Plan Review Notes
Plan Review Notes For Permit 08070268
Permit Number 08070268
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-03 12:46:17 
 ** DENIED **
  
  
 ** PLANS ARE IN GOOD SHAPE. THE FOLLOWING ITEMS COULD
 HAVE BEEN REDLINED OR *PROVISO* ITEMS HOWEVER PLANS ARE
 COMING BACK FOR COMMENTS FROM OTHER TRADES. PLEASE
 ADDRESS AT THIS TIME.
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTES TO FBC
 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING CONTROLS. THE
 DETAIL ADDED TO THE SHEET E-6 DOES PROVIDE THE
 ASTRONOMICAL TIME CLOCK AS REQUIRED HOWEVER IF NOT
 USING A PHOTO-SENSOR AS THE OVER RIDE THE CODE REQUIRES
 A MINIMUM OF 10HRS FOR BATTERY BACK UP OF PROGRAMMING.
 PLEASE MAKE NOTE OF THE 10HR BACK UP.
 THIS WAS REDLINED ON PLANS AS THIS IS A MINOR ITEM.
  
 2) NOTE: PLEASE PROVIDE INFORMATION FOR LIGHTING IN
 SEPARATE SPACES. THE PLANS FOR BOTH NOTE #6 AND NOTE #7
 GIVE NOTES TO SEE DETAIL ON SHEET E-7. THE PLANS STILL
 ACTUALLY SHOW THE OCCUPANCY SENSOR DEVICE FOR AREAS
 NOTED AS NOTE #6 HOWEVER NOT THE DEVICE FOR NOTE #7. IF
 THESE ARE GOING TO BE WALL MOUNTED PLEASE SHOW
 LOCATIONS SO COVERAGE MAY BE VERIFIED. FOR AN EXAMPLE
 OF THIS IS THE FUTURE BUILD OUT SPACES. IF A WALL
 MOUNTED OCCUPANCY SENSOR IS GOING TO BE USED IN
 CONJUNCTION WITH THE SINGLE POLE SWITCH COVERAGE NEEDS
 TO BE SHOWN AS AREAS ARE NOT SQUARE. PLEASE CALL TO GO
 OVER
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  