Plan Review Notes
Plan Review Notes For Permit 08070215
Permit Number 08070215
Review Stop B
Sequence Number 3
Notes
Date Text
2009-01-08 18:02:26****CORRECTIONS****
 ****PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. ADDRESSED.
  
 2. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 561-233-5025. THIS MAY BE DONE AS A PART
 OF THE STRUCTURAL PERMIT, AS IT IS LIKELY THAT THE
 STRUCTURAL PERMIT WILL BE ISSUED FIRST.
  
 3. ADDRESSED.
  
 4. INFORMATIONAL, A PERMIT MUST BE APPLIED FOR PRIOR TO
 MARCH 1, 2009 TO BE ISSUED UNDER FBC2004 W/2007
 REVISIONS AS GOVERNING CODE. THIS IS A PLAN CHECK ONLY.
 THE PLAN REVIEW WILL REMAIN IN FAILED STATUS UNTIL A
 PERMIT APPLICATION IS SUBMITTED.
  
 5-6. PLEASE INCLUDE A COPY OF THE THRESHOLD INSPECTION
 PLAN AND THE RESIDENT INSPECTOR AGREEMENT IN THE
 RESUBMITTAL OR ADVISE IF IT IS A PART OF THE STRUCTURE
 SHELL PERMIT.
  
 7-12. ADDRESSED.
  
 13. SEE FBC1009.11.5, PLEASE SHOW HANDRAIL EXTENSIONS
 WITH DIMENSIONS ON THE PLAN. NOTE THAT EXTENSIONS ARE
 NOT SHOWN ON THE PLAN A3, OTHER PLACES, BUT ARE SHOWN
 ON THE SECTION, A6.
  
 2ND REVIEW, HANDRAIL EXTENSIONS NOT SHOWN AT TOP OF
 STAIR 2, LS1; TOP OF STAIR 1, LS1; FRONT STAIR,
 REMODELED STAIR ENCLOSURE (A2), FIRST FLOOR (A1). IT
 APPEARS THAT THE REQUIRED STAIR EXTENSION AT STAIR 2
 MAY INTERFERE WITH DOOR SWING. REMODELED SECOND FLOOR
 PLAN A2 SHOWS HANDRAIL ON ONE SIDE ONLY (CENTER).
 PLEASE CHECK ALL STAIR PLANS.
  
 3RD REVIEW, COMMENT WAS NOT ADDRESSED. ARCHITECT?S
 RESPONSE WAS: ?ALL STAIR PLANS HAVE BEEN CHECKED AND
 UPDATED TO SHOW THE REQUIREMENTS SET FORTH BY SECTION
 1009.11.5. SEE SHEET LS-1 FOR COMPLIANCE NOTES.?
  
 PLEASE SEE FBC1009.11.5: HANDRAIL EXTENSIONS. HANDRAILS
 SHALL RETURN TO A WALL, GUARD OR THE WALKING SURFACE OR
 SHALL BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT
 STAIR FLIGHT. WHERE HANDRAILS ARE NOT CONTINUOUS
 BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY AT LEAST 12 INCHES BEYOND THE TOP RISER
 AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND
 THE BOTTOM RISER.?
  
 I HAVE HIGHLIGHTED THE AREAS WHERE THE HANDRAIL
 EXTENSIONS ARE MISSING ON THE PLAN (SAME LOCATIONS AS
 PREVIOUS REVIEW). PLEASE REVISE HANDRAILS AT THE
 FOLLOWING LOCATIONS (AND CHECK ALL FOR COMPLIANCE):
  
 A. LS1, PROPOSED STAIR CORRIDOR, TOP LEFT OF FLOOR
 PLAN, ONE HANDRAIL IS MISSING THE EXTENSION AT THE TOP.
  
 B. LS1, PROPOSED ROOF TOP LIFE SAFETY PLAN, TOP LEFT,
 NO EXTENSION ON ONE SIDE OF THE HAND RAIL, TOP. THIS
 EXTENSION WILL BLOCK THE DOOR.
  
