Plan Review Notes
Plan Review Notes For Permit 08070215
Permit Number 08070215
Review Stop P
Sequence Number 3
Notes
Date Text
2009-01-22 11:44:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A-5 SUBMIT CALCULATIONS FOR THE VERTICAL
 CONTRIBUTION OF THE STORM WATER ON TO ADJACENT EXISTING
 NEIGHBORING BUILDINGS TO THE EAST & WEST SIDE OF THE
 PROPOSED WORK. PLEASE VERIFY ON THE PLANS OR IN A
 SIGNED, SEALED LETTER THAT THE ADJACENT ROOFS WILL BE
 ABLE TO ACCEPT AND DRAIN THE ADDED VERTICAL
 CONTRIBUTION WITH THE EXISTING SYSTEMS PER SECTIONS
 1106 & 1107.
 ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT.
 COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE COMMENT RESPONSE DID NOT
 INDICATE THE TOTAL SQUARE FOOTAGE BEING DRAINED BY THE
 GUTTER AND DOWNSPOUT. PLEASE INDICATE THE SQUARE
 FOOTAGE, THE SIZE OF THE GUTTER AND THE SIZE OF THE
 DOWNSPOUT. TABLES 1106.3 & 1106.6.
  
 5. SHT A-8 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS SHOWING THE SQUARE FOOTAGE BEING
 DRAINED FOR EACH ROOF DRAIN. (SEE ADDED VERTICAL
 CONTRIBUTION ABOVE THE EXISTING ROOF. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH
 AREA. SECTIONS 1106 & 1107 WITH ALL SUB SECTIONS AND
 TABLES. SHOW THE LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS.
 ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT.
 COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE RESPONSE ONLY ADDRESSED
 THE CONTRIBUTION ADDED TO THE ROOF AREAS OF THE
 BUILDINGS ON THE EAST & WEST SIDES OF THE BUILDING. THE
 INFORMATION REQUIRED IS FOR THE EXISTING ROOF OF
 ROXY'S. INDICATE THE TOTAL SQUARE FOOTAGE BEING
 DRAINED. SUBMIT CALCULATIONS FOR THE AREA OF THE ROOF
 AND SHOW 1/2 AREA OF ALL VERTICAL WALLS IN THE
 CALCULATIONS. INDICATE THE SIZE OF THE DOWNSPOUTS, THE
 SIZE OF THE COLLECTOR HEAD FOR THE DOWNSPOUTS AND THE
 SIZE OF THE OVERFLOW SCUPPERS. SUBMIT A DETAIL FOR THE
 OVERFLOW SCUPPERS SHOWING HEIGHT, WIDTH AND DISTANCE
 OFF THE ROOF TO THE FLOW LINE OF THE SCUPPER. SUBMIT A
 DETAIL FOR THE OPENING FOR THE DOWNSPOUTS INDICATING
 THE HEIGH & WIDTH. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES AS WELL AS SECTION 1503.4.3.
  
 6. SUBMIT DETAILS FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. OK
 ___FOR URINAL:
 A. OK
 B. 11-4.18.3 CLEAR FLOOR SPACE
 ******RESPONSE NOTED, COMMENT NOT ADDRESSED.
 C. OK
 ___FOR LAVS:
 A. OK
 ___FOR TOILET ROOM:
 A. 1OK
  
 7. OK
  
 8. SHT P-3 SANITARY RISER DIAGRAM. SANITARY COMBINATION
 WASTE & VENT SYSTEM DOWNSTREAM OF WOMENS TOILET
 REQUIRES 4" DOWNSTREAM OF CLEANOUT & MINIMUM 5" IS
 REQUIRED DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER.
 TABLE 912.3. -- MINIMUM 5" PIPE IS REQUIRED DOWNSTREAM
 OF THE COMBINATION WASTE & VENT INDICATED. SECTION
 704.2.
 ****RESPONSE NOTED, BUT THE VOIDED SHEETS HAVE NOT BEEN
 SUBMITTED FOR COMPARISON. PLEASE SUBMIT ONE SET OF
 PREVIOUSLY REVIEWED SHEETS.
 ******RESPONSE NOTED, BUT THE PIPE SIZE IS STILL SHOWN
 AS 4" DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER IN THE
 COMBINATION WASTE & VENT SYSTEM.
  
 9. OK
  
 10. OK (GAS DELETED)
  
 ***********NEW COMMENTS***********
  
 1B. SHT A-2 SHOW TABLES AND CHAIRS ON 2ND FLOOR AS 15
 NET IS INDICATED FOR MAXIMUM FLOOR AREA ALLOWANCES PER
 OCCUPANT AND 2 W/C'S HAVE BEEN DELETED. SECTION 106.1.1
 AND TABLES 1004.1.2 & 403.1.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2B. SHT P-3 MAXIMUM 20 FIXTURE UNITS ALLOWED ON 4"
 COMBINATION WASTE & VENT SYSTEM. INDICATE PIPE SIZE AND
 TRAP SIZE FOR FLOOR SINK AT 3 COMPARTMENT SINK. IF 3"
 THEN 5" IS REQUIRED DOWNSTREAM OF FLOOR SINK AT BEER
 COOLER/FLOOR DRAIN. TABLE 912.3. PLEASE SHOW DRAINAGE
 FIXTURE UNITS AS THEY ACCUMULATE IN THE SYSTEM ON THE
 SANITARY RISER DIAGRAM. TABLES 710.1(1) & 710.1(2).
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED AS 1 COPY
 OF VOIDED SHEETS HAS NOT BEEN SUBMITTED FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved