| 2008-07-28 12:05:16 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT I-1 SHOW THE LOCATION OF THE CONTROLLER AND THE |
| | RAIN SENSOR. FS 373.62. |
| | |
| | 2. SHT A-3 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. SHOW THE AREA FOR EACH ROOF |
| | DRAIN ALONG WITH 1/2 THE AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS ADDED TO THE AREA OF EACH ROOF |
| | DRAIN. SHOW THE ELEVATION OF THE ROOF AT THE PARAPETS |
| | IN ORDER TO VERIFY VERTICAL CONTRIBUTION. |
| | |
| | 3. SHT A-6 DETAILS 5A & 5B LAVS TO BE 2 FEET OFF THE |
| | WALL TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED ON |
| | THE 48" DIMENSION OF THE CLEAR FLOOR SPACE FOR PARALLEL |
| | APPROACH REQUIRED IF LAVS ARE 20" HIGH TO THE FLOOD RIM |
| | LEVEL PER EXCEPTION 2 OF 4.19.2 CHILDRENS GUIDELINES OF |
| | THE ACCESS BOARD. (SEE ATTACHED SHEET). |
| | |
| | 4. SHT A-6 DETAIL 4 27" HIGH CLEARANCE REQUIRED PER |
| | SECTION 11-4.24.3. 26-3/4" SHOWN. PLEASE CORRECT |
| | DETAIL. |
| | |
| | 5. SHT A-6 DETAILS 3A & 3B ALONG WITH SHT A-7 FINISH |
| | SCHEDULE INDICATES C.T. WAINSCOT 3' A.F.F. SECTION |
| | 1210.2 REQUIRES SURFACES WITHIN 2 FEET OF WATER CLOSETS |
| | AND URINALS TO HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE UP TO 4' A.F.F. PLEASE SHOW ON DETAILS AND |
| | FINISH SCHEDULE. |
| | |
| | 6. SHT A-12 DETAIL 6 SHOWS STAINLESS STEEL SCREEN OVER |
| | THE OUTLET OF THE SECONDARY ROOF DRAIN. THIS IS NOT |
| | APPROVED AS IT CAN CAUSE BLOCKAGE IN THE REQUIRED DRAIN |
| | AS WELL AS REDUCING THE REQUIRED AREA OF THE DRAIN. |
| | TABLE 1106.3.--THE DETAIL ALSO SHOWS THE COVER |
| | AGAINST THE COUPLING WHICH DOES NOT REFLECT DETAIL 1 ON |
| | SHT A-14. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 7. SHT P-1 WATER HEATER "A" DETAIL. SUBMIT CALCULATIONS |
| | OR THE SIZING CHART FOR THE EXPANSION TANK SHOWING THE |
| | CORRECT SIZE TANK FOR 80 GAL W/H. SUBMIT MANUF |
| | SPECIFICATION AND INSTALLATION SHEETS FOR THE EXPANSION |
| | TANK INDICATING MODEL NUMBER. SECTION 607.3.2. |
| | |
| | 8. SHT P-2 SHOW CLEANOUTS REQUIRED IN THE STORM SYSTEM |
| | PER SECTION 1101.8. ALSO SHOW CLEANOUT REQUIRED ON THE |
| | STORM RISER DIAGRAM SHT P-4. |
| | |
| | 9. SHT P-2THE P-4 SINK IN THE TEACHERS LOUNGE SHALL |
| | DRAIN DOWNSTREAM OF THE FIXTURES IN TOILET ROOM 131 PER |
| | SECTION 909.1. ONLY FIXTURES IN THE TOILET ROOM SHALL |
| | CONNECT TO THE HORIZONTAL WET VENT FOR THE TOILET ROOM |
| | FIXTURES. ALL OTHER FIXTURES SHALL DISCHARGE DOWNSTREAM |
| | OF THE TOILET ROOM FIXTURES. PLEASE CORRECT THE |
| | SANITARY RISER DIAGRAM ON SHT P-4 ALSO. |
| | |
| | 10. SHT P-2 CONDENSATE FROM THE MECHANICAL ROOM 128 |
| | STATES, "SEE CIVIL FOR CONNECTION TO STORM". CONDENSATE |
| | IS NOT SHOWN ON THE CIVIL PLANS. PLEASE INDICATE THE |
| | TERMINATION OF THE CONDENSATE PER SECTION 314.2.1. IF |
| | THE CONDENSATE CONNECTS TO THE STORM SEWER, THEN A |
| | RELIEF VENT, (GOOSENECK), IS REQUIRED ON THE CONDENSATE |
| | AS IT EXITS THE BUILDING. |
| | |
| | 11. SHT P-4 WATER RISER DIAGRAM. THE WATER HAMMER |
| | ARRESTORS SHALL BE INSTALLED NEAR THE FIXTURES IN AN |
| | EFFECTIVE RANGE, NOT IN THE CEILING AS SHOWN. PDI-WH |
| | 201 & MANUF INSTALLATION INSTRUCTIONS. |
| | |
| | 12. SHT P-4OVERFLOW (ORD) ROOF DRAIN DETAIL |
| | TERMINATION DOES NOT REFLECT THE DETAILS ON SHTS A-12 & |
| | A-14. PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 13. SUBMIT RISER DIAGRAMS FOR THE OVERFLOW DRAINAGE |
| | PIPING PER SECTION 106.3.5.1.3. |
| | |
| | 14. PLUMBING PLANS WERE LOOSE AT THE BACK OF THE PLANS. |
| | PLEASE SUBMIT COMPLETE BOUND SETS, (MINIMUM 2), FOR |
| | REVIEW. SECTION 106.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |