| 2008-08-01 09:56:52 | ***DENIED*** |
| | |
| | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE |
| | SAFETY SHALL COMPLY WITH NFPA 101, 2003. |
| | |
| | 2) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE MOUNTED |
| | AT LOCATIONS NOT TO EXCEED 75' TRAVEL DISTANCE |
| | REQUIREMENT. |
| | |
| | 3) SHEET LS-1 ILLUSTRATES FIRE ALARM EQUIPMENT BUT DOES |
| | NOT INDICATE DUCT SMOKE DETECTOR(S) THAT ARE SHOWN ON |
| | SHEET E-3. DUCT SMOKE DETECTORS SHALL INITIATE A |
| | GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS. |
| | |
| | 4) NOTE ON SHEET E-3 INDICATES A NEW FIRE ALARM PANEL |
| | THAT WILL REPLACE THE EXISTING PANEL. PLEASE ILLUSTRATE |
| | THE LOCATION OF THE PANEL AND REQUIRED SMOKE DETECTOR |
| | IN SAME AREA. IF THE PANEL REMAINS IN THE EXISTING |
| | LOCATION, PLEASE INDICATE AND SHOW EQUIPMENT. |
| | |
| | 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER AND FIRE ALARM REMODEL. FIRE ALARM PANEL TO |
| | BE INCLUDED WITH FIRE ALARM DRAWINGS IF APPLICABLE. |
| | |
| | 6) UL LISTED CLOSERS REQUIRED ON RATED DOORS TO ENSURE |
| | POSITIVE LATCH. PLEASE ADD TO DOOR SCHEDULE. |
| | ADDITIONALLY, PLEASE INDICATE WHAT DOORS IF ANY ARE |
| | PROVIDED WITH PANIC OF FIRE EXIT HARDWARE. |
| | |
| | |
| | A RESPONSE LETTER INDICATING HOW AND WHERE ON PLANS |
| | EACH COMMENT WAS ADDRESSED WOULD HELP EXPEDITE THE PLAN |
| | REVIEW PROCESS. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |