| 2008-09-15 15:02:33 | 1. ANY REQUIRED FIRE AND LIFE SAFETY SYSTEMS WHICH |
| | INCLUDES THE FIRE SPRINKLER OR FIRE ALARM SYSTEM THAT |
| | IS SHUT DOWN FOR MORE THAN 4 HOURS IN A TWENTY FOUR |
| | HOUR PERIOD WILL REQUIRE A FIRE WATCH. ALL FIRE WATCH |
| | ACTIVITIES SHALL BE REQUESTED IN WRITING TO THE |
| | BATTALION CHIEF OF FIRE PREVENTION OR HIS DESIGNEE. |
| | PERSONNEL PERFORMING FIRE WATCH ACTIVITIES SHALL HAVE |
| | NO OTHER DUTIES EXCEPT TO PATROL ALL AREAS OF THE |
| | BUILDING. THESE PERSONNEL ARE REQUIRED TO MAINTAIN A |
| | LOG OF ACTIVITIES AND BE ABLE TO REPORT EMERGENCIES |
| | IMMEDIATELY. |
| | |
| | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER OR FIRE ALARM REMODELING ACTIVITIES. |
| | |
| | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| | |
| | 4. PLEASE ENSURE THAT ALL EXISTING EMERGENCY LIGHTING |
| | EQUIPMENT WITHIN THE STAIRWELLS AND IN OTHER LOCATIONS |
| | ARE OPERATING CORRECTLY. |
| | |
| | 5. ON PAGE FP-3 STANDPIPE CONNECTIONS ARE SHOWN. THE |
| | BUILDING DOES NOT HAVE A STANDPIPE SYSTEM SO THE |
| | STANDPIPE SYSTEM ILLUSTRATED ON THE ROOF ARE NOT |
| | REQUIRED. |
| | |
| | 6. FIRE LINE BACKFLOW DEVICE SHALL BE EQUIPPED WITH |
| | TAMPER SWITCHES, CHAIN AND LOCK. |
| | |
| | 7. COULD NOT LOCATE NOTES ON ON NOTES PAGE RELATING TO |
| | CUTTING OR WELDING OPERATIONS OR TO THE FIRE CODE, NFPA |
| | 51B, THAT RELATES TO THIS ACTIVITY. |
| | |
| | 8. ON PAGE M-2 AIR CONDITIONING EQUIPMENT APPEARS TO BE |
| | LOCATED IN STAIRWELLS. NFPA 101, THE LIFE SAFETY CODE, |
| | SECTION 7.1.3.2.1 (6) STIPULATES EQUIPMENT THAT CAN BE |
| | CONTAINED IN STAIRWELLS. PLEASE REVIEW. |
| | |
| | 9. EMERGENCY PLAN FOR THE BUILDING NEEDS TO BE PREPARED |
| | AND SUBMITTED TO THIS OFFICE FOR REVIEW. |
| | |
| | 10. PLEASE EXPLAIN THE NON RATED DOOR FOR THE PROPOSED |
| | DRY STORAGE GOODS AREA DIRECTLY ADJACENT TO THE TWO |
| | RATED FIRE DOORS. IT APPEARS THAT PERSONS WILL HAVE TO |
| | PASS THIS NON RATED DOOR IN AN EXIT ACCESS AREA TO |
| | REACH THE RATED FIRE DOORS. |
| | |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | 804-4709 PHONE |
| | 804-4774 FAX |