Plan Review Notes
Plan Review Notes For Permit 08070216
Permit Number 08070216
Review Stop P
Sequence Number 1
Notes
Date Text
2008-10-10 16:57:56PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
 THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH
 2007 REVISIONS".
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. NOTE: FROM THE RESUBMITTAL FORM AND WHATS BEING
 INDICATED ON SHEET A-2, IT APPEARS THE ENTIRE RESIDENCE
 HAS A NEW FLOOR PLAN LAYOUT. PLEASE PROVIDE AN EXISTING
 FLOOR PLAN LAYOUT OF THE RESIDENCE THAT CLEARLY
 INDICATES EXACTLY WHERE ALL THE EXISTING PLUMBING
 FIXTURES WERE LOCATED. PER FBC-2004 CHAPTER 1, (W.P.B.
 AS AMENDED SECTION 106.1.2 ADDITIONAL DATA.
  
 4. SHEET A-3 TYPICAL PLUMBING ISOMETRIC: PLEASE KNOW
 THAT THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN. THE TUB AND LAVATORY
 IN ONE OF THE 2ND FLOOR BATHROOMS ARE BEING INDICATED
 IN THE WRONG LOCATION. AT A MINIMUM THE SANITARY RISER
 DIAGRAM SHALL REFLECT THE FLOOR PLAN. PLEASE PROVIDE A
 FLAT LINE DRAWING OF THE PROPOSED SANITARY PLUMBING ON
 THE FLOOR PLAN AND CORRELATE THE SANITARY RISER DIAGRAM
 WITH IT. PER FBC-2004 PLUMBING CODE SECTION 701.1 AND
 901.1 SCOPE AND FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED)
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. SHEET A-3 TYPICAL PLUMBING ISOMETRIC: PLEASE CORRECT
 THE FOLLOING ITEMS ON THE SANITARY ISOMETRIC COMPLIANT
 WITH THE FBC-2004 PLUMBING CODE SECTIONS.
  
 A} THE WATER CLOSETS ARE BEING INDICATED WITH TRAPS
 BEING INSTALLED FOR THEM. PLEASE KNOW THAT WATER
 CLOSETS HAVE INTEGRAL TRAPS AND THAT FIXTURES SHALL NOT
 BE DOUBLE TRAPPED. PER SECTION 1002.1 FIXTURE TRAPS.
  
 B} A LOT OF THE FIXTURES ARE BEING INDICATED AS HAVING
 "S" TRAPS. PLEASE KNOW THAT "S" TRAPS ARE PROHIBITED.
 PLEASE REFERENCE THE RED CIRCLED PROHIBITED "S" TRAPS
 ON THE ISOMETIC AND REVISE. PER SECTION 1002.3
 PROHIBITED TRAPS.
  
 C} FIXTURE VENTS ARE BEING INDICATED AT THE FIXTURE
 TRAP INLET. HOW WILL THESE FIXTURES DRAIN WITH A VENT
 IN THEIR FIXTURE TRAP INLET? PLEASE KNOW THAT THE VENT
 FOR THE FIXTURE DRAIN SHALL CONNECT ABOVE THE WEIR OF
 THE FIXTURE TRAP BEING VENTED. PER SECTION 906.2
 VENTING OF FIXTURE DRAINS.
  
 D} PLEASE CLARIFY THE VENT TERMINATIONS OF THE STACK
 VENT AS TERMINATING OUTDOORS TO OPEN AIR, SUCH AS VENT
 THRU ROOF (V.T.R.). PER SECTION 903.3 VENT TERMINATION.
  
 E} THE PROPOSED 2ND FLOOR SANITARY PLUMBING IS BEING
 INDICATED AS CONNECTING TO THE WASHING MACHINE FIXTURE
 DRAIN INLET. HOW WILL THE WASHING MACHINE DRAIN? PLEASE
 KNOW THAT THE PROPOSED 2ND FLOOR PLUMBING FIXTURES WILL
 REQUIRE A SEPERATE DRAINAGE STACK. PER SECTION 908.3
 CONNECTION AT DIFFERENT LEVELS.
  
 F} NOTE: IF THE PROPOSED DRAINAGE STACK FOR THE 2ND
 FLOOR FLOOR PLUMBING IS LOCATED BY THE WASHING MACHINE
 PLEASE KNOW THAT VENTS WILL BE REQUIRED FOR THE 1ST
 FLOOR L.T. AND KITCHEN FIXTURES. PER SECTION 901.2.1
 VENTING REQUIRED.
  
 G} NOTE: 2ND FLOOR NEW 3" WASTE LINE BY THE LAV. IS
 BEING INDICATED WITH A DEAD END. PLEASE KNOW THAT IN
 THE INSTALLATION OF ANY PART OF A DRAINAGE SYSTEM, DEAD
 ENDS SHALL BE PROHIBITED. PER SECTION 704.5 DEAD ENDS.
  
 H} NOTE: CLEANOUTS ARE REQUIRED FOR THE SANITARY SYSTEM
 AND THEY SHALL BE LOCATED PER THE FOLLOWING CODE
 SECTIONS.
  
 SECTION 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
  
 SECTION 708.3.5 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION. THERE SHALL BE A TWO-WAY CLEANOUT NEAR THE
 JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER.
  
 6. ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA
 BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED
 NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL
 SIGNATURE AND DATE ON SUCH INFORMATION. PER SECTION
 *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
 NOTE: ONLY TITLE SHEET CONTAINED THE PRINTED NAME AND
 ORIGINAL SIGNATURE OF THE RESPOSIBLE PERSON.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **PLEASE KNOW THAT ADDITIONAL COMMENTS MAY APPEAR ON
 THE NEXT PLUMBING PLAN REVIEW DUE TO THE SANITARY
 ISOMETRIC RISER DIAGRAM BEING REVISED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER