| Plan Review Notes For Permit 08070216 |
| Permit Number |
08070216 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-10 14:32:07 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, PER | | | 2004 FBC 13-600.3.A (12-8-06 REVISION). | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-103.3. | | | | | | 3) SUBMIT COOLING LOAD CALCULATIONS, PER 2004 FBC | | | 13-607.1.ABC.1. | | | | | | 4) SUBMIT MECHANICAL (A/C) PLANS, PER 2004 WPB AMEND. | | | 106.3.5.4 (10). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|