| 2008-07-10 15:23:34 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ALL COMMENTS RELATE TO SHEET #4 UNLESS OTHERWISE NOTED. |
| | ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED |
| | PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER |
| | 230.72(A)(1)A DISCONNECT IS SHOWN ON THE RISER BUT |
| | NOT LOCATED ON THE FLOOR PLAN. |
| | |
| | 2} THE POOL HEATER AND PUMP IN THE LOAD CALCULATION IS |
| | NOT ON THE PANEL SCHEDULE, INDICATE OCP AND CONDUCTOR |
| | SIZE. 408.4 NEC. |
| | |
| | 3} THE 60 AMP OCP FOR THE NEW HEAT LOAD OF 5KW IS TOO |
| | LARGE TO PROTECT THE UNIT. 5000/240=20.83 X 125%=26 |
| | AMPS.30 AMP BREAKER MAX. |
| | |
| | 4} 13-606.1.ABC.1.2.4 RECESSED LIGHTING FIXTURES. |
| | RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT |
| | ABUT AN ATTIC SPACE SHALL MEET ONE OF THREE |
| | REQUIREMENTS: INDICATE DESIGNERS INTENTION ON THE |
| | PLAN. |
| | |
| | 5} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 |
| | NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE |
| | LOCATIONS OF THE SOUNDING DEVICES. |
| | |
| | 6} 9B-3.0472 CARBON MONOXIDE PROTECTION. |
| | (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW |
| | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A |
| | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON |
| | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM |
| | USED FOR SLEEPING PURPOSES. |
| | (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR |
| | PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING |
| | IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS |
| | SHALL HAVE BATTERY BACK UP. |
| | (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED |
| | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. |
| | HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.NOTE: |
| | MAY BE COMBINATION SMOKE/CARBON MONOXIDE. |
| | |
| | 7} KITCHEN RECEPTACLES MUST COMPLY WITH 210.8(A)(6) |
| | GFI, INDICATE ON THE PLAN. |
| | |
| | 8} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, LABEL THE |
| | ROOMS ON THE ELECTRICAL PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |