Plan Review Notes
Plan Review Notes For Permit 08070215
Permit Number 08070215
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-28 15:19:00****CORRECTIONS****
 ****PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE CERTIFICATE OF AUTHORIZATION IS TO BE PRINTED
 ON EACH SHEET, SMITH ENGINEERING CONSULTANTS, INC.,
 FAC61G15-23.002.
  
 2.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.THE
 PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025.THIS MAY BE DONE AS A PART
 OF THE STRUCTURAL PERMIT, AS IT IS LIKELY THAT THE
 STRUCTURAL PERMIT WILL BE ISSUED FIRST.
  
 3.DECLARE TOTAL SQUARE FOOT AREA, PER FLOOR, EXISTING
 BUILDING.DECLARE TOTAL SQUARE FOOT AREA PER FLOOR,
 PROPOSED NEW.PLEASE INCLUDE THE AREA CALCULATIONS
 PRIOR TO IMPACT FEE ASSESSMENT.FOR THE THIRD FLOOR,
 PLEASE NOTE AREA UNDER ROOF, UNDER AIR AND
 UNCONDITIONED, FBC CHAPTER 5 AND IMPACT FEE
 ASSESSMENT.
  
  
 4. INFORMATIONAL, A PERMIT MUST BE APPLIED FOR PRIOR TO
 DECEMBER 31, 2007 TO BE ISSUED UNDER FBC2004 W/2007
 REVISIONS AS GOVERNING CODE.THIS IS A PLAN CHECK
 ONLY.
  
 5.THREE SETS OF PLANS REQUIRED FOR A THRESHOLD
 BUILDING, FS553.71(7), TWO SETS IF IT IS NOT A
 THRESHOLD BUILDING.ALTHOUGH THIS IS A PLAN REVIEW,
 ALL SETS ARE REQUIRED TO BE SUBMITTED AS ALL CITY
 STAMPS ARE PLACED ON EACH SHEET WITH THE EXCEPTION OF
 THE DATE STAMP WHEN EACH TRADE PASSES REVIEW.REVIEWS
 REMAIN IN FAILED STATUS. AFTER A PERMIT IS APPLIED FOR,
 THE REVIEWS ARE CHANGED TO PASS AND, AS ALL STAMPS ARE
 ALREADY ON EACH SHEET, NO ADDITIONAL PLAN REVIEWS ARE
 REQUIRED.FAILURE TO INCLUDE ALL REQUIRED SETS WILL
 RESULT IN A DELAY OF ISSUANCE.
  
 6. THRESHOLD INSPECTOR, FBC*105.13.6 AND FS 553.79(5);
 PLEASE CONTACT KEN CONRAD, 561-805-6666.A
 PRECONSTRUCTION MEETING BETWEEN THE CITY, OWNER,
 CONTRACTOR, SPECIAL INSPECTOR, AND DESIGNER IS
 REQUIRED.APPROVAL OF THE SPECIAL INSPECTOR AND THE
 PRECONSTRUCTION MEETING IS REQUIRED PRIOR TO PERMIT
 ISSUANCE.
  
 7.SEE FBC105.13.4.4 AND FS553.79, THE STATEMENT
 REGARDING CODE COMPLIANCE IS REQUIRED ON THE PLAN FOR
 THRESHOLD BUILDINGS.
  
 8.CS, DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
  
 9.PLANS SHOW REMODELED RESTROOM ON 2ND FLOOR.IT IS
 NOT CLEAR; IS THIS PART OF THIS PERMIT?SPECIFICATIONS
 NOT PROVIDED.
  
 10. A8 SHOWS CABANA TBD, OTHER PLACES SHOW CANVAS
 AWNING.PLEASE CLARIFY.NOTE THAT SEPARATE PERMITS
 WILL BE REQUIRED FOR CANVAS AWNINGS.
  
 11.CS, GOVERNING CODE IS TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.
  
 12. SEE FBC TABLE 503, 50 FEET MAXIMUM FOR A2, TYPE VA
 (NOT 55 FEET AS STATED ON PLAN).
  
 13.SEE FBC1009.11.5, PLEASE SHOW HANDRAIL EXTENSIONS
 WITH DIMENSIONS ON THE PLAN.NOTE THAT EXTENSIONS ARE
 NOT SHOWN ON THE PLAN A3, OTHER PLACES, BUT ARE SHOWN
 ON THE SECTION, A6.
  
 14.SEE FBC11-4.10, ACCESSIBLE ELEVATORS, PLEASE NOTE
 REQUIREMENTS ON THE PLAN.ALSO SEE FBC11-4.10.6, A
 SWING DOOR IS SHOWN A1, BUT ELEVATOR DOOR IS REQUIRED
 TO OPEN AUTOMATICALLY.
  
 15.A1, BOTTOM LEFT, DOES THE NEW DOOR LEAD TO THE
 OUTSIDE?THIS AREA, BETWEEN THE DOOR AND THE OUTSIDE,
 SHOULD HAVE THE SAME LEVEL OF FIRE RESISTANCE AS THE
 STAIRS, FBC1002, FBC1018.3.PLEASE NOTE ON THE PLAN.
  
 16.FBC1003.6, FBC1005.2, THE NEW DOOR (SHEET A1,
 BOTTOM LEFT) ALONG WITH THE DOOR FOR THE EMPLOYEE
 LOCKERS BLOCKS THE EGRESS FOR THE EXISTING EXIT AT THE
 END OF THE CORRIDOR.
  
 17.A DOOR HARDWARE SCHEDULE WAS NOT PROVIDED.PLEASE
 SEE FBC1008.1.8.7 AND NOTE ALL PROPOSED LOCKS AND EXIT
 HARDWARE FBC1008.1.9.
  
