| Plan Review Notes For Permit 08070215 |
| Permit Number |
08070215 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2009-06-01 10:17:39 | **TEMP FAIL** | | | REVIEW IS IN TEMPORARY FAIL STATUS PENDING RECEIPT OF | | | SIGNED PERMIT APPLICATION FROM THE CONTRACTOR. | | | | | | NOTE: EXTENSION AND RELOCATION OF EXISTING KITCHEN | | | EXHAUST SHALL BE UNDER SEPARATE PERMIT AND EXCLUDED | | | FROM THIS SCOPE OF WORK. | | | | | | NOTE FOR YOUR INFORMATION: MECHANICAL PLAN SHOWS THE | | | KITCHEN EXHAUST FAN AT A MINIMUM HEIGHT OF 40" ABOVE | | | THE ROOD SURFACE. ARCHITECTURAL PLANS SHOW THE FAN | | | SURROUNDED ON 3 SIDES BY A 42" HIGH PARAPET. IF FAN IS | | | TO BE LOCATED IN CLOSE PROXIMITY TO PARAPET (MIN. 2' | | | SEPARATION) THE DISCHARGE OPENING OF THE FAN MUST BE | | | HIGHER THAN THE PARAPET IN ACCORDANCE WITH FBC-M | | | 506.5.5. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|