| 2008-07-14 12:21:37 | 1. ALL CONSTRUCTION, ALTERATION, AND DEMOLITION WORK |
| | SHALL COMPLY WITH NFPA 241, THE STANDARD FOR THE |
| | SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION |
| | OPERATIONS. |
| | |
| | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM |
| | AND FIRE SPRINKLER SYSTEM ADDITIONS. NO FIRE SPRINKLER |
| | PLANS SUBMITTED WITH DRAWINGS. |
| | |
| | 3. NO INFORMATION PROVIDED THAT INDICATES THE FACILITY |
| | WILL BE OPEN OR CLOSED DURING THE CONSTRUCTION WORK |
| | REQUIRED FOR THE ROOFTOP AREA. PROPER SEPARATION |
| | BETWEEN CONSTRUCTION AND NONCONSTRUCTION AREAS SHALL BE |
| | PROVIDED. ALL EXITS ARE TO REMAIN CLEAR AND UNBSTRUCTED |
| | DURING CONSTRUCTION ACTIVITIES. |
| | |
| | 4. THE EXIT SIGN DIRECTING PERSONS TO STAIR # 2 MAY NOT |
| | BE READILY VISIBLE. AN ADDITIONAL EXIT SIGN MAY BE |
| | NEEDED TO DIRECT PERSONS TO STAIR # 2. |
| | |
| | 5. ANY CANVAS MATERIAL PLANNED TO BE USED SHALL BE FIRE |
| | RETARDANT SINCE THE CANVAS WILL BE OVER PERSONS HEADS. |
| | |
| | 6. THE PROPOSED SOUTH ELEVATION DOES NOT DISPLAY THE |
| | BUILDING ADDRESS. THE ADDRESS IS REQUIRED TO BE |
| | INSTALLED ON THE PROPER ELEVATION OF THE BUILDING. THE |
| | ADDRESS SHALL BE A MINIMUM OF AT LEAST 6" HIGH AND AT |
| | LEAST 1" WIDE NUMBERS. |
| | |
| | 7. ALL ELECTRICAL SHEETS DSIPLAY THE WRONG ADDRESS, 311 |
| | CLEMATIS STREET. THE OTHER SHEETS OF THE DRAWINGS |
| | DISPLAY 309 CLEMATIS STREET. |
| | |
| | 8. MORE DETAILS NEEDED ON THE GAS LIGHT FIXTURES |
| | DISPLAYED ON THE PLANS. |
| | |
| | 9. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| | |
| | 10. THE PROPOSED THRID FLOOR ROOFTOP DECK PLANS DOES |
| | NOT ILLUSTRATE PORTABLE FIRE EXTINGUIHSER LOCATIONS. |
| | |
| | 11. NO DOOR SCHEDULE PROVIDED. PLEASE PROVIDE A DOOR |
| | SCHEDULE LISTING THE APPROPRIATE FIRE RATINGS AND DOOR |
| | HARDWARE. ALL FIRE RATED DOORS TO COMPLY WITH NFPA 80, |
| | THE STANDARD FOR FIRE DOORS AND WINDOWS AND SHALL BE |
| | EQUIPPED WITH SELF-CLOSING DEVICES TO CAUSE THE DOORS |
| | TO POSITIVELY LATCH WHEN CLOSED. |
| | |
| | 12. SOME MODIFICATIONS MAY BE NECESSARY TO THE SECOND |
| | FLOOR AREA DUE TO THE PROPOSED REMODEL AREA. |
| | |
| | 13. PLEASE PROVIDE STAIR DETAILS FOR THE NEW STAIRS |
| | THAT ARE BEING PROVIDED. THESE DETAILS SHALL INCLUDE |
| | STAIR RISE, RUN, AND TREAD DIMENSIONS. |
| | |
| | 14. PLEASE INDICATE HANDICAP SEATING LOCATIONS ON THE |
| | PROPOSED ROOF TOP FLOOR PLAN. |
| | |
| | 15. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR ALL HANDRAILS AND GUARDRAILS. |
| | |
| | 16. PLEASE PROVIDE PRODUCT INFORMATION FOR THE |
| | INTUMESCENT PAINT DESCRIBED ON SHEET A-10. |
| | |
| | 17. ALL PROPOSED WALKING SURFACES SHALL BE SLIP |
| | RESISTANT. |
| | |
| | 18. THE STORAGE ROOMS AND THE MECHANICAL, ELECTRICAL |
| | ROOM ON THE ROOF MAY NEED TO BE ONE HOUR FIRE RATED |
| | DEPENDING ON THE TYPE OF STORAGE AND EQUIPMENT |
| | CONTAINED WITHIN THEM. PLEASE PROVIDE DETAILS. |
| | |
| | 19. NO MECHANICAL OR PLUMBING SHEETS PROVIDED WITH |
| | DRAWINGS. |
| | |
| | 20. ANY CUTTING AND WELDING ACTIVITIES SHALL CONFORM TO |
| | THE REQUIREMENTS OF 51B, THE STANDARD FOR CUTTING AND |
| | WELDING OPERATIONS. A SEPARATION DISTANCE OF AT LEAST |
| | THIRTY FIVE (35) FEET SHALL BE PROVIDED FROM THESE |
| | OPERATIONS TO ANY COMBUSTIBLE MATERIALS. IF THIS |
| | DISTANCE CANNOT BE ACHEIVED, FIRE RATED TARPS ARE TO BE |
| | USED TO COVER THESE MATERIALS AND A FIRE WATCH BE |
| | IMPLEMENTED. |
| | |
| | 21. PLEASE IDENTIFY EXIT DISCHARGE LOCATIONS AND |
| | IDENTIFY THE MAIN INGRESS/EGRESS ARE FOR THE FACILITY. |
| | |
| | |
| | 22. NO INFORMATION PROVIDED REGARDING THE STANDPIPE |
| | SYSTEM. |
| | |
| | 23. NO INFORMATION RELATED TO ELEVATOR WARNING SIGNS |
| | FOR THE ROOFTOP AREA. |
| | |
| | 24. PLEASE PROVIDE INFORMATION ON EMERGENCY PLANNING |
| | SHOULD AN EMERGENCY DEVELOP WHILE THE ROOFTOP AREA IS |
| | IN OPERATION. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | 804-4709 PHONE |
| | 804-4774 FAX |