 18.A2, PLEASE PROVIDE STAIR DIMENSIONS; WIDTH, TREAD,
 RISER, AND LANDING DIMENSIONS FBC1009.3, FBC1009.4.
 NOTE THAT LANDINGS DO NOT APPEAR TO COMPLY WITH
 FBC1009.4, WIDTH OF LANDINGS SHALL NOT BE LESS THAN THE
 WIDTH OF THE STAIRWAYS THEY SERVE.
  
 19. A1, SEE FBC1008.1.8.8, DOOR SHOULD NOT PROJECT MORE
 THAN 7 INCHES INTO THE REQUIRED WIDTH OF A CORRIDOR
 WHEN FULLY OPEN.THE NEW PLANTER OBSTRUCTS THE DOOR
 SWING.SHOW COMPLIANCE WITH FNC1008.1.8.8.
  
 20.A1, DECLARE OCCUPANT LOAD FOR EXISTING FIRST
 FLOOR; REQUIRED TO DETERMINE REQUIRED EGRESS WIDTH, SEE
 OTHER COMMENTS.
  
 21. A2, PROPOSED STAIR CIRCULATION PLAN, SEE DOUBLE
 DOORS ON LEFT SIDE.SHOW THE DIMENSION OF CLEAR FLOOR
 SPACE ON THE LANDING WITH THE DOORS IN THE OPEN
 POSITION FBC1005.2.SHOW THE REQUIRED WIDTH; APPEARS
 TO BE
  
 22.A2 SHOWS LIQUOR STORAGE.PLEASE SEE TABLE
 FBC307.7(1), AND NOTE MAXIMUMS WHICH WILL BE STORED ON
 THE PLAN. PLEASE ALSO SEE FOOTNOTES.
  
 23. INFORMATIONAL, AS THE STRUCTURAL SHEETS PREPARED BY
 CUTCHER AND GINSBURG WERE SUBMITTED SEPARATELY, THERE
 MAY BE SOME DUPLICATION REQUIRED FOR INFORMATION.BOTH
 PERMITS WILL BE REQUIRED TO SHOW CODE COMPLIANCE
 INDEPENDENTLY.
  
 24.LS1, BUILDING TYPE 5A DECLARED.PLEASE NOTE ALL
 REQUIRED FIRE RESISTANCE ON THE PLAN, BOTH VERTICAL AND
 HORIZONTAL, INCLUDING THE VENTILATION SHAFT.SEE FBC
 TABLE 601 AND 602, ALL EXTERIOR WALLS TO BE A MINIMUM
 OF 1 HOUR.ONE WALL IS SHOWN AS HAVING A 1 HOUR
 RATING, BUT THE OTHER THREE DO NOT.THERE ARE GENERAL
 NOTES, BUT THE PLAN IS TO BE SPECIFIC AS TO
 REQUIREMENTS FBC*106.
  
 25.FBC903.2.1.2, 903.3.1.1, PLEASE CLARIFY SHEET FP3,
 ROOF FIRE PROTECTION PLAN; IS THIS THE OLD ROOF AREA?
 FIRE SPRINKLERS REQUIRED IN THIS CONCEALED SPACE, AND
 IT APPEARS THAT A SPRINKLER PLAN WAS SUBMITTED BUT THE
 TITLE OF THE PLAN IS CONFUSING AS THIS AREA IS NO
 LONGER A ROOF.
  
 26. PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH
 FIRE RESISTIVE RATED ASSEMBLIES, FBC712.
  
 27.PLANS SHOW FIRE RATED DOORS.SEE FBC TABLE 715.3,
 SPECIFY REQUIREMENT.
  
 28. THERE IS A DOOR BETWEEN THE GAZEBO AND STAIR 2 AT
 THE TABLE SEATING AREA.HOW MANY OCCUPANTS DOES THAT
 DOOR SERVE?IT IS CLOSEST TO STAIR 2, SEE FBC1008.1.2
 REGARDING DOOR SWING.
  
 29.PROVIDE PRODUCT APPROVALS FOR THE HARDIPANEL AND
 EXTERIOR DOORS, FAC9B72.
  
 30. A2 SHOWS A RAISED PLATFORM NOTING THAT THIS WILL BE
 ADJUSTED.IS THIS NEW OR EXISTING?STAIRS APPEAR TO
 BE SHOWN BUT NO RAMP, FBC11-4.3.2(3), FBC11-5.7.
  
 31. SHOW ACCESSIBLE SEATING AT FIXED TABLES, FBC11-5.1,
 FBC 11 FIGURE 45.
  
 32. SEE A10, UL ASSEMBLIES ARE SPECIFIED.PLEASE
 PROVIDE A DETAIL OF EACH UL ASSEMBLY ON THE PLAN.
  
 33. SEE A10 AND FBC TABLE 601.TYPE 5A REQUIRES THAT
 ALL STRUCTURAL FRAME AND FLOOR BE 1 HOUR RATED, BUT NOT
 ALL STRUCTURAL ELEMENTS ARE SHOWN AS FIRE RESISTIVE
 RATED.PLEASE REVISE.
  
 34.PROVIDE INFORMATION (SPEC SHEETS) FOR THE
 INTUMESCENT PAINT, FBC7, FBC*106.
  
 35.ENERGY CALCS REQUIRED, FBC13-101.1.2.
  
 36.PROVIDE DETAILS, INCLUDING ALL DIMENSIONS, FOR
 ACCESSIBLE BATHROOMS; TOILET, LAVATORY, GRAB BARS,
 TURNING RADIUS, CLEAR FLOOR SPACE.