| 2008-08-01 16:07:09 | 2004 FBC W/2007 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT 2 COPIES OF ENERGY CALCULATION FORMS AS |
| | REQUIRED BY FBC 13-101.2.2. THE OWNER/AGENT IS REQUIRED |
| | TO SIGN THE FORMS. |
| | |
| | 4) SHOW COMPLIANCE WITH FAC RULE 9B-3.0472 FOR CARBON |
| | MONOXIDE ALARMS. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND LISTING |
| | INFORMATION FOR THE PREFAB FIREPLACE AND CHIMNEY. FBC |
| | R1002 AND R1004 |
| | |
| | 6) PROVIDE BUCK DETAILS FOR THE OVERHEAD GARAGE DOOR. |
| | FBC R613.6.1 |
| | |
| | 7) PROVIDE DETAILS FOR THE ATTACHMENT OF THE NEW |
| | FOOTINGS AND TIE BEAMS TO THE EXISTING STRUCTURE. FBC |
| | R301.1 |
| | |
| | 8) DIFFERENT LENGTHS OF TAPCONS FOR ANCHORING THE DOOR |
| | BUCKS ARE SPECIFIED ON SHEETS 2 AND 3. PLEASE |
| | COORDINATE. |
| | |
| | 9) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10) TWO COPIES OF PRODUCT APPROVALS ARE REQUIRED PER |
| | FBC 106.1* CITY AMENDMENTS. ONE ONE SET WAS SUBMITTED |
| | FOR THE SINGLE HUNG WINDOWS, SWING DOOR AND SLIDING |
| | GLASS DOORS. |
| | |
| | 11) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE |
| | DOOR AND ROOFING MATERIAL FOR THE FLAT ROOF AS REQUIRED |
| | BY DCA RULE 9B-72. |
| | |
| | 12) SPECIFY THE FASTENING METHOD THAT WILL BE USED TO |
| | INSTALL THE MONIER ROOF TILES. CIRCLE THE APPROPRIATE |
| | FASTENING ON THE NOA. FBC R 301.2.1 |
| | |
| | 13) SPECIFY THE FASTENING OPTION AND DESIGN PRESSURE |
| | FOR THE FLAT ROOF SYSTEM THAT WILL BE USED. SUBMIT RAS |
| | 117 CALCULATIONS FOR ENHANCED FASTENING AT PERIMETER |
| | AND CORNER AREAS. FBC R301.2.1 |
| | |
| | 14) THE PLANS SPECIFY SINGLE HUNG WINDOWS AND A PRODUCT |
| | APPROVAL FOR CASEMENT WINDOWS WAS SUBMITTED. PLEASE |
| | CLARIFY. THE PRODUCT APPROVAL FOR THE CASEMENT WINDOWS |
| | IS EXPIRED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |