Plan Review Notes
Plan Review Notes For Permit 08070268
Permit Number 08070268
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-01 09:56:52***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE MOUNTED
 AT LOCATIONS NOT TO EXCEED 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 3) SHEET LS-1 ILLUSTRATES FIRE ALARM EQUIPMENT BUT DOES
 NOT INDICATE DUCT SMOKE DETECTOR(S) THAT ARE SHOWN ON
 SHEET E-3. DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 4) NOTE ON SHEET E-3 INDICATES A NEW FIRE ALARM PANEL
 THAT WILL REPLACE THE EXISTING PANEL. PLEASE ILLUSTRATE
 THE LOCATION OF THE PANEL AND REQUIRED SMOKE DETECTOR
 IN SAME AREA. IF THE PANEL REMAINS IN THE EXISTING
 LOCATION, PLEASE INDICATE AND SHOW EQUIPMENT.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL. FIRE ALARM PANEL TO
 BE INCLUDED WITH FIRE ALARM DRAWINGS IF APPLICABLE.
  
 6) UL LISTED CLOSERS REQUIRED ON RATED DOORS TO ENSURE
 POSITIVE LATCH. PLEASE ADD TO DOOR SCHEDULE.
 ADDITIONALLY, PLEASE INDICATE WHAT DOORS IF ANY ARE
 PROVIDED WITH PANIC OF FIRE EXIT HARDWARE.
  
  
 A RESPONSE LETTER INDICATING HOW AND WHERE ON PLANS
 EACH COMMENT WAS ADDRESSED WOULD HELP EXPEDITE THE PLAN
 REVIEW PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756