| 2008-12-18 16:35:00 | |
| | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | THE SAME COMMENT AS THE PREVIOUS TWO REVIEWS |
| | |
| | 3} INDICATE COMPLIANCE WITH LIGHTING POWER |
| | DENSITIES.13-415.2B OR 13-415.2.C.1. FIXTURE TYPES AND |
| | WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE |
| | CALCULATIONS.***THE WATTAGES FOR THE FIXTURES WAS ON |
| | SHEET E-4, BUT NO COUNTS, TOTAL WATTAGES, ALLOWED |
| | WATTAGES ETC***FORM A CANNOT BE USED FOR AN EXISTING |
| | BUILDING, SEE REFERENCED SECTIONS GIVEN IN THE PREVIOUS |
| | REVIEWS. |
| | |
| | NEW COMMENT: |
| | 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE AFFIXED. |
| | (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND |
| | AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, |
| | FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR |
| | ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC |
| | RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED |
| | AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, |
| | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER.*** |
| | THE ELECTRICAL ENGINEER USED A RUBBER STAMP INSTEAD OF |
| | HIS SIGNATURE IN VIOLATION OF THE FAC. THE ELECTRICAL |
| | PLANS ARE BEING RETAINED TO SEND TO THE BOARD OF |
| | ENGINEERS FOR REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |