Plan Review Notes
Plan Review Notes For Permit 08070215
Permit Number 08070215
Review Stop M
Sequence Number 2
Notes
Date Text
2008-09-10 16:27:24REVIEW #: 2ND **PLAN CHECK ONLY**
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. NOT FULLY ADDRESSED. NO INFORMATION IS SHOWN ON
 PLANS REGARDING CODE REQUIREMENTS FOR THE KITCHEN HOOD
 EXHAUST FAN SUCH AS WIND RESISTANCE, CLEARANCES,
 HEIGHTS, SERVICE ACCESS, GUARDS, ETC. SEE PREVIOUS
 COMMENT #2 FOR ALL CODE REQUIREMENTS WHICH NEED TO BE
 ADDRESSED. PROVIDE SUFFICIENT DETAIL TO DEMONSTRATE
 COMPLIANCE WITH ALL OF THESE REQUIREMENTS. ONE OR MORE
 ELEVATION VIEWS MAY BE HELPFUL.
  
 3. OK
  
 4. OK
  
 5. OK
  
 6. THE WRITTEN RESPONSE FROM SEC STATES THAT A
 SPECIFICATION SHEET FOR THE EXHAUST FAN IS ATTACHED. NO
 SUCH DOCUMENTATION COULD BE FOUND WITH THIS SUBMISSION.
 PLEASE ENSURE ALL REFERENCED DOCUMENTATION IS PROVIDED
 WHEN THIS INFORMATION IS BEING USED TO DEMONSTRATE CODE
 COMPLIANCE.
  
 7. OK
  
 8. THE WRITTEN RESPONSE FROM SEC STATES THAT A
 SPECIFICATION SHEET FOR THE REMOTE CONDENSING UNIT IS
 ATTACHED. NO SUCH DOCUMENTATION COULD BE FOUND WITH
 THIS SUBMISSION. PLEASE ENSURE ALL REFERENCED
 DOCUMENTATION IS PROVIDED WHEN THIS INFORMATION IS
 BEING USED TO DEMONSTRATE CODE COMPLIANCE.
  
  
 9. OK. PLEASE FOLLOW-UP WITH SUPPORTING DOCUMENTATIONS.
  
 10. THE WRITTEN RESPONSE FROM SEC STATES THAT ENERGY
 CALCULATIONS AND COOLING LOAD CALCULATIONS ARE
 ATTACHED. NO SUCH DOCUMENTATION COULD BE FOUND WITH
 THIS SUBMISSION. PLEASE ENSURE ALL REFERENCED
 DOCUMENTATION IS PROVIDED WHEN THIS INFORMATION IS USED
 TO DEMONSTRATE CODE COMPLIANCE. CODE COMPLIANCE FOR ALL
 BUILDINGS SHALL BE CERTIFIED BY USE OF APPROVED FORMS
 FOR THE COMPLIANCE METHOD CHOSEN IN ACCORDANCE WITH
 FBCB 13-103.0. ADDITIONS TO EXISTING COMMERCIAL
 BUILDINGS ARE CONSIDERED NEW BUILDING CONSTRUCTION AND
 SHALL COMPLY WITH FBCB SUBCHAPTER 13-4 OF THIS CODE AS
 ALLOWED IN SECTION 101.1.1 IN ACCORDANCE WITH FBCB
 13-101.1.2. COOLING LOAD CALCULATIONS SHALL BE APPENDED
 TO THE ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH
 FBCB 13-407.1.ABC.1.
  
 NEW: DURING THE PREVIOUS REVIEW, I WAS NOT AWARE OF THE
 FACT THAT THE MINI-SPLIT UNITS WERE IN A FIRE-RATED
 STAIR ENCLOSURE. PLEASE SHOW HOW THESE A/C UNITS CAN BE
 INSTALLED IN AN EXIT ENCLOSURE AND BE IN COMPLIANCE
 WITH THE PENETRATION REQUIREMENTS OF FBCB 1019.1.2.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION IN ACCORDANCE WITH THIS SECTION. IT
 WOULD APPEAR THE PENETRATIONS FOR ELECTRICAL,
 REFRIGERANT AND CONDENSATE LINES WOULD BE NECESSARY FOR
 THESE UNITS. ALL OF THESE PENETRATIONS WOULD BE
 PROHIBITED PER 1019.1.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]