Plan Review Notes
Plan Review Notes For Permit 08070216
Permit Number 08070216
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-15 11:10:39 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A-4, UNLESS OTHERWISE
 NOTED.
  
 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE THE REFERENCED NEC ON SHEET A-4 IS 2002.NOTE
 RELOCATE THE NOTES AND SYMBOLS LEGEND AS THEY ARE
 PARTIALLY CUT OFF AS ARE THE CIRCUIT NUMBERS IN PANEL
 "B". NOTES #4, 6, AND 8 ON SHEET A-2 SHOULD ALSO BE
 LOCATED ON SHEET A-4
  
 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.52(A)(3) FOR FOOTER STEEL SINCE AVAILABLE.
  
 3} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122.
  
 4} THERE APPEARS TO BE 10 SMALL APPLIANCE CIRCUITS IN
 PANEL"B", CLARIFY THE PANEL SCHEDULE PER 408.4 NEC.
  
 5} PANEL "A", CIRCUITS #6,8 HAVE A #10 CONDUCTOR
 PROTECTED WITH A 40 AMP OCP IN VIOLATION OF 310.16.
  
 6} LOCATE THE WATER HEATER AND DISCONNECTING MEANS FOR
 SAME ON THE PLAN PER 422.III.
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES.
  
 8} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN
 SO THAT COMPLIANCE WITH 110.26 CAN BE REMOVED.
  
 9} THERE IS A POOL PUMP DISCONNECT SHOWN ON THE PLAN BY
 THE A/C DISCONNECTS, BUT NO POOL EQUIPMENT IN THE PANEL
 SCHEDULE OR LOAD CALCULATION.408.4, 220.82, 220.83.
  
 10} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER
 106.1.1 FBC AS AMENDED.
  
 11} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN
 MUST PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD
 SHEETS TO EXPEDITE REVIEW AND SUBMIT WRITTEN RESPONSE
 TO THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  