| Plan Review Notes For Permit 08070268 |
| Permit Number |
08070268 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-12-23 16:07:26 | 100 N CHILLINGWORTH DR | | | HEAD START FACILITY | | | JULY 25,2008 | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 08070268 | | | ADD: 100N CHILLINGSWORTH DR | | | CONT: CATALFUMO | | | TEL: (561)694-3000 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: REVIEWED | | | | | | BUILDING PROVISOS: | | | ENERGY INPUT REPORT R-19.8 | | | ROOFING PERMIT NOA SUBMITTED 07-02228.04 | | | PAGE 7&8 | | | | | | MEMBRANE TYPE SBS | | | DECK DESCRIPTION: STEEL INSULATED, 18-2 GA. | | | FOAM INSULATION: ENERGY 3/ 3.0"=R 18.5 + | | | 1/2" RETRO - FIT BOARD R= 1.32= R 19.82 | | | | | | R-19.8= 3.5 INCHES MINIMUM FOAM AT ROF DRAINS AND | | | INCREASES TO PARAPET. | | | | | | ROOFING PERMIT WIL REQUIRE A ROOFING INSULATION LAYOUT | | | SHEET WITH MINIMUM R VALUE OF 19.8 (3.5 ") AT ROOF | | | DRAINS. | | | | | | ZONE 3 WIL REQUIRE ENHANCED FASTENING MAXIMUM DESIGN | | | PRESURE 75 PSF LIMITATION# 7. RAS 17 CALCULAIONS | | | PREPARED | | | BY EITHER A FL ENGINEER OR ARCHITECT. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | | | | | | | |
|