Plan Review Notes
Plan Review Notes For Permit 08070215
Permit Number 08070215
Review Stop P
Sequence Number 2
Notes
Date Text
2008-09-05 17:44:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A-3 SHOWS A WATER TROUGH & WATER FEATURE. PLEASE
 INDICATE IF THERE WILL BE A WATER SUPPLY, DRAIN AND
 OVERFLOW FOR THE WATER FEATURE. INDICATE BACKFLOW
 METHOD IF CONNECTING TO THE POTABLE WATER SUPPLY.
 SECTION 608. SHOW THE TERMINATION OF THE DRAIN AND
 OVERFLOWS FOR THE FOUNTAIN. ARTICLE III SECTIONS 90-124
 & 90-125.
 ****RESPONSE NOTED, BUT THE WATER FEATURES INDICATED AS
 3 STEP WATERFALL FEATURE INTO WATER TROUGH 30" A.F.F.
 BELOW W/RECIRC PUMP (TYPICAL) STILL INDICATED ON SHT
 A-3. COMMENT NOT ADDRESSED.
  
 3. OK
  
 4. SHT A-5 SUBMIT CALCULATIONS FOR THE VERTICAL
 CONTRIBUTION OF THE STORM WATER ON TO ADJACENT EXISTING
 NEIGHBORING BUILDINGS TO THE EAST & WEST SIDE OF THE
 PROPOSED WORK. PLEASE VERIFY ON THE PLANS OR IN A
 SIGNED, SEALED LETTER THAT THE ADJACENT ROOFS WILL BE
 ABLE TO ACCEPT AND DRAIN THE ADDED VERTICAL
 CONTRIBUTION WITH THE EXISTING SYSTEMS PER SECTIONS
 1106 & 1107.
 ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT.
 COMMENT NOT ADDRESSED.
  
 5. SHT A-8 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS SHOWING THE SQUARE FOOTAGE BEING
 DRAINED FOR EACH ROOF DRAIN. (SEE ADDED VERTICAL
 CONTRIBUTION ABOVE THE EXISTING ROOF. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH
 AREA. SECTIONS 1106 & 1107 WITH ALL SUB SECTIONS AND
 TABLES. SHOW THE LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS.
 ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT.
 COMMENT NOT ADDRESSED.
  
 6. SUBMIT DETAILS FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.3 HEIGHT
 ___FOR URINAL:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 ___FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 ___FOR TOILET ROOM:
 A. 11-4.22.3 TURNING AREA IN TOILET ROOM, NOT IN STALL
  
 7. OK
  
 8. SHT P-3 SANITARY RISER DIAGRAM. SANITARY COMBINATION
 WASTE & VENT SYSTEM DOWNSTREAM OF WOMENS TOILET
 REQUIRES 4" DOWNSTREAM OF CLEANOUT & MINIMUM 5" IS
 REQUIRED DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER.
 TABLE 912.3. -- MINIMUM 5" PIPE IS REQUIRED DOWNSTREAM
 OF THE COMBINATION WASTE & VENT INDICATED. SECTION
 704.2.
 ****RESPONSE NOTED, BUT THE VOIDED SHEETS HAVE NOT BEEN
 SUBMITTED FOR COMPARISON. PLEASE SUBMIT ONE SET OF
 PREVIOUSLY REVIEWED SHEETS.
  
 9. OK
  
 10. OK (GAS DELETED)
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED AS 1 COPY
 OF VOIDED SHEETS HAS NOT BEEN SUBMITTED FOR COMPARISON.
  
 ***********NEW COMMENTS***********
  
 1B. SHT A-2 SHOW TABLES AND CHAIRS ON 2ND FLOOR AS 15
 NET IS INDICATED FOR MAXIMUM FLOOR AREA ALLOWANCES PER
 OCCUPANT AND 2 W/C'S HAVE BEEN DELETED. SECTION 106.1.1
 AND TABLES 1004.1.2 & 403.1.
  
 2B. SHT P-3 MAXIMUM 20 FIXTURE UNITS ALLOWED ON 4"
 COMBINATION WASTE & VENT SYSTEM. INDICATE PIPE SIZE AND
 TRAP SIZE FOR FLOOR SINK AT 3 COMPARTMENT SINK. IF 3"
 THEN 5" IS REQUIRED DOWNSTREAM OF FLOOR SINK AT BEER
 COOLER/FLOOR DRAIN. TABLE 912.3. PLEASE SHOW DRAINAGE
 FIXTURE UNITS AS THEY ACCUMULATE IN THE SYSTEM ON THE
 SANITARY RISER DIAGRAM. TABLES 710.1(1) & 710.1(2).
  
 REVIEW BY KEN STEVENS