| Plan Review Notes For Permit 08070215 |
| Permit Number |
08070215 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-01-26 16:12:40 | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM SYSTEM REMODEL. | | | | | | 2. COULD NOT LOCATE ANY ELECTRICAL SHEETS EXCEPT FOR | | | EP-1. | | | | | | 3. LIFE SAFETY PLAN ONLY INDICATES TWO ILLUMINATED EXIT | | | SIGNS WHICH CANNOT BE SEEN FROM ALL AREAS OF THE | | | ROOFTOP. THE TWO SIGNS ARE BLOCKED BY ARCHITECTURAL | | | FEATURES. | | | | | | 4. PLEASE SUBMIT A COMPLETE SET OF PLANS FOR APPROVAL. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|