 C. LS1, PROPOSED STAIR CORRIDOR, MIDDLE SECTION OF
 STAIR AT LANDING, BY THE 48? DOOR, NO EXTENSION AT
 BOTTOM OF STAIR RUN WHERE THE STAIR CHANGES DIRECTION;
 AS DRAWN, HANDRAIL TO THE INSIDE ENDS BEFORE THE END OF
 THE LAST TREAD.
  
 D. LS1, PROPOSED ROOF TOP LIFE SAFETY PLAN, TOP STAIR
 #2, NO EXTENSION AT THE TOP OF THE STAIR (BY THE DOOR).
 IT APPEARS THAT THIS EXTENSION WILL BLOCK THE DOOR
 (SAME STAIR AREA AS ITEM B).
  
 E. A2, PROPOSED STAIR CIRCULATION PLAN, TOP STAIR #2,
 NO EXTENSION AT THE TOP OF THE STAIR (SAME AS B AND D).
  
 F. SAME STAIR AS (E), A2, PROPOSED STAIR CIRCULATION
 PLAN, INTERMEDIATE LANDING NEAR DOOR 201 MISSING
 HANDRAIL WHERE STAIRS CHANGE DIRECTIONS; ALSO PROPOSED
 STAIR CORRIDOR LIFE SAFETY PLAN LS1.
  
 G. A3 AND LS1, LABELED SOUTH EGRESS STAIR, TOP, BOTH
 SIDES, EXTENSIONS APPEAR LESS THAN THE REQUIRED 12
 INCHES.
  
 14-23. ADDRESSED.
  
 24. CODE COMPLIANCE FOR THIS ITEM (BUILDING TYPE)
 SHOULD BE SHOWN ON THE STRUCTURAL PERMIT, BUT SHOULD BE
 INCLUDED ON THIS PLAN AS WELL. THE NEW PLAN HAS BEEN
 REVISED TO DECLARE TYPE IIIA, RESPONSE LETTER STATES
 THIS IS TYPE IIIB. PLEASE CONFIRM BUILDING TYPE.
  
 25-32. ADDRESSED.
  
 33. PREVIOUS COMMENTS STATED THAT FIRE RESISTANCE IS TO
 BE CONTINUOUS TO THE UNDERSIDE OF THE DECK ABOVE,
 FBC707.4, 707.5. ARCHITECT?S RESPONSE STATED THAT FIRE
 RESISTANCE CONTINUITY REQUIREMENTS WERE STATED ON NTS.
 SEE M2, DUCTWORK SHOWN ABOVE THE STAIRS AND DUCTWORK
 SHOWN IN THE ELEVATOR LOBBY AREA. THE EXIT TERMINATES
 AT THE EXIT DISCHARGE, WHICH WOULD BE THE EXTERIOR
 DOOR, DUCT IS SHOWN AT THE STAIRWAY DOOR.
  
 SHEET A2 SPECIFIES FIRE RATED PARTITIONS FOR THE
 STAIRS. SEE FBC1019.1, FIRE BARRIERS REQUIRED IN
 ACCORDANCE WITH FBC706, NOT FIRE PARTITIONS FBC708. THE
 CONSTRUCTION REQUIREMENTS DIFFER, AND PARTITIONS ARE
 LESS STRINGENT THAN BARRIERS. PLEASE CLARIFY COMPLIANCE
 WITH THE REQUIREMENTS AS A FIRE BARRIER.
  
 FOR INSTANCE, SEE B A12. WALLS W1, W6 SHOW THE WALL
 TERMINATING AT THE CEILING ABOVE RATHER THAN AT THE
 ROOF DECK ABOVE. A A12 ALSO SHOWS THE RATED WALL W6
 ENDING AT A CEILING, RATHER THAN EXTENDING UP TO THE
 BOTTOM OF THE ROOF DECK. IT ALSO SHOWS A 1 HOUR FIRE
 RATED CEILING ABOVE THE STAIR, NOT CLEAR HOW THIS
 COMPLIES WITH THE REQUIREMENT FOR FIRE RATING TO BE
 CONTINUOUS TO THE ROOF DECK OR FLOOR/CEILING ASSEMBLY
 ABOVE. SEE ALSO A14.
  
