| Date |
Text |
| 2008-07-24 11:35:27 | RESIDENTIAL(R3)ADDITION, BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1-A) PROPERTY IS LOCATED ON FLOOD ZONE A5WITH BASE |
| | FLOOD ELEVATION OF 7'. IF EXISTING HOUSE AND |
| | PROPOSED ADDITION FINISH FLOOR ELEVATION IS LESS THAN |
| | 7'-6", THEN THE HOUSE NEEDS TO BE RAISED AS REQUIRED BY |
| | CITY ORDINANCESEC. 94-546(A) AND (B).PROVIDE |
| | SURVEY OR ANY OTHERDOCUMENT SHOWING EXISTING FINISH |
| | FLOOR ELEVATION TO VERIFY COMPLIANCE WITH THIS CODE |
| | ORDINANCE. |
| | |
| | B) PROPOSED PLANS NEED TO SHOW THE PROPOSED FINISH |
| | FLOOR ELEVATION TO SHOW COMPLIANCE WITH THIS CITY |
| | ORDINANCE. |
| | |
| | 2- SHEET #1: |
| | A) SPECIFYATTIC LIVE LOAD AS REQUIRED BY TABLE |
| | R301.5 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | ***NOTE: COORDINATELOADS WITH TRUSS ENGINEER. SEE |
| | TRUSS PACKAGE.EG: PROJECT NOTES CALL FOR 30PSF ROOF |
| | LIVE LOAD. COORDINATE AND REVISE AS REQUIRED. |
| | |
| | B) ENTRY PORCH FOUNDATION PLAN: SPECIFY HOW MUCH |
| | EMBEDMENT IS REQUIRED FOR ANCHOR BOLTSAT BASE OF |
| | STEEL COLUMN. SEC.106.1.2 CITY AMENDMENTS TO FBC 2004 |
| | TO VERIFY COMPLIANCE WITH UPLIFT LOADS SEC. R301 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | C) REVISE LEVEL ALTERATION TYPE SHOWN ON PROJECT |
| | NOTES. SEECHAPTER 3 OF THE EXISTING BUILDING CODE |
| | 2004TO VIEW SCOPE OF WORK AND REVISE AS REQUIRED. |
| | |
| | 3- SHEET #2: |
| | A) PROVIDE ATTIC ACCESSFOR NEW ADDITION AS |
| | REQUIRED BY SEC. R807 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | B) SPECIFY SIZE OF NEW ATTIC ACCESSWITH DROP |
| | LADDER TO VERIFY COMPLIANCE WITH SEC. R807. |
| | |
| | 4- SHEET#3, TYPICAL WALL SECTION: |
| | A)REVISE ROOF SHEATHING FASTENING OPTION FOR ROOF |
| | ZONE #3 AS REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | B) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) CLEARLY SPECIFY ROOF TILE FASTENING AS REQUIRED |
| | BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. ***NOTE: |
| | COORDINATE WITH PRODUCT APPROVAL SUBMITTED. SEE SHEET |
| | 12 OF NOA 07-1129.04 SUBMITTED AND REVISE INFORMATION |
| | ON WALL SECTION AS REQUIRED. |
| | |
| | D) INDICATE LINE OF GRADE TO VERIFY COMPLIANCE WITH |
| | FOOTING MINIMUM DEPTH SEC. R403.1.4 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 5- SHEET #4: SPECIFY SIZE OF STEEL CORNER BUCKET FOR |
| | STEEL COLUMNS. |
| | |
| | 6- OWES #5.90 FOR RADON FEES. |
| | |
| | 7- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | *** NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 8- PROVIDE ENERGY CALCULATIONS AS REQUIRED BYSEC. |
| | 13-101.2 FBC 2004. |
| | NOTE: MAKE SURE CORRECT REVISED FORM IS USED TO AVOID |
| | DELAYS OR CONFLICTS. |
| | |
| | 9- SOIL TEST REPORT SUBMITTED: |
| | A) NEEDS TO HAVE ENGINEER'S ORIGINAL SIGNATURE (NO |
| | COPY) AS REQUIRED BY SEC. 61G15-23.002 (1) OF FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. |
| | |
| | B) NEEDS TO HAVE THE ENGINEERING FIRM CERTIFICATE OF |
| | AUTHORIZATION NUMBER AS REQUIRED BY SEC. |
| | 61G15-23.002(2). FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) WINDOW MULLIONS.AND CLEARLY MARKSPECIFIC |
| | MULLION SIZE AND FASTENERS TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES OF SEC. |
| | R301. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. |
| | NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND PAGE WHERE CONNECTOR IS LOCATED. NO NEED TO |
| | SUBMIT COMPLETE PRODUCT APPROVAL REPORT. |
| | |
| | 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCTAPPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | NOTE: SEPARATE LETTER SUBMITTED BY THE ENGINEER IS |
| | INCOMPLETE. IT'SNO LISTING ALL PRODUCT APPROVALS AND |
| | IS NOT LISTING THE SPECIFIC FLORIDAPRODUCT APPROVAL |
| | OR NOANUMBER REVIEWED. |
| | |
| | 12- TRUSS PACKAGE: |
| | A) INDEX SHEET DOESN'TCOMPLY WITH THE REQUIREMENTS |
| | OF SEC. 61G15-31.003.THE NAME OF THE ENGINEER OF |
| | RECORD IS NOT SHOWN AND ALL INDIVIDUAL TRUSSES NEED TO |
| | HAVE THE TRUSS ENGINEER NAME AND INFORMATION. REVISE AS |
| | REQUIRED. |
| | |
| | B) TRUSS PACKAGE NEEDS TO BE REVIEWED BY THE |
| | ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | C) PROVIDE ONLY 2 COMPLETE COPIES WITH ORIGINAL SEAL |
| | AND SIGNATURE.(FOUR COPIES WHERE SUBMITTED AND TWO OF |
| | THOSE HAD NO ORIGINAL SIGNATURE). |
| | |
| | |
| | ***NOTE: PLEASE RESUBMIT PAGES WITH PALM BEACH COUNTY |
| | IMPACT FEES STAMP. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |