| 2008-09-15 16:15:49 | 100 N CHILLINGWORTH DR |
| | HEAD START FACILITY |
| | JULY 25,2008 |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 08070268 |
| | ADD: 100N CHILLINGSWORTH DR |
| | CONT: CATALFUMO |
| | TEL: (561)694-3000 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1-10 COMPLIED. |
| | |
| | 11) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | |
| | A- B) COMPLIED. |
| | B) |
| | C) ROOF HATCHES -NOT PART OF THIS PROJECT |
| | D) EXTERIOR WALL LOUVERS- NOT PART OF THIS PROJECT |
| | E) ROOFING ASSEMBLIES- THE PRODUCT REPORT SUBMITTED: |
| | FL 1046-R2 / NOA 06-0417.10 |
| | SUB-SYSTEM TYPE :D PAGE 14 OF 16 |
| | THE CONTRACTOR NEEDS TO IDENTIFY WHICH OPTION THEY |
| | PREFER TO USE 1,2 OR 3. |
| | THE OTHER ISSUE IS TO HIGHLIGHT OR CIRCLE WHICH |
| | INSULATION TYPE WILL BE INSTALLED ON THIS PROJECT. NOTE |
| | WE WILL ALSO NEED THE MANUFACTURERS CUT SHEET ON THIS |
| | MATERIAL INDICATING THE R-VALUE. |
| | |
| | |
| | 12-13) COMPLIED. |
| | |
| | 14)2ND REQUEST, SHEET M-8 DETAIL 3 BOTH INDICATES CURB |
| | DETAIL. PLEASE PROVIDE CURB ATTACHMENT DETAILS. SHEET |
| | S-3 INDICATES FRAMING AROUND THE ROOF OPENINGS, |
| | REINFORCEMENT OF THE BAR JOIST BUT NOT THE ATTACHMENT |
| | OF ROOF CURBS. 1609. 6.2.2 COMPONENTS AND CLADDING. |
| | |
| | 15) ENERGY CALCULATIONS, FIRST REVIEW, THE INPUT DATA |
| | REPORT INDICATES THE ROOF INSULATION TO BE A METAL ROOF |
| | BLDG WITH R-19 ROOF INSULATION (BATT). NOTE THE INPUT |
| | DATA REPORT NEEDS TO REFLECT NOT A METAL ROOF SYSTEM |
| | AND BATT BUT A MODIFIED ROOF SYSTEM FOAM INSULATION OR |
| | DURA BOARD DEPENDING ON THE ROOFING REPORT SUBMITTED ON |
| | A CORRIGATED METAL DECK. |
| | 13-404.1ABC.1 |
| | !#-410.1ABC3.6 CAVITIES/ PLENTUMS |
| | |
| | 16) COMPLIED. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |