| 2008-07-28 15:19:00 | ****CORRECTIONS**** |
| | ****PLAN REVIEW**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.THE CERTIFICATE OF AUTHORIZATION IS TO BE PRINTED |
| | ON EACH SHEET, SMITH ENGINEERING CONSULTANTS, INC., |
| | FAC61G15-23.002. |
| | |
| | 2.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.THE |
| | PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.561-233-5025.THIS MAY BE DONE AS A PART |
| | OF THE STRUCTURAL PERMIT, AS IT IS LIKELY THAT THE |
| | STRUCTURAL PERMIT WILL BE ISSUED FIRST. |
| | |
| | 3.DECLARE TOTAL SQUARE FOOT AREA, PER FLOOR, EXISTING |
| | BUILDING.DECLARE TOTAL SQUARE FOOT AREA PER FLOOR, |
| | PROPOSED NEW.PLEASE INCLUDE THE AREA CALCULATIONS |
| | PRIOR TO IMPACT FEE ASSESSMENT.FOR THE THIRD FLOOR, |
| | PLEASE NOTE AREA UNDER ROOF, UNDER AIR AND |
| | UNCONDITIONED, FBC CHAPTER 5 AND IMPACT FEE |
| | ASSESSMENT. |
| | |
| | |
| | 4. INFORMATIONAL, A PERMIT MUST BE APPLIED FOR PRIOR TO |
| | DECEMBER 31, 2007 TO BE ISSUED UNDER FBC2004 W/2007 |
| | REVISIONS AS GOVERNING CODE.THIS IS A PLAN CHECK |
| | ONLY. |
| | |
| | 5.THREE SETS OF PLANS REQUIRED FOR A THRESHOLD |
| | BUILDING, FS553.71(7), TWO SETS IF IT IS NOT A |
| | THRESHOLD BUILDING.ALTHOUGH THIS IS A PLAN REVIEW, |
| | ALL SETS ARE REQUIRED TO BE SUBMITTED AS ALL CITY |
| | STAMPS ARE PLACED ON EACH SHEET WITH THE EXCEPTION OF |
| | THE DATE STAMP WHEN EACH TRADE PASSES REVIEW.REVIEWS |
| | REMAIN IN FAILED STATUS. AFTER A PERMIT IS APPLIED FOR, |
| | THE REVIEWS ARE CHANGED TO PASS AND, AS ALL STAMPS ARE |
| | ALREADY ON EACH SHEET, NO ADDITIONAL PLAN REVIEWS ARE |
| | REQUIRED.FAILURE TO INCLUDE ALL REQUIRED SETS WILL |
| | RESULT IN A DELAY OF ISSUANCE. |
| | |
| | 6. THRESHOLD INSPECTOR, FBC*105.13.6 AND FS 553.79(5); |
| | PLEASE CONTACT KEN CONRAD, 561-805-6666.A |
| | PRECONSTRUCTION MEETING BETWEEN THE CITY, OWNER, |
| | CONTRACTOR, SPECIAL INSPECTOR, AND DESIGNER IS |
| | REQUIRED.APPROVAL OF THE SPECIAL INSPECTOR AND THE |
| | PRECONSTRUCTION MEETING IS REQUIRED PRIOR TO PERMIT |
| | ISSUANCE. |
| | |
| | 7.SEE FBC105.13.4.4 AND FS553.79, THE STATEMENT |
| | REGARDING CODE COMPLIANCE IS REQUIRED ON THE PLAN FOR |
| | THRESHOLD BUILDINGS. |
| | |
| | 8.CS, DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. |
| | |
| | |
| | 9.PLANS SHOW REMODELED RESTROOM ON 2ND FLOOR.IT IS |
| | NOT CLEAR; IS THIS PART OF THIS PERMIT?SPECIFICATIONS |
| | NOT PROVIDED. |
| | |
| | 10. A8 SHOWS CABANA TBD, OTHER PLACES SHOW CANVAS |
| | AWNING.PLEASE CLARIFY.NOTE THAT SEPARATE PERMITS |
| | WILL BE REQUIRED FOR CANVAS AWNINGS. |
| | |
| | 11.CS, GOVERNING CODE IS TO INCLUDE 2007 |
| | REVISIONS/SUPPLEMENTS. |
| | |
| | 12. SEE FBC TABLE 503, 50 FEET MAXIMUM FOR A2, TYPE VA |
| | (NOT 55 FEET AS STATED ON PLAN). |
| | |
| | 13.SEE FBC1009.11.5, PLEASE SHOW HANDRAIL EXTENSIONS |
| | WITH DIMENSIONS ON THE PLAN.NOTE THAT EXTENSIONS ARE |
| | NOT SHOWN ON THE PLAN A3, OTHER PLACES, BUT ARE SHOWN |
| | ON THE SECTION, A6. |
| | |
| | 14.SEE FBC11-4.10, ACCESSIBLE ELEVATORS, PLEASE NOTE |
| | REQUIREMENTS ON THE PLAN.ALSO SEE FBC11-4.10.6, A |
| | SWING DOOR IS SHOWN A1, BUT ELEVATOR DOOR IS REQUIRED |
| | TO OPEN AUTOMATICALLY. |
| | |
| | 15.A1, BOTTOM LEFT, DOES THE NEW DOOR LEAD TO THE |
| | OUTSIDE?THIS AREA, BETWEEN THE DOOR AND THE OUTSIDE, |
| | SHOULD HAVE THE SAME LEVEL OF FIRE RESISTANCE AS THE |
| | STAIRS, FBC1002, FBC1018.3.PLEASE NOTE ON THE PLAN. |
| | |
| | 16.FBC1003.6, FBC1005.2, THE NEW DOOR (SHEET A1, |
| | BOTTOM LEFT) ALONG WITH THE DOOR FOR THE EMPLOYEE |
| | LOCKERS BLOCKS THE EGRESS FOR THE EXISTING EXIT AT THE |
| | END OF THE CORRIDOR. |
| | |
| | 17.A DOOR HARDWARE SCHEDULE WAS NOT PROVIDED.PLEASE |
| | SEE FBC1008.1.8.7 AND NOTE ALL PROPOSED LOCKS AND EXIT |
| | HARDWARE FBC1008.1.9. |
| | |
| | 18.A2, PLEASE PROVIDE STAIR DIMENSIONS; WIDTH, TREAD, |
| | RISER, AND LANDING DIMENSIONS FBC1009.3, FBC1009.4. |
| | NOTE THAT LANDINGS DO NOT APPEAR TO COMPLY WITH |
| | FBC1009.4, WIDTH OF LANDINGS SHALL NOT BE LESS THAN THE |
| | WIDTH OF THE STAIRWAYS THEY SERVE. |
| | |
| | 19. A1, SEE FBC1008.1.8.8, DOOR SHOULD NOT PROJECT MORE |
| | THAN 7 INCHES INTO THE REQUIRED WIDTH OF A CORRIDOR |
| | WHEN FULLY OPEN.THE NEW PLANTER OBSTRUCTS THE DOOR |
| | SWING.SHOW COMPLIANCE WITH FNC1008.1.8.8. |
| | |
| | 20.A1, DECLARE OCCUPANT LOAD FOR EXISTING FIRST |
| | FLOOR; REQUIRED TO DETERMINE REQUIRED EGRESS WIDTH, SEE |
| | OTHER COMMENTS. |
| | |
| | 21. A2, PROPOSED STAIR CIRCULATION PLAN, SEE DOUBLE |
| | DOORS ON LEFT SIDE.SHOW THE DIMENSION OF CLEAR FLOOR |
| | SPACE ON THE LANDING WITH THE DOORS IN THE OPEN |
| | POSITION FBC1005.2.SHOW THE REQUIRED WIDTH; APPEARS |
| | TO BE |
| | |
| | 22.A2 SHOWS LIQUOR STORAGE.PLEASE SEE TABLE |
| | FBC307.7(1), AND NOTE MAXIMUMS WHICH WILL BE STORED ON |
| | THE PLAN. PLEASE ALSO SEE FOOTNOTES. |
| | |
| | 23. INFORMATIONAL, AS THE STRUCTURAL SHEETS PREPARED BY |
| | CUTCHER AND GINSBURG WERE SUBMITTED SEPARATELY, THERE |
| | MAY BE SOME DUPLICATION REQUIRED FOR INFORMATION.BOTH |
| | PERMITS WILL BE REQUIRED TO SHOW CODE COMPLIANCE |
| | INDEPENDENTLY. |
| | |
| | 24.LS1, BUILDING TYPE 5A DECLARED.PLEASE NOTE ALL |
| | REQUIRED FIRE RESISTANCE ON THE PLAN, BOTH VERTICAL AND |
| | HORIZONTAL, INCLUDING THE VENTILATION SHAFT.SEE FBC |
| | TABLE 601 AND 602, ALL EXTERIOR WALLS TO BE A MINIMUM |
| | OF 1 HOUR.ONE WALL IS SHOWN AS HAVING A 1 HOUR |
| | RATING, BUT THE OTHER THREE DO NOT.THERE ARE GENERAL |
| | NOTES, BUT THE PLAN IS TO BE SPECIFIC AS TO |
| | REQUIREMENTS FBC*106. |
| | |
| | 25.FBC903.2.1.2, 903.3.1.1, PLEASE CLARIFY SHEET FP3, |
| | ROOF FIRE PROTECTION PLAN; IS THIS THE OLD ROOF AREA? |
| | FIRE SPRINKLERS REQUIRED IN THIS CONCEALED SPACE, AND |
| | IT APPEARS THAT A SPRINKLER PLAN WAS SUBMITTED BUT THE |
| | TITLE OF THE PLAN IS CONFUSING AS THIS AREA IS NO |
| | LONGER A ROOF. |
| | |
| | 26. PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH |
| | FIRE RESISTIVE RATED ASSEMBLIES, FBC712. |
| | |
| | 27.PLANS SHOW FIRE RATED DOORS.SEE FBC TABLE 715.3, |
| | SPECIFY REQUIREMENT. |
| | |
| | 28. THERE IS A DOOR BETWEEN THE GAZEBO AND STAIR 2 AT |
| | THE TABLE SEATING AREA.HOW MANY OCCUPANTS DOES THAT |
| | DOOR SERVE?IT IS CLOSEST TO STAIR 2, SEE FBC1008.1.2 |
| | REGARDING DOOR SWING. |
| | |
| | 29.PROVIDE PRODUCT APPROVALS FOR THE HARDIPANEL AND |
| | EXTERIOR DOORS, FAC9B72. |
| | |
| | 30. A2 SHOWS A RAISED PLATFORM NOTING THAT THIS WILL BE |
| | ADJUSTED.IS THIS NEW OR EXISTING?STAIRS APPEAR TO |
| | BE SHOWN BUT NO RAMP, FBC11-4.3.2(3), FBC11-5.7. |
| | |
| | 31. SHOW ACCESSIBLE SEATING AT FIXED TABLES, FBC11-5.1, |
| | FBC 11 FIGURE 45. |
| | |
| | 32. SEE A10, UL ASSEMBLIES ARE SPECIFIED.PLEASE |
| | PROVIDE A DETAIL OF EACH UL ASSEMBLY ON THE PLAN. |
| | |
| | 33. SEE A10 AND FBC TABLE 601.TYPE 5A REQUIRES THAT |
| | ALL STRUCTURAL FRAME AND FLOOR BE 1 HOUR RATED, BUT NOT |
| | ALL STRUCTURAL ELEMENTS ARE SHOWN AS FIRE RESISTIVE |
| | RATED.PLEASE REVISE. |
| | |
| | 34.PROVIDE INFORMATION (SPEC SHEETS) FOR THE |
| | INTUMESCENT PAINT, FBC7, FBC*106. |
| | |
| | 35.ENERGY CALCS REQUIRED, FBC13-101.1.2. |
| | |
| | 36.PROVIDE DETAILS, INCLUDING ALL DIMENSIONS, FOR |
| | ACCESSIBLE BATHROOMS; TOILET, LAVATORY, GRAB BARS, |
| | TURNING RADIUS, CLEAR FLOOR SPACE. |