FBC TABLE 715.3 IF |
| | AN OCCUPANCY SEPARATION IS REQUIRED.PLEASE SEE OTHER |
| | REQUIREMENTS REGARDING FBC302, FBC 5, REGARDING |
| | BUILDING HEIGHT AND AREA.AN UNLIMITED BUILDING SIZE |
| | WAS DECLARED BUT THIS BUILDING DOES NOT COMPLY |
| | (ASSEMBLY LIMITATIONS).DEPENDING ON HOW COMPLIANCE IS |
| | SHOWN, VERTICAL AND HORIZONTAL OCCUPANCY SEPARATION MAY |
| | BE REQUIRED. |
| | |
| | 47. STAIR 2 SPECIFIES A 1 HOUR WALL ON THE EXTERIOR |
| | SIDE OF THE STAIR, A101C, BUT NO FIRE RATING FOR THE |
| | DOOR 136 1.CLARIFY DESIGN INTENT. |
| | |
| | 48. A114C, 2 HOUR BLOCK SPECIFIED.PLEASE PROVIDE SPEC |
| | SHEETS AS 2 HOUR IS PROPRIETARY. |
| | |
| | 49. UL905 SPECIFIED A114C, PROVIDE A COMPLETE DETAIL |
| | FOR THIS AND ANY OTHER UL ASSEMBLIES SPECIFIED ON THE |
| | PLAN. |
| | |
| | 50. PROVIDE PENETRATION DETAILS, FBC712. |
| | |
| | 51. SEE STAIR SHAFT DETAILS A114C, DOES THIS GO TO THE |
| | UNDERSIDE OF THE DECK?SEE FBC706.4, 1019.1, PROVIDE A |
| | DETAIL SHOWING COMPLIANCE. |
| | |
| | 52. A112C SPECIFIES PLYWOOD.PLEASE CLARIFY USE OF |
| | COMBUSTIBLE IN THIS TYPE IIB BUILDING, FBC603. |
| | |
| | 53. SPECIFY INTERIOR FINISH CLASSIFICATION, FBC TABLE |
| | 803.5. |
| | |
| | 54.THE WALL BETWEEN THE VISITOR?S GALLERY AND THE |
| | OTHER ADJACENT MEZZANINE AREAS DOES NOT SHOW ANY FIRE |
| | RESISTIVE RATING.PLEASE SEE OTHER COMMENTS; IS THIS |
| | ALL ASSEMBLY OCCUPANCY, OR DOES IT REQUIRE AN OCCUPANCY |
| | SEPARATION?DESIGN INTENT IS NOT CLEAR. |
| | |
| | 55. FBC13-101.1, ENERGY CALCS REQUIRED FOR BOTH THE |
| | MAIN BUILDING AND FOR THE SCALE HOUSE. |
| | |
| | 56. JANITOR?S ROOM 138 IS TO BE ACCESSIBLE |
| | FBC11-4.1.1(3), WORK AREAS ARE TO BE DESIGNED SO THAT |
| | EMPLOYEES CAN APPROACH, ENTER, AND EXIT THE AREAS. SHOW |
| | TURNING RADIUS. |
| | |
| | 57. PROVIDE INFORMATION (SPEC SHEETS SUGGESTED) FOR THE |
| | DOOR AT THE VESTIBULE, 112 2 TO SHOW COMPLIANCE WITH |
| | FBC11-4.13 AND FBC10. |
| | 58. PROVIDE THE ANTICIPATED OCCUPANT LOAD FOR THE AREA |
| | AT THE BOTTOM OF THE COMMUNICATING NON EGRESS STAIR. |
| | THIS APPEARS TO BE 3FT4IN.10 OCCUPANTS SHOWN FOR DOOR |
| | 134 1, PLEASE CLARIFY HOW YOU HAVE DETERMINED |
| | ANTICIPATED OCCUPANTS PER DOOR. |
| | |
| | 59. SEE FBC1016.4, AIR MOVEMENT IN CORRIDORS.PLEASE |
| | REMOVE SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION |
| | AIR DUCTS FROM EXIT ACCESS CORRIDORS, SEE OTHER |
| | COMMENTS.PLEASE NOTE THAT THERE ARE TWO HALLS IN THE |