 AS STRUCTURALS ARE NOT A PART OF THIS PERMIT, AND THE
 RENOVATION IS SOMEWHAT COMPLEX, IT IS DIFFICULT TO
 DETERMINE EXACT CONSTRUCTION BASED ON THE INFORMATION
 PROVIDED. THE WALLS ARE SPECIFIED AS RATED WALLS,
 STRUCTURAL ELEMENTS RATED, BUT NOTE THE REQUIREMENT FOR
 THE SUPPORTING CONSTRUCTION TO BE RATED AS WELL,
 INCLUDING EXISTING CONSTRUCTION (VERTICAL EXITS).
 ARCHITECT?S RESPONSE STATES THAT THE WALLS ARE
 CONTINUOUS, THE PLANS STATE THEY ARE CONTINUOUS, BUT
 THE DETAILS PROVIDED DO NOT SHOW CONTINUOUS WALLS.
 PLEASE REVISE DETAILS TO CLEARLY SHOW COMPLIANCE WITH
 FBC707.4, 707.5, AND REVISE NOTES WHICH SPECIFY FIRE
 PARTITIONS TO SPECIFY FIRE BARRIERS AS REQUIRED BY
 FBC1019.1. ALSO COORDINATE WITH MECHANICAL ENGINEER;
 CLARIFY DUCTS IN THE OPEN SPACE ABOVE STAIRS, WHEN
 STAIR WALLS SHOULD EXTEND TO THE UNDERSIDE OF THE ROOF
 DECK; THERE SHOULD NOT BE AN OPEN SPACE. IF NECESSARY,
 PROVIDE ADDITIONAL SECTION DETAILS TO SHOW COMPLIANCE.
  
 35-36. ADDRESSED.
  
 37. THE STAIR LABELED "FRONT EGRESS STAIR" SHOWS AN
 ELEVATOR LOBBY IN THE STAIR ENCLOSURE ON THE FIRST
 FLOOR. SEE A1. PLEASE SEE FBC1019.1.
  
 3RD REVIEW, RESPONSE LETTER STATES THAT NO MECHANICAL
 EQUIPMENT IS IN THE STAIR ENCLOSURE. SEE SHEET A1,
 BOTTOM LEFT. THIS PLAN SHOWS THE STAIR AND THE ELEVATOR
 IN THE SAME ENCLOSURE. THIS STAIR IS LABELED A "MEANS
 OF EGRESS STAIR". TWO EXITS ARE REQUIRED FROM THIS
 SPACE, FBC1018.1, NOT MEANS OF EGRESS. EXITS SHALL BE
 CONTINUOUS, FBC1018.3. VERTICAL EXIT ENCLOSURE SHALL
 NOT BE USED FOR ANY PURPOSE OTHER THAN MEANS OF EGRESS,
 FBC1019.1. SEE ALSO DEFINITION OF EXIT, FBC1002.
  
 NEW COMMENT:
  
 38. FP SHEETS, DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FS471. SHEETS SUBMITTED DO NOT INCLUDE
 A SIGNATURE, DATE, AND SEAL AND THE PRINTED NAME AND
 LICENSE NUMBER OF THE PERSON WHO IS RESPONSIBLE FOR THE
 DOCUMENT.
  
 39. SEE M2, DUCTS SHOWN THROUGH THE WALL, BUT ISN?T
 THIS WALL ON THE PROPERTY LINE? SEE FBC TABLE 602,
 FBC704.8, NO OPENINGS ALLOWED FOR A. PREVIOUS COMMENTS
 REQUESTED THAT ALL FIRE RATED WALLS AND OTHER ELEMENTS
 BE NOTED ON THE PLAN.
  
  
  