| 2008-07-25 12:14:20 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET 4, SANITARY PLUMBING RISER DIAGRAM: PLEASE |
| | CORRECT THE FOLLOWING ON THE RISER DIAGRAM PER FBC-2004 |
| | PLUMBING SECTIONS |
| | A} THE BRANCH DRAIN AND STACK TO THE WASHING MACHINE |
| | SHALL BE 3 INCH (3"). PER SECTION 406.3 WASTE |
| | CONNECTIONS. |
| | B} A CLEANOUT IS REQUIRED FOR THE WASHING MACHINE |
| | STACK AND IT SHALL BE ACCESSIBLE. PLEASE LOCATE THE |
| | CLEANOUT TO THE EXTERIOR OR LOCATE IT AT 4' A.F.F.. PER |
| | SECTION 708.3.5 BASE OF STACK AND SECTION 708.9 |
| | ACCESS. |
| | C} THE KITCHEN SINK MUST DRAIN DOWNSTREAM OF WET |
| | VENTED BATHROOM 2. PER SECTION 909.1 WET VENT |
| | PERMITTED. |
| | D} THE DEMO OF THE OLD WASHING MACHINE BRANCH DRAIN |
| | CAN NOT HAVE ANY DEAD ENDS.THE BRANCH DRAIN MUST BE |
| | TERMINATED WITHIN 2 FEET OF THE MAIN, AND PLEASE |
| | CLEARLY INDICATE THIS ON THE RESUBMITTAL . PER SECTION |
| | 704.5 DEAD ENDS. |
| | E} A CLEANOUT IS REQUIRED AT THE BASE OF THE LAV STACK |
| | IN THE MASTER BATH. PER SECTION 708.3.5 BASE OF STACK. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |