| 2008-07-18 15:09:51 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.THE WIND DESIGN CALCULATIONS ARE TO BE IN |
| | ACCORDANCE WITH ASCE7-02, SEE FBC R 43. |
| | |
| | 2.THE APPLICATION STATES THAT THE ROOF IS 3/12, THE |
| | CALCULATIONS ARE FOR A 5/12 ROOF, BUT THE |
| | ENGINEER/CONTRACTOR COMPLETED BOTH DOCUMENTS.PLEASE |
| | CHECK ALL PAPERWORK SUBMITTED FOR ERRORS. |
| | |
| | 3.SEE FBC61G15-23.002, TITLE BLOCK REQUIRED ON EACH |
| | SIGNED, SEALED AND DATED SHEET.FOR CALCULATIONS, AN |
| | INDEX SHEET MUST BE USED OR EACH SHEET SIGNED AND |
| | SEALED. |
| | |
| | 4.PLEASE CONTACT FBPE REGARDING TWO ISSUES: |
| | |
| | AS DISCUSSED, YOU STATED THAT YOU APPLIED FOR A |
| | CERTIFICATE OF AUTHORIZATION OVER SIX WEEKS AGO.I |
| | SPOKE WITH AMANDA, AND THEY DO NOT HAVE RECORD OF THIS |
| | APPLICATION AND IT ALSO DOES NOT APPEAR ON THE |
| | INTERNET, WWW.MYFLORIDALICENSE.COM.IN ORDER TO GET |
| | THIS ISSUE OFF OF MY DESK, I HAVE SENT IT TO FBPE WITH |
| | A COMPLIANT FORM, ESPECIALLY AS YOU HAD BEEN TOLD ON |
| | NUMEROUS OCCASIONS THAT THIS WAS REQUIRED, YOU AGREED, |
| | AND SAID THAT YOU HAD ALREADY APPLIED.AS I AM GETTING |
| | TWO DIFFERENT STORIES, PLEASE RESOLVE THIS WITH FBPE. |
| | |
| | PLEASE ASK FBPE IF YOU CAN DO THIS ENGINEERING AS AN |
| | INDIVIDUAL WITHOUT A COFA, AS THE CONTRACT/APPLICATION |
| | IS WITH THE ENGINEERING COMPANY.THIS IS A LEGAL ISSUE |
| | ON WHICH I PREFER NOT TO MAKE ANY DETERMINATIONS. THE |
| | USUAL SITUATION IS THAT AN ENGINEERING COMPANY DOES NOT |
| | HAVE A COFA, AND PERMIT DOCUMENTS WHICH ARE NOT IN |
| | COMPLIANCE WITH THE FLORIDA STATUTES ARE NOT ACCEPTED |
| | FOR PERMITTING.YOUR SITUATION DIFFERS IN THAT THE |
| | ENGINEERING COMPANY DOES NOT APPEAR ON THE PERMIT |
| | DOCUMENTS, BUT THE PERMIT APPLICATION IS FROM THE |
| | ENGINEERING COMPANY.PLEASE HAVE FBPE PROVIDE AN EMAIL |
| | OR LETTER STATING THAT IT IS ACCEPTABLE FOR YOU TO BE |
| | TAKING CONTRACTS UNDER A & F ENGINEERING INC. AND |
| | SIGNING AND SEALING AS DAVID FORKEY, PE.I ASSUME THAT |
| | YOU HAVE ALREADY DISCUSSED THIS ISSUE WITH THEM THE |
| | FIRST TIME YOU CALLED. |
| | |
| | AS INFORMED PREVIOUSLY, I DO NOT BELIEVE THAT THE |
| | VIOLATION OF FS471.023 CAN PREVENT A PERMIT FROM BEING |
| | ISSUED, BUT I DO NOT BELIEVE THAT I CAN ACCEPT |
| | ENGINEERING FROM THIS COMPANY UNTIL A COFA IS ISSUED. |
| | THIS WAS NOT ON THE FIRST COMMENT LIST BECAUSE DAVID |
| | FORKEY HAD INFORMED ME THAT THE APPLICATION WAS IN |
| | PROGRESS, AND I WAS WAITING FOR A RETURN CALL FROM |
| | FBPE. |
| | |
| | 5.AS I MUST PROVIDE THEM WITH THE PERMIT |
| | APPLICATIONS, THE OTHER NONCOMPLIANCE ISSUES WILL BE |
| | INCLUDED IN THE COMPLAINT (PHOTOCOPY ENGINEERING |
| | SUBMITTED FOR PERMITTING, LACK OF A DATE FOR THE SEAL, |
| | LACK OF TITLE BLOCK, WRONG ENGINEERING STANDARD USED |
| | FOR WIND DESIGN).THIS IS ADVISORY. |
| | |