| | MEZZANINE WHICH SERVE AS CORRIDORS. |
| | |
| | 60. SEE FBC1019.1.2, PENETRATIONS INTO THE STAIRS ARE |
| | PROHIBITED EXCEPT AS PERMITTED BY THIS CODE SECTION. |
| | PLEASE REVISE PLANS. |
| | |
| | 61. DETAIL 1 A007C STATES TO SEE STRUCTURAL DRAWINGS |
| | FOR THE STAIR RAIL DETAIL.PLEASE SPECIFY DETAIL, |
| | NUMBER AND PAGE. THERE ARE MANY REFERENCES THROUGHOUT |
| | THE A SHEETS TO SEE STRUCTURAL DWGS.PLEASE REVISE ALL |
| | TO REFER SPECIFICALLY TO A DETAIL. |
| | |
| | 62. A114C, SPECIFY GUARD PICKET SPACING FBC1012. |
| | |
| | 63. GUARDRAILS AND HANDRAILS, SPECIFY DESIGN STRENGTH |
| | TO COMPLY WITH FBC1607.7. |
| | |
| | 64. SEE 3 A007C, THE HANDRAIL IS NOT CONTINUOUS. A106C |
| | HANDRAIL EXTENSIONS AT BOTTOM NOT SHOWN. PLEASE PROVIDE |
| | DETAILS AND CORRELATE A SHEETS. |
| | |
| | 65. 2 A107 IS LOCATED ON SHEET A102 RATHER THAN 101. IS |
| | ACCESSIBILITY REQUIRED?PLEASE CONFIRM THAT ALL |
| | DETAILS ARE REFERRED TO PROPERLY ON THE PLAN. |
| | |
| | 66. IT APPEARS THAT THE CHAIN LINK FENCE AND GATE |
| | OBSTRUCT THE MEANS OF EGRESS CONTINUITY, FBC1003.1. THE |
| | GATE AND COIL DOOR DO NOT MEET ANY OF THE REQUIREMENTS |
| | AS A MEANS OF EGRESS COMPONENT OF CHAPTER 10. |
| | |
| | 67. PROVIDE A SITE PLAN AND A SURVEY TO BE INCORPORATED |
| | INTO THIS PLAN TO SHOW COMPLIANCE WITH THE OPEN SPACE |
| | REQUIREMENT FBC507.2, REVIEWED BY PRIVATE PROVIDER, AS |
| | WELL AS ACCESSIBILITY REQUIREMENTS FOR PARKING AND |
| | ACCESSIBLE ROUTE, SEE OTHER COMMENTS.PLANS WERE |
| | SUBMITTED WHICH WERE PREPARED BY THE LANDSCAPE |
| | ARCHITECT; IT IS NOT CLEAR IF THE LANDSCAPE PLAN IS TO |
| | BE USED TO SHOW CODE COMPLIANCE WITH LIFE SAFETY, FBC |
| | CHAPTER 5, AND ACCESSIBILITY.PLEASE PROVIDE A PLAN TO |
| | BE USED FOR THAT PURPOSE OR INCORPORATE THE REQUIRED |
| | INFORMATION INTO THE C SHEETS. |
| | |
| | 68. THE SITE PLAN IS TO DECLARE TOTAL NUMBER OF PARKING |
| | SPACES AND TOTAL NUMBER OF ACCESSIBLE PARKING SPACES |
| | FBC11-4.1.2(5)(A). |
| | |
| | 69. THE ACCESSIBLE PARKING SPACES ARE TO BE DISPERSED |
| | FBC11-4.6.2.PLEASE SHOW THE DOORS ON THE SITE PLAN IN |
| | RELATION TO THE PROPOSED ACCESSIBLE PARKING SPACES AND |
| | ALSO SHOW ACCESSIBLE ENTRANCES. |
| | |
| | 70. SHOW THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY TO |
| | THE ACCESSIBLE BUILDING ENTRANCE FBC11-4.3.2.1(1). |
| | |
| | 71. PROVIDE A DETAIL FOR THE ACCESSIBLE PARKING SPACE |
| | FBC11-4.6 AND SHOW WIDTH OF ACCESSIBLE ROUTE, NO LESS |
| | THAN 44INCHES, FBC11-4.6.2(1). |
| | |
| | 72. PLEASE NOTE THAT THE FOUNDATION PERMIT HAS NOT BEEN |
| | ISSUED; THEREFORE, ANY INFORMATION INCLUDED IN THAT |
| | PERMIT CANNOT BE USED TO SHOW CODE COMPLIANCE FOR THIS |
| | PERMIT AT THIS TIME. |
| | |
| | 73. SHOW LOCATION OF STROBES, FBC11-4.28.1. |
| | |
| | 74. ELEVATOR SIGNAGE TO COMPLY WITH FBC11-4.10.5, CALL |
| | BUTTONS WITH FBC11-4.10.3. |
| | |
| | 75. SEE FC1009.4, STAIR LANDINGS, INTERMEDIATE LANDING |
| | IS 44 IN, 48 INCHES REQUIRED, A113C. |
| | |
| | 76. PROVIDE A SPECIFICATION FOR ATTACHMENT OF THE GRAB |
| | BARS TO THE SHEET METAL TO SHOW COMPLIANCE WITH |
| | FBC1607.7.1.1, FBC11-4.26.3. |
| | |
| | 77. PROVIDE A SPECIFICATION FOR ATTACHMENT OF THE |
| | BACKING FOR THE GRAB BARS (A111C) TO SHOW COMPLIANCE |
| | WITH FBC1607.7.1.1, FBC11-4.26.3.DETAIL STATES |
| | SCREWED TO STUD BUT DOES NOT SPECIFY SIZE OF SCREWS OR |
| | DISTANCE APART, DOES NOT SPECIFY A WIDTH FOR THE 22G |
| | SHEET METAL BACKING. |
| | |
| | 78. SEE FBC1006 AND SHOW COMPLIANCE.IT IS NOT CLEAR |
| | WHAT ILLUMINATION WILL BE PROVIDED FOR THE EQUIPMENT |
| | PLATFORMS, STAIRS. |
| | |
| | 79. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR |
| | SIGNS.THEY ARE USUALLY APPLIED FOR BY THE SIGN |
| | CONTRACTOR PRIOR TO INSTALLATION. |
| | |
| | 80. PLEASE SHOW COMPLIANCE WITH FBC910, SMOKE AND HEAT |
| | VENTS.PROVIDE CALCULATIONS ON THE PLAN AND SHOW |
| | COMPLIANCE WITH ALL REQUIREMENTS. |
| | |
| | 81. FBC505.5.2, FP101C DOES NOT MAKE REFERENCE TO |
| | SPRINKLERS ABOVE AND BELOW PLATFORMS.ON THE SPRINKLER |
| | HEAD LAYOUT PLAN, SHOW COMPLIANCE. |
| | |
| | 82. SEE OTHER COMMENTS.IT IS NOT CLEAR WHETHER THE |
| | EXIT LIGHTS PROVIDED ARE ADEQUATE, FBC1006.3; CANNOT |
| | DETERMINE WHETHER OR NOT EQUIPMENT OBSTRUCTS THE EXIT |
| | LIGHTS.PLEASE ADDRESS ON THE PLAN, PREFERABLY THE |
| | LIFE SAFETY PLAN. |
| | |
| | 83. SEE FBC1503.6, PROVIDE A DETAIL FOR CONDENSATE |
| | LINES AND ROOF DOWNSPOUTS. |
| | |
| | 84. WHEN RESUBMITTING, PLEASE INCLUDE A DETAILED |
| | RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED, |
| | INCLUDING PAGE NUMBER(S) IF POSSIBLE.THIS WILL HELP |
| | TO EXPEDITE PLAN REVIEW. |
| | |
| | 85. SOME OF THE PLANS HAVE BEEN RETAINED.WHEN |
| | RESUBMITTING, PLEASE SUBMIT THREE COMPLETE SETS. THE |
| | PLANS WHICH HAVE BEEN RETAINED WILL NOT BE RELEASED FOR |
| | PERMITTING PURPOSES.CONTACT DEWEY PALMER IF YOU HAVE |
| | QUESTIONS REGARDING THIS ISSUE. |