Plan Review Notes
Plan Review Notes For Permit 08070215
Permit Number 08070215
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-09-15 15:02:331. ANY REQUIRED FIRE AND LIFE SAFETY SYSTEMS WHICH
 INCLUDES THE FIRE SPRINKLER OR FIRE ALARM SYSTEM THAT
 IS SHUT DOWN FOR MORE THAN 4 HOURS IN A TWENTY FOUR
 HOUR PERIOD WILL REQUIRE A FIRE WATCH. ALL FIRE WATCH
 ACTIVITIES SHALL BE REQUESTED IN WRITING TO THE
 BATTALION CHIEF OF FIRE PREVENTION OR HIS DESIGNEE.
 PERSONNEL PERFORMING FIRE WATCH ACTIVITIES SHALL HAVE
 NO OTHER DUTIES EXCEPT TO PATROL ALL AREAS OF THE
 BUILDING. THESE PERSONNEL ARE REQUIRED TO MAINTAIN A
 LOG OF ACTIVITIES AND BE ABLE TO REPORT EMERGENCIES
 IMMEDIATELY.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER OR FIRE ALARM REMODELING ACTIVITIES.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PLEASE ENSURE THAT ALL EXISTING EMERGENCY LIGHTING
 EQUIPMENT WITHIN THE STAIRWELLS AND IN OTHER LOCATIONS
 ARE OPERATING CORRECTLY.
  
 5. ON PAGE FP-3 STANDPIPE CONNECTIONS ARE SHOWN. THE
 BUILDING DOES NOT HAVE A STANDPIPE SYSTEM SO THE
 STANDPIPE SYSTEM ILLUSTRATED ON THE ROOF ARE NOT
 REQUIRED.
  
 6. FIRE LINE BACKFLOW DEVICE SHALL BE EQUIPPED WITH
 TAMPER SWITCHES, CHAIN AND LOCK.
  
 7. COULD NOT LOCATE NOTES ON ON NOTES PAGE RELATING TO
 CUTTING OR WELDING OPERATIONS OR TO THE FIRE CODE, NFPA
 51B, THAT RELATES TO THIS ACTIVITY.
  
 8. ON PAGE M-2 AIR CONDITIONING EQUIPMENT APPEARS TO BE
 LOCATED IN STAIRWELLS. NFPA 101, THE LIFE SAFETY CODE,
 SECTION 7.1.3.2.1 (6) STIPULATES EQUIPMENT THAT CAN BE
 CONTAINED IN STAIRWELLS. PLEASE REVIEW.
  
 9. EMERGENCY PLAN FOR THE BUILDING NEEDS TO BE PREPARED
 AND SUBMITTED TO THIS OFFICE FOR REVIEW.
  
 10. PLEASE EXPLAIN THE NON RATED DOOR FOR THE PROPOSED
 DRY STORAGE GOODS AREA DIRECTLY ADJACENT TO THE TWO
 RATED FIRE DOORS. IT APPEARS THAT PERSONS WILL HAVE TO
 PASS THIS NON RATED DOOR IN AN EXIT ACCESS AREA TO
 REACH THE RATED FIRE DOORS.
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX