Plan Review Notes
Plan Review Notes For Permit 08070224
Permit Number 08070224
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-10 15:23:34 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET #4 UNLESS OTHERWISE NOTED.
 ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A)(1)A DISCONNECT IS SHOWN ON THE RISER BUT
 NOT LOCATED ON THE FLOOR PLAN.
  
 2} THE POOL HEATER AND PUMP IN THE LOAD CALCULATION IS
 NOT ON THE PANEL SCHEDULE, INDICATE OCP AND CONDUCTOR
 SIZE. 408.4 NEC.
  
 3} THE 60 AMP OCP FOR THE NEW HEAT LOAD OF 5KW IS TOO
 LARGE TO PROTECT THE UNIT. 5000/240=20.83 X 125%=26
 AMPS.30 AMP BREAKER MAX.
  
 4} 13-606.1.ABC.1.2.4 RECESSED LIGHTING FIXTURES.
 RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT
 ABUT AN ATTIC SPACE SHALL MEET ONE OF THREE
 REQUIREMENTS: INDICATE DESIGNERS INTENTION ON THE
 PLAN.
  
 5} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 6} 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.NOTE:
 MAY BE COMBINATION SMOKE/CARBON MONOXIDE.
  
 7} KITCHEN RECEPTACLES MUST COMPLY WITH 210.8(A)(6)
 GFI, INDICATE ON THE PLAN.
  
 8} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, LABEL THE
 ROOMS ON THE ELECTRICAL PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718