Plan Review Notes
Plan Review Notes For Permit 08070215
Permit Number 08070215
Review Stop P
Sequence Number 1
Notes
Date Text
2008-08-01 16:36:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA STATUTES
  
 1. SHT A-2 INDICATES A REMODEL OF THE WOMEN'S TOILET
 ROOM. PLEASE SUBMIT AN EXISTING FLOOR PLAN FOR THE
 TOILET ROOM TO DETERMINE THE EXTENT OF THE REMODEL.
  
 2. SHT A-3 SHOWS A WATER TROUGH & WATER FEATURE. PLEASE
 INDICATE IF THERE WILL BE A WATER SUPPLY, DRAIN AND
 OVERFLOW FOR THE WATER FEATURE. INDICATE BACKFLOW
 METHOD IF CONNECTING TO THE POTABLE WATER SUPPLY.
 SECTION 608. SHOW THE TERMINATION OF THE DRAIN AND
 OVERFLOWS FOR THE FOUNTAIN. ARTICLE III SECTIONS 90-124
 & 90-125.
  
 3. SHT A-3 SHOWS PLANTERS. WILL THERE BE IRRIGATION
 AND/OR DRAINAGE TO/FROM THE PLANTERS. PLEASE CLAIRFY.
 SECTIONS 106.1.2, 1101 & FS 373.62.
  
 4. SHT A-5 SUBMIT CALCULATIONS FOR THE VERTICAL
 CONTRIBUTION OF THE STORM WATER ON TO ADJACENT EXISTING
 NEIGHBORING BUILDINGS TO THE EAST & WEST SIDE OF THE
 PROPOSED WORK. PLEASE VERIFY ON THE PLANS OR IN A
 SIGNED, SEALED LETTER THAT THE ADJACENT ROOFS WILL BE
 ABLE TO ACCEPT AND DRAIN THE ADDED VERTICAL
 CONTRIBUTION WITH THE EXISTING SYSTEMS PER SECTIONS
 1106 & 1107.
  
 5. SHT A-8 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS SHOWING THE SQUARE FOOTAGE BEING
 DRAINED FOR EACH ROOF DRAIN. (SEE ADDED VERTICAL
 CONTRIBUTION ABOVE THE EXISTING ROOF. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH
 AREA. SECTIONS 1106 & 1107 WITH ALL SUB SECTIONS AND
 TABLES. SHOW THE LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS.
  
 6. SUBMIT DETAILS FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 7. SHT LS-1 PLUMBING FIXTURE REQUIREMENTS. WATER
 CLOSETS REQUIRED FOR MEN & WOMEN IS 3 EACH. (340/2
 EQUALS 170 EACH MEN/WOMEN). REQUIRED IS INDICATED AS 2.
 1 PER 75 REQUIRES 3 WATER CLOSETS. TABLE 403.1. PLEASE
 CORRECT AMOUNT REQUIRED.
  
 8. SHT P-3 SANITARY RISER DIAGRAM. SANITARY COMBINATION
 WASTE & VENT SYSTEM DOWNSTREAM OF WOMENS TOILET
 REQUIRES 4" DOWNSTREAM OF CLEANOUT & MINIMUM 5" IS
 REQUIRED DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER.
 TABLE 912.3. -- MINIMUM 5" PIPE IS REQUIRED DOWNSTREAM
 OF THE COMBINATION WASTE & VENT INDICATED. SECTION
 704.2.
  
 9. SHT P-3 WATER RISER DIAGRAM. SHUT OFF VALVES ARE
 REQUIRED ON THE SUPPLY PIPES TO THE HOSE BIBBS. SECTION
 606.2(2). -- SHOW ALL PIPE SIZES AND SHOW THE POINT OF
 CONNECTION ON THE RISER DIAGRAM. SECTION 604.
  
 10. A SEPARATE GAS PERMIT IS REQUIRED. (SEE SHT A-5 KEY
 NOTE 6). SUBMIT THE FOLLOWING INFORMATION FOR PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved