| 2008-07-08 10:32:46 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS |
| | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THERE ARE NINE BAYS WITH PANELS SHOWN ON THE FLOOR |
| | PLAN, ONLY EIGHT PANELS SHOWN ON THE RISER DIAGRAM. SEE |
| | 240.24(B). PLEASE CORRELATE SAME. |
| | |
| | 2} 230.2 NUMBER OF SERVICES |
| | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| | BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) |
| | THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 |
| | ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND |
| | LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED |
| | TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER |
| | AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING |
| | ONE SERVICE. THERE ARE TWO OVERHEAD SERVICES SHOWN |
| | WHICH IS IN VIOLATION OF THIS ARTICLE.SEE 230.40 |
| | EXCEPTION #2 AND INDICATE IF THAT EXCEPTION APPLIES. |
| | |
| | 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED.NOTE #2 IN THE ELECTRICAL SPECIFICATIONS |
| | REFERENCING THE LATEST EDITION OF THE NEC, WHICH IS |
| | 2008, IS INCORRECT.THE 2005 NEC WAS ADOPTED BY THE |
| | FLORIDA LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE |
| | APPLICATION FOR THIS PROJECT WAS AFTER THAT DATE AND |
| | THE PLANS ARE SUBJECT TO THAT CODE. PLEASE CHANGE ALL |
| | NOTES TO REFLECT THIS CHANGE. |
| | |
| | 4} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL |
| | INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG |
| | WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 5} THE FLOOR PLAN LOCATES THE EXISTING ELECTRICAL |
| | SERVICE, INDICATE IF THE NEW SERVICE IS TO BE INSTALLED |
| | IN THE SAME LOCATION. |
| | |
| | 6} THE SCOPE OF WORK ON THE APPLICATION INDICATES NEW |
| | PANELS IN BAY'S 2 AND 6. PANELS "B" AND "F" WHICH SERVE |
| | THOSE BAYS ARE MARKED "EX SERVICE" ON THE PLAN, PLEASE |
| | CLARIFY. |
| | |
| | 7} ALL THE PANELS ON THE FLOOR PLAN ARE MARKED PANEL |
| | "A", CORRELATE WITH THE RISER DIAGRAM. |
| | |
| | 8} VERIFY THAT THE 3/0 FEEDERS SHOWN FOR 150 AMP LOADS |
| | ARE CORRECT, ALSO VERIFY THE #2 EQUIPMENT GROUND IS |
| | INTENDED TO BE RAN TO PANEL "F", ALTHOUGH NOT A |
| | VIOLATION IF IT IS REQUIRED BY THE ENGINEER ON THE PLAN |
| | IT MUST BE INSTALLED IN THE FIELD OR A REVISION IS |
| | REQUIRED IF CHANGED AT A LATER DATE. SEE 250.66 FOR |
| | REQUIRED SIZE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |