| 2008-07-30 08:35:17 | |
| | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | ARE NOT COMPLETE AS THE INPUT DATA REPORT AS REQUIRED |
| | DID NOT ACCOMPANY THE SUMMARY SHEETS. |
| | PLEASE BE SURE THE CERTIFICATION SHEETS ARE SIGNED, |
| | DATED AND SEALED AS REQUIRED. |
| | PLEASE BE SURE THE LOCATION IS UPDATED AS THE COVER |
| | SHEET DOES LIST ANOTHER MUNICIPALITY. |
| | PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES WITH |
| | THE ENERGY CALCULATIONS TO BE SUBMITTED. |
| | PLEASE SEE THE SQ FT ON PLANS AND CALCULATIONS ARE NOT |
| | THE SAME. |
| | PLEASE SEE SECTIONS 13-101.1, 13-103.1, 13-415.2, |
| | 13-415.2.ABC.1.1,.1.2 AND .1.3. |
| | |
| | 2) NOTE: PLEASE MEET SECTION 13-415.1.ABC.1.4 FOR |
| | EXTERIOR LIGHTING. THE DETAIL ON SHEET E-8 (#6) DOES |
| | NOT PROVIDE THE MINIMUM BACK UP AND TYPE OF SYSTEM |
| | REQUIRED. |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETE INFORMATION ON THE |
| | REQUIRED LIGHTING CONTROLS. SOME NOTES ON PLANS |
| | INDICATE DUAL TECHNOLOGY SENSORS TO BE INSTALLED |
| | HOWEVER THIS CONFLICTS THE SYMBOLS ON PLANS AS WELL AS |
| | THE SYMBOL LEGEND. |
| | PLEASE COMPLETE ALL DEVICES IN ALL LOCATIONS AND |
| | PROVIDE ALL MAXIMUM TIMES. |
| | 13-415.1.ABC.1.1,.1.2 AND .1.3. |
| | |
| | ** PLEASE BE SURE DEVICES MEET ADA REQUIREMENTS OF FBC |
| | 11-4.27.4 |
| | |
| | 4) NOTE: PLEASE SUBMIT AND INDICATE MINIMUM LEVELS FOR |
| | ALL ADA DEVICES. (HORNS, STROBES) HEIGHTS ETC. |
| | FBC 11-4.28.1, .2 AND .3.PLEASE BE SURE MINIMUM CD |
| | LEVELS PER PARAGRAPH (4) UNDER SECTION THREE IS MET. |
| | |
| | 5) NOTE: PLEASE BE SURE TO STATE THE FOLLOWING MINIMUM |
| | CODES ON THE PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2003 NFPA-101 |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 6) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON THE |
| | LOAD CALCULATIONS TABLE ARE FROM THE PREVIOUS 2002 NEC. |
| | PLEASE ADJUST TO 2005 CODE. |
| | |
| | 7) NOTE: PLEASE BE SURE TO LIST ALL CIRCUITS ON PANEL |
| | SCHEDULE TO SPECIFIC ROOMS AND AREAS IN WHICH THEY |
| | FEED. FOR EXAMPLE: THE WORDING OF *RECEPTACLES* ON ALL |
| | OF THE CIRCUITS ON PANEL SCHEDULE SHOULD READ RECEPT |
| | ROOM 101,102, 103 OR SOME SORT OF ROOM DESIGNATION. |
| | NEC 408.4 |
| | FBC 106.5, 106.1.1 |
| | |
| | 8) NOTE: PLEASE SUBMIT A COMPLETE THE GROUNDING |
| | ELECTRODE SYSTEM. WATER PIPE (IF METALLIC), FOOTER |
| | STEEL. |
| | 250.50 |
| | |
| | 9) NOTE: PLEASE SEE THE FUTURE INTERIOR BUILD OUT |
| | SPACES SHALL CONTAIN SOME SORT OF BATTERY BACK UP |
| | FIXTURES FOR EGRESS OUT OF THESE SPACES. |
| | LS 101 7.8, 7.9. |
| | |
| | *** AS NOTED ABOVE AS THERE ARE SOME ITEMS NOT SHOWN ON |
| | PLANS AT THIS TIME OR SUBMITTED THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE |
| | MADE AT THIS TIME. |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |