| Date |
Text |
| 2009-01-22 11:44:04 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SHT A-5 SUBMIT CALCULATIONS FOR THE VERTICAL |
| | CONTRIBUTION OF THE STORM WATER ON TO ADJACENT EXISTING |
| | NEIGHBORING BUILDINGS TO THE EAST & WEST SIDE OF THE |
| | PROPOSED WORK. PLEASE VERIFY ON THE PLANS OR IN A |
| | SIGNED, SEALED LETTER THAT THE ADJACENT ROOFS WILL BE |
| | ABLE TO ACCEPT AND DRAIN THE ADDED VERTICAL |
| | CONTRIBUTION WITH THE EXISTING SYSTEMS PER SECTIONS |
| | 1106 & 1107. |
| | ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT. |
| | COMMENT NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE COMMENT RESPONSE DID NOT |
| | INDICATE THE TOTAL SQUARE FOOTAGE BEING DRAINED BY THE |
| | GUTTER AND DOWNSPOUT. PLEASE INDICATE THE SQUARE |
| | FOOTAGE, THE SIZE OF THE GUTTER AND THE SIZE OF THE |
| | DOWNSPOUT. TABLES 1106.3 & 1106.6. |
| | |
| | 5. SHT A-8 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS SHOWING THE SQUARE FOOTAGE BEING |
| | DRAINED FOR EACH ROOF DRAIN. (SEE ADDED VERTICAL |
| | CONTRIBUTION ABOVE THE EXISTING ROOF. SHOW 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH |
| | AREA. SECTIONS 1106 & 1107 WITH ALL SUB SECTIONS AND |
| | TABLES. SHOW THE LOCATION OF ALL PRIMARY AND SECONDARY |
| | ROOF DRAINS. |
| | ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT. |
| | COMMENT NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE RESPONSE ONLY ADDRESSED |
| | THE CONTRIBUTION ADDED TO THE ROOF AREAS OF THE |
| | BUILDINGS ON THE EAST & WEST SIDES OF THE BUILDING. THE |
| | INFORMATION REQUIRED IS FOR THE EXISTING ROOF OF |
| | ROXY'S. INDICATE THE TOTAL SQUARE FOOTAGE BEING |
| | DRAINED. SUBMIT CALCULATIONS FOR THE AREA OF THE ROOF |
| | AND SHOW 1/2 AREA OF ALL VERTICAL WALLS IN THE |
| | CALCULATIONS. INDICATE THE SIZE OF THE DOWNSPOUTS, THE |
| | SIZE OF THE COLLECTOR HEAD FOR THE DOWNSPOUTS AND THE |
| | SIZE OF THE OVERFLOW SCUPPERS. SUBMIT A DETAIL FOR THE |
| | OVERFLOW SCUPPERS SHOWING HEIGHT, WIDTH AND DISTANCE |
| | OFF THE ROOF TO THE FLOW LINE OF THE SCUPPER. SUBMIT A |
| | DETAIL FOR THE OPENING FOR THE DOWNSPOUTS INDICATING |
| | THE HEIGH & WIDTH. SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES AS WELL AS SECTION 1503.4.3. |
| | |
| | 6. SUBMIT DETAILS FOR THE TOILET ROOMS SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, 11-4.19 & |
| | 11-4.22 WITH ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | ___FOR W/C'S: |
| | A. OK |
| | ___FOR URINAL: |
| | A. OK |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | ******RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | C. OK |
| | ___FOR LAVS: |
| | A. OK |
| | ___FOR TOILET ROOM: |
| | A. 1OK |
| | |
| | 7. OK |
| | |
| | 8. SHT P-3 SANITARY RISER DIAGRAM. SANITARY COMBINATION |
| | WASTE & VENT SYSTEM DOWNSTREAM OF WOMENS TOILET |
| | REQUIRES 4" DOWNSTREAM OF CLEANOUT & MINIMUM 5" IS |
| | REQUIRED DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER. |
| | TABLE 912.3. -- MINIMUM 5" PIPE IS REQUIRED DOWNSTREAM |
| | OF THE COMBINATION WASTE & VENT INDICATED. SECTION |
| | 704.2. |
| | ****RESPONSE NOTED, BUT THE VOIDED SHEETS HAVE NOT BEEN |
| | SUBMITTED FOR COMPARISON. PLEASE SUBMIT ONE SET OF |
| | PREVIOUSLY REVIEWED SHEETS. |
| | ******RESPONSE NOTED, BUT THE PIPE SIZE IS STILL SHOWN |
| | AS 4" DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER IN THE |
| | COMBINATION WASTE & VENT SYSTEM. |
| | |
| | 9. OK |
| | |
| | 10. OK (GAS DELETED) |
| | |
| | ***********NEW COMMENTS*********** |
| | |
| | 1B. SHT A-2 SHOW TABLES AND CHAIRS ON 2ND FLOOR AS 15 |
| | NET IS INDICATED FOR MAXIMUM FLOOR AREA ALLOWANCES PER |
| | OCCUPANT AND 2 W/C'S HAVE BEEN DELETED. SECTION 106.1.1 |
| | AND TABLES 1004.1.2 & 403.1. |
| | ******NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 2B. SHT P-3 MAXIMUM 20 FIXTURE UNITS ALLOWED ON 4" |
| | COMBINATION WASTE & VENT SYSTEM. INDICATE PIPE SIZE AND |
| | TRAP SIZE FOR FLOOR SINK AT 3 COMPARTMENT SINK. IF 3" |
| | THEN 5" IS REQUIRED DOWNSTREAM OF FLOOR SINK AT BEER |
| | COOLER/FLOOR DRAIN. TABLE 912.3. PLEASE SHOW DRAINAGE |
| | FIXTURE UNITS AS THEY ACCUMULATE IN THE SYSTEM ON THE |
| | SANITARY RISER DIAGRAM. TABLES 710.1(1) & 710.1(2). |
| | ******NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED AS 1 COPY |
| | OF VOIDED SHEETS HAS NOT BEEN SUBMITTED FOR COMPARISON. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |