| 2008-10-10 16:57:56 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER |
| | CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.5 |
| | RETENTION OF CONSTRUCTION DOCUMENTS. |
| | THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH |
| | 2007 REVISIONS". |
| | |
| | 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 |
| | EXISTING BUILDING CHAPTER 3. |
| | |
| | 3. NOTE: FROM THE RESUBMITTAL FORM AND WHATS BEING |
| | INDICATED ON SHEET A-2, IT APPEARS THE ENTIRE RESIDENCE |
| | HAS A NEW FLOOR PLAN LAYOUT. PLEASE PROVIDE AN EXISTING |
| | FLOOR PLAN LAYOUT OF THE RESIDENCE THAT CLEARLY |
| | INDICATES EXACTLY WHERE ALL THE EXISTING PLUMBING |
| | FIXTURES WERE LOCATED. PER FBC-2004 CHAPTER 1, (W.P.B. |
| | AS AMENDED SECTION 106.1.2 ADDITIONAL DATA. |
| | |
| | 4. SHEET A-3 TYPICAL PLUMBING ISOMETRIC: PLEASE KNOW |
| | THAT THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN. THE TUB AND LAVATORY |
| | IN ONE OF THE 2ND FLOOR BATHROOMS ARE BEING INDICATED |
| | IN THE WRONG LOCATION. AT A MINIMUM THE SANITARY RISER |
| | DIAGRAM SHALL REFLECT THE FLOOR PLAN. PLEASE PROVIDE A |
| | FLAT LINE DRAWING OF THE PROPOSED SANITARY PLUMBING ON |
| | THE FLOOR PLAN AND CORRELATE THE SANITARY RISER DIAGRAM |
| | WITH IT. PER FBC-2004 PLUMBING CODE SECTION 701.1 AND |
| | 901.1 SCOPE AND FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) |
| | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. SHEET A-3 TYPICAL PLUMBING ISOMETRIC: PLEASE CORRECT |
| | THE FOLLOING ITEMS ON THE SANITARY ISOMETRIC COMPLIANT |
| | WITH THE FBC-2004 PLUMBING CODE SECTIONS. |
| | |
| | A} THE WATER CLOSETS ARE BEING INDICATED WITH TRAPS |
| | BEING INSTALLED FOR THEM. PLEASE KNOW THAT WATER |
| | CLOSETS HAVE INTEGRAL TRAPS AND THAT FIXTURES SHALL NOT |
| | BE DOUBLE TRAPPED. PER SECTION 1002.1 FIXTURE TRAPS. |
| | |
| | B} A LOT OF THE FIXTURES ARE BEING INDICATED AS HAVING |
| | "S" TRAPS. PLEASE KNOW THAT "S" TRAPS ARE PROHIBITED. |
| | PLEASE REFERENCE THE RED CIRCLED PROHIBITED "S" TRAPS |
| | ON THE ISOMETIC AND REVISE. PER SECTION 1002.3 |
| | PROHIBITED TRAPS. |
| | |
| | C} FIXTURE VENTS ARE BEING INDICATED AT THE FIXTURE |
| | TRAP INLET. HOW WILL THESE FIXTURES DRAIN WITH A VENT |
| | IN THEIR FIXTURE TRAP INLET? PLEASE KNOW THAT THE VENT |
| | FOR THE FIXTURE DRAIN SHALL CONNECT ABOVE THE WEIR OF |
| | THE FIXTURE TRAP BEING VENTED. PER SECTION 906.2 |
| | VENTING OF FIXTURE DRAINS. |
| | |
| | D} PLEASE CLARIFY THE VENT TERMINATIONS OF THE STACK |
| | VENT AS TERMINATING OUTDOORS TO OPEN AIR, SUCH AS VENT |
| | THRU ROOF (V.T.R.). PER SECTION 903.3 VENT TERMINATION. |
| | |
| | E} THE PROPOSED 2ND FLOOR SANITARY PLUMBING IS BEING |
| | INDICATED AS CONNECTING TO THE WASHING MACHINE FIXTURE |
| | DRAIN INLET. HOW WILL THE WASHING MACHINE DRAIN? PLEASE |
| | KNOW THAT THE PROPOSED 2ND FLOOR PLUMBING FIXTURES WILL |
| | REQUIRE A SEPERATE DRAINAGE STACK. PER SECTION 908.3 |
| | CONNECTION AT DIFFERENT LEVELS. |
| | |
| | F} NOTE: IF THE PROPOSED DRAINAGE STACK FOR THE 2ND |
| | FLOOR FLOOR PLUMBING IS LOCATED BY THE WASHING MACHINE |
| | PLEASE KNOW THAT VENTS WILL BE REQUIRED FOR THE 1ST |
| | FLOOR L.T. AND KITCHEN FIXTURES. PER SECTION 901.2.1 |
| | VENTING REQUIRED. |
| | |
| | G} NOTE: 2ND FLOOR NEW 3" WASTE LINE BY THE LAV. IS |
| | BEING INDICATED WITH A DEAD END. PLEASE KNOW THAT IN |
| | THE INSTALLATION OF ANY PART OF A DRAINAGE SYSTEM, DEAD |
| | ENDS SHALL BE PROHIBITED. PER SECTION 704.5 DEAD ENDS. |
| | |
| | H} NOTE: CLEANOUTS ARE REQUIRED FOR THE SANITARY SYSTEM |
| | AND THEY SHALL BE LOCATED PER THE FOLLOWING CODE |
| | SECTIONS. |
| | |
| | SECTION 708.3.4 BASE OF STACK. A CLEANOUT |
| | SHALL BE PROVIDED AT THE BASE OF EACH |
| | WASTE OR SOIL STACK |
| | |
| | SECTION 708.3.5 BUILDING DRAIN AND BUILDING SEWER |
| | JUNCTION. THERE SHALL BE A TWO-WAY CLEANOUT NEAR THE |
| | JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER. |
| | |
| | 6. ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA |
| | BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED |
| | NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL |
| | SIGNATURE AND DATE ON SUCH INFORMATION. PER SECTION |
| | *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, |
| | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA |
| | STATUTES 481 AND 471 RESPECTIVELY. |
| | NOTE: ONLY TITLE SHEET CONTAINED THE PRINTED NAME AND |
| | ORIGINAL SIGNATURE OF THE RESPOSIBLE PERSON. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | **PLEASE KNOW THAT ADDITIONAL COMMENTS MAY APPEAR ON |
| | THE NEXT PLUMBING PLAN REVIEW DUE TO THE SANITARY |
| | ISOMETRIC RISER DIAGRAM BEING REVISED. |
| | |
| | END OF COMMENTS: |
| | |