2008-07-10 11:29:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.A PHOTOCOPY OF THE ENGINEERING WAS PROVIDED.
 PLEASE PROVIDE TWO SIGNED, SEALED, DATED ORIGINALS,
 FS471.
  
 2.PROVIDE THE ROOF HEIGHT, RAS127.CODE COMPLIANCE
 FOR CONTRACTOR?S PROPOSED METHOD OF ATTACHMENT OF ONE
 #14 SCREW CANNOT BE DETERMINED WITHOUT ALL REQUIRED
 INFORMATION.
  
 3.CONTRACTOR?S PROPOSED METHOD OF ATTACHMENT OF ONE
 #14 SCREW IS NOT INCLUDED IN THE PRODUCT APPROVAL.
 THEREFORE, UNLESS ENGINEERING IS PROVIDED, ATTACHMENT
 RESISTANCE FOR 1 #8 SCREW DATA (FROM THE MIAMIDADE NOA)
 WILL BE USED.
  
 4.SEE RAS127.TABLE 1 IS TO BE USED FOR DESIGN
 PRESSURES OR SIGNED, SEALED, DATED CALCULATIONS (FOR
 DESIGN PRESSURES) REQUIRED.
  
 5.THE SEAL FOR THE ENGINEER IS TO INCLUDE A DATE,
 FS471, FAC61G15-23.002.
  