Plan Review Notes
Plan Review Notes For Permit 08070215
Permit Number 08070215
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-18 14:35:29 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ADDRESS OF THE PROJECT IS INCORRECT ON THE
 ELECTRICAL SHEETS 106.1.1 FBC AS AMENDED.
  
 2} SUBMIT THREE SETS OF PLANS FOR REVIEW PER 106 FBC AS
 AMENDED.
  
 3} INDICATE COMPLIANCE WITH LIGHING POWER
 DENSITIES.13-415.2B OR 13-415.2.C.1. FIXTURE TYPES AND
 WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  