| 2008-10-15 11:10:39 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET A-4, UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| | CHANGE THE REFERENCED NEC ON SHEET A-4 IS 2002.NOTE |
| | RELOCATE THE NOTES AND SYMBOLS LEGEND AS THEY ARE |
| | PARTIALLY CUT OFF AS ARE THE CIRCUIT NUMBERS IN PANEL |
| | "B". NOTES #4, 6, AND 8 ON SHEET A-2 SHOULD ALSO BE |
| | LOCATED ON SHEET A-4 |
| | |
| | 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH |
| | 250.52(A)(3) FOR FOOTER STEEL SINCE AVAILABLE. |
| | |
| | 3} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED |
| | FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER |
| | 250.118, SIZED PER 250.122. |
| | |
| | 4} THERE APPEARS TO BE 10 SMALL APPLIANCE CIRCUITS IN |
| | PANEL"B", CLARIFY THE PANEL SCHEDULE PER 408.4 NEC. |
| | |
| | 5} PANEL "A", CIRCUITS #6,8 HAVE A #10 CONDUCTOR |
| | PROTECTED WITH A 40 AMP OCP IN VIOLATION OF 310.16. |
| | |
| | 6} LOCATE THE WATER HEATER AND DISCONNECTING MEANS FOR |
| | SAME ON THE PLAN PER 422.III. |
| | |
| | 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR |
| | DEFICIENCIES. |
| | |
| | 8} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN |
| | SO THAT COMPLIANCE WITH 110.26 CAN BE REMOVED. |
| | |
| | 9} THERE IS A POOL PUMP DISCONNECT SHOWN ON THE PLAN BY |
| | THE A/C DISCONNECTS, BUT NO POOL EQUIPMENT IN THE PANEL |
| | SCHEDULE OR LOAD CALCULATION.408.4, 220.82, 220.83. |
| | |
| | 10} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER |
| | 106.1.1 FBC AS AMENDED. |
| | |
| | 11} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN |
| | MUST PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER |
| | 106.1.3.FBC. |
| | |
| | PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD |
| | SHEETS TO EXPEDITE REVIEW AND SUBMIT WRITTEN RESPONSE |
| | TO THE COMMENTS MADE IN THIS REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |