| Plan Review Notes For Permit 08070215 |
| Permit Number |
08070215 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-09-19 16:06:21 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THE SAME COMMENT AS THE PREVIOUS REVIEW | | | | | | 3} INDICATE COMPLIANCE WITH LIGHTING POWER | | | DENSITIES.13-415.2B OR 13-415.2.C.1. FIXTURE TYPES AND | | | WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE | | | CALCULATIONS.***THE WATTAGES FOR THE FIXTURES WAS ON | | | SHEET E-4, BUT NO COUNTS, TOTAL WATTAGES, ALLOWED | | | WATTAGES ETC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|