Plan Review Notes
Plan Review Notes For Permit 08070216
Permit Number 08070216
Review Stop E
Sequence Number 2
Notes
Date Text
2009-03-24 11:58:37 
  
  
 THIS REVIEW WAS DONE UNDER THESE CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 2} THERE ARE NO FEEDER CONDUCTORS SHOWN BETWEEN PANEL
 "A" AND PANEL "B" ON THE RISER DIAGRAM.THERE IS NO OCP
 OR CIRCUITS IN PANEL "A" FOR THIS FEED. INDICATE HOW
 PANEL "B" IS FED, SUBMIT CONDUIT AND CONDUCTOR SIZES.
 SEE 250.122 AND 215.5 NEC 2005.
  
 3} THERE ARE TWO CIRCUITS (11,13) FOR SMALL APPLIANCE
 ON THE SCHEDULE BUT 3 ARE CALCULATED, SEE 4500 WATTS
 FOR THESE CIRCUITS.408.4 NEC
  
 4} THE DISCONNECT FOR ACU #1IS IN VIOLATION OF 110.26
 CLEARANCE REQUIREMENTS IT IS SHOWN ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  