Plan Review Notes
Plan Review Notes For Permit 08070268
Permit Number 08070268
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-30 08:35:17 
 ** DENIEDREVIEW **
  
  
 1) NOTE:PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT COMPLETE AS THE INPUT DATA REPORT AS REQUIRED
 DID NOT ACCOMPANY THE SUMMARY SHEETS.
 PLEASE BE SURE THE CERTIFICATION SHEETS ARE SIGNED,
 DATED AND SEALED AS REQUIRED.
 PLEASE BE SURE THE LOCATION IS UPDATED AS THE COVER
 SHEET DOES LIST ANOTHER MUNICIPALITY.
 PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES WITH
 THE ENERGY CALCULATIONS TO BE SUBMITTED.
 PLEASE SEE THE SQ FT ON PLANS AND CALCULATIONS ARE NOT
 THE SAME.
 PLEASE SEE SECTIONS 13-101.1, 13-103.1, 13-415.2,
 13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 2) NOTE: PLEASE MEET SECTION 13-415.1.ABC.1.4 FOR
 EXTERIOR LIGHTING. THE DETAIL ON SHEET E-8 (#6) DOES
 NOT PROVIDE THE MINIMUM BACK UP AND TYPE OF SYSTEM
 REQUIRED.
  
 3) NOTE: PLEASE SUBMIT COMPLETE INFORMATION ON THE
 REQUIRED LIGHTING CONTROLS. SOME NOTES ON PLANS
 INDICATE DUAL TECHNOLOGY SENSORS TO BE INSTALLED
 HOWEVER THIS CONFLICTS THE SYMBOLS ON PLANS AS WELL AS
 THE SYMBOL LEGEND.
 PLEASE COMPLETE ALL DEVICES IN ALL LOCATIONS AND
 PROVIDE ALL MAXIMUM TIMES.
 13-415.1.ABC.1.1,.1.2 AND .1.3.
  
 ** PLEASE BE SURE DEVICES MEET ADA REQUIREMENTS OF FBC
 11-4.27.4
  
 4) NOTE: PLEASE SUBMIT AND INDICATE MINIMUM LEVELS FOR
 ALL ADA DEVICES. (HORNS, STROBES) HEIGHTS ETC.
 FBC 11-4.28.1, .2 AND .3.PLEASE BE SURE MINIMUM CD
 LEVELS PER PARAGRAPH (4) UNDER SECTION THREE IS MET.
  
 5) NOTE: PLEASE BE SURE TO STATE THE FOLLOWING MINIMUM
 CODES ON THE PLANS.
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 6) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON THE
 LOAD CALCULATIONS TABLE ARE FROM THE PREVIOUS 2002 NEC.
 PLEASE ADJUST TO 2005 CODE.
  
 7) NOTE: PLEASE BE SURE TO LIST ALL CIRCUITS ON PANEL
 SCHEDULE TO SPECIFIC ROOMS AND AREAS IN WHICH THEY
 FEED. FOR EXAMPLE: THE WORDING OF *RECEPTACLES* ON ALL
 OF THE CIRCUITS ON PANEL SCHEDULE SHOULD READ RECEPT
 ROOM 101,102, 103 OR SOME SORT OF ROOM DESIGNATION.
 NEC 408.4
 FBC 106.5, 106.1.1
  
 8) NOTE: PLEASE SUBMIT A COMPLETE THE GROUNDING
 ELECTRODE SYSTEM. WATER PIPE (IF METALLIC), FOOTER
 STEEL.
 250.50
  
 9) NOTE: PLEASE SEE THE FUTURE INTERIOR BUILD OUT
 SPACES SHALL CONTAIN SOME SORT OF BATTERY BACK UP
 FIXTURES FOR EGRESS OUT OF THESE SPACES.
 LS 101 7.8, 7.9.
  
 *** AS NOTED ABOVE AS THERE ARE SOME ITEMS NOT SHOWN ON
 PLANS AT THIS TIME OR SUBMITTED THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE
 MADE AT THIS TIME.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-07-29 17:06:31REVIEW COMPLETED, NOTES TO FOLLOW