| 2008-07-09 16:36:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC |
| | 13-101.2.2. |
| | |
| | 2) PLEASE SUBMIT MECHANICAL PLANS AS THE AIR HANDLER |
| | AND CONDENSER UNIT ARE BEING INSTALLED AT THE NEW |
| | ADDITION, PER 2004 WPB AMEND. 106.3.5.4 (10). |
| | |
| | 3) PLEASE SHOW ON PLANS WERE THE CLOTHES DRYER VENT |
| | WILL TERMINATE AT, BE INFORMED THE CLOTHES DRYER VENT |
| | MAY NOT TERMINATE NEAR THE A/C CONDENSER UNIT, PER 2004 |
| | FBC/R R303.4.2. |
| | |
| | 4) THE EXISTING BATH 2 WILL REQUIRE AN EXHAUST FAN AS |
| | THE WINDOW IS BEING ENCLOSED, IF THEIR IS AN EXHAUST |
| | FAN IN THE ROOM, SHOW A EXISTING FAN IF NOT SHOW A NEW |
| | FAN, PER 2004 FBC/R303.3 EXCEPT. |
| | |
| | 5) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR |
| | PREFAB FIREPLACE, PER 2004 FBC/R R1004. |
| | |
| | 6) PER FS 553.885CARBON MONOXIDE ALARM REQUIRED.-- |
| | EVERY BUILDING FOR WHICH A BUILDING PERMIT IS ISSUED |
| | FOR NEW CONSTRUCTION ON OR AFTER JULY 1, 2008, AND |
| | HAVING A FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A |
| | FIREPLACE, OR AN ATTACHED GARAGE SHALL HAVE AN APPROVED |
| | OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10 |
| | FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. PLEASE |
| | COMPLY. |
| | |