| Date |
Text |
| 2008-08-01 16:36:31 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A-2 INDICATES A REMODEL OF THE WOMEN'S TOILET |
| | ROOM. PLEASE SUBMIT AN EXISTING FLOOR PLAN FOR THE |
| | TOILET ROOM TO DETERMINE THE EXTENT OF THE REMODEL. |
| | |
| | 2. SHT A-3 SHOWS A WATER TROUGH & WATER FEATURE. PLEASE |
| | INDICATE IF THERE WILL BE A WATER SUPPLY, DRAIN AND |
| | OVERFLOW FOR THE WATER FEATURE. INDICATE BACKFLOW |
| | METHOD IF CONNECTING TO THE POTABLE WATER SUPPLY. |
| | SECTION 608. SHOW THE TERMINATION OF THE DRAIN AND |
| | OVERFLOWS FOR THE FOUNTAIN. ARTICLE III SECTIONS 90-124 |
| | & 90-125. |
| | |
| | 3. SHT A-3 SHOWS PLANTERS. WILL THERE BE IRRIGATION |
| | AND/OR DRAINAGE TO/FROM THE PLANTERS. PLEASE CLAIRFY. |
| | SECTIONS 106.1.2, 1101 & FS 373.62. |
| | |
| | 4. SHT A-5 SUBMIT CALCULATIONS FOR THE VERTICAL |
| | CONTRIBUTION OF THE STORM WATER ON TO ADJACENT EXISTING |
| | NEIGHBORING BUILDINGS TO THE EAST & WEST SIDE OF THE |
| | PROPOSED WORK. PLEASE VERIFY ON THE PLANS OR IN A |
| | SIGNED, SEALED LETTER THAT THE ADJACENT ROOFS WILL BE |
| | ABLE TO ACCEPT AND DRAIN THE ADDED VERTICAL |
| | CONTRIBUTION WITH THE EXISTING SYSTEMS PER SECTIONS |
| | 1106 & 1107. |
| | |
| | 5. SHT A-8 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS SHOWING THE SQUARE FOOTAGE BEING |
| | DRAINED FOR EACH ROOF DRAIN. (SEE ADDED VERTICAL |
| | CONTRIBUTION ABOVE THE EXISTING ROOF. SHOW 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH |
| | AREA. SECTIONS 1106 & 1107 WITH ALL SUB SECTIONS AND |
| | TABLES. SHOW THE LOCATION OF ALL PRIMARY AND SECONDARY |
| | ROOF DRAINS. |
| | |
| | 6. SUBMIT DETAILS FOR THE TOILET ROOMS SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, 11-4.19 & |
| | 11-4.22 WITH ALL SUBSECTIONS. |
| | |
| | 7. SHT LS-1 PLUMBING FIXTURE REQUIREMENTS. WATER |
| | CLOSETS REQUIRED FOR MEN & WOMEN IS 3 EACH. (340/2 |
| | EQUALS 170 EACH MEN/WOMEN). REQUIRED IS INDICATED AS 2. |
| | 1 PER 75 REQUIRES 3 WATER CLOSETS. TABLE 403.1. PLEASE |
| | CORRECT AMOUNT REQUIRED. |
| | |
| | 8. SHT P-3 SANITARY RISER DIAGRAM. SANITARY COMBINATION |
| | WASTE & VENT SYSTEM DOWNSTREAM OF WOMENS TOILET |
| | REQUIRES 4" DOWNSTREAM OF CLEANOUT & MINIMUM 5" IS |
| | REQUIRED DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER. |
| | TABLE 912.3. -- MINIMUM 5" PIPE IS REQUIRED DOWNSTREAM |
| | OF THE COMBINATION WASTE & VENT INDICATED. SECTION |
| | 704.2. |
| | |
| | 9. SHT P-3 WATER RISER DIAGRAM. SHUT OFF VALVES ARE |
| | REQUIRED ON THE SUPPLY PIPES TO THE HOSE BIBBS. SECTION |
| | 606.2(2). -- SHOW ALL PIPE SIZES AND SHOW THE POINT OF |
| | CONNECTION ON THE RISER DIAGRAM. SECTION 604. |
| | |
| | 10. A SEPARATE GAS PERMIT IS REQUIRED. (SEE SHT A-5 KEY |
| | NOTE 6). SUBMIT THE FOLLOWING INFORMATION FOR PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |