Plan Review Notes
Plan Review Notes For Permit 08070288
Permit Number 08070288
Review Stop P
Sequence Number 1
Notes
Date Text
2008-07-16 11:57:44PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 1, STATES THE FOLLOWING, "BUILDING SITE
 INSTALLATION REQUIREMENTS LOCAL INSPECTIONS DEPARTMENT:
 SPECIAL CONDITIONS/LIMITATIONS, THE FOLLOWING ITEMS
 HAVE NOT BEEN COMPLETED BY THE MANUFACTURER, HAVE NOT
 BEEN INSPECTED BY A THIRD PARTY INSPECTION AGENCY AND
 ARE NOT CERTIFIED BY THE STATE MODULAR LABEL AND/OR
 CERTIFICATION. CODE COMPLIANCE FOR THESE ITEMS MUST BE
 DETERMINED AT A LOCAL LEVEL: 3) BUILDING DRAINS,
 CLEANOUTS AND HOOK-UPS TO PLUMBING SYSTEMS, AND FINNISH
 PLUMBING." WITH THAT BEING INDICATED ON THE PLANS AND
 MOST ICE MACHINES HAVING POTABLE WATER AND DRAINS,
 PLEASE PROVIDE TWO COPIES OF MANUFACTURER
 SPECIFICATIONS OF THE ICE MACHINE CLEARLY INDICATING
 THE MAKE, MODEL NUMBER, PLUMBING REQUIREMENTS (POTABLE
 WATER AND DRAINAGE), AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY. ALSO PLEASE PROVIDE THE
 INFORMATION THAT IS REQUSTED IN COMMENTS #2 AND #3. PER
 FBC- PLUMBING SECTIONS 401.1, 601.1 AND 701.1 SCOPE.
  
 2.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (4)(6)(13) AND FBC-PLUMBING SECTION 701.1 AND
 901.1 SCOPE: PLEASE SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS,
 TRAPS AND SIZES WITH CLEANOUT LOCATIONS FOR THE ICE
 MACHINE DRAIN.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3)(8)(10)(13) AND FBC-PLUMBING SECTION 601.1
 SCOPE: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED ICE MACHINE WORK FOR THE COLD
 WATER INDICATING THE PIPE SIZE, VALVE LOCATIONS,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731