| Date |
Text |
| 2009-01-09 09:39:43 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | ***FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SHEET A1 PROPOSED FLOOR PLAN DOES NOT HAVE ANY |
| | INDICATION OF THE REQUIRED SERVICE SINK (EXISTING OR |
| | PROPOSED). PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER |
| | OF REQUIRED PLUMBING FIXTURES, OCCUPANCY A-3. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHEET A1 PROPOSED FLOOR PLAN MEN BATH #103: PER FBC- |
| | CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION |
| | 11-4.17.3. |
| | (1) THE STANDARD RESTROOM STALL SHALL CONTAIN AN |
| | ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH |
| | LAVATORY TO BE NOT LESS THAT 19 INCHES WIDE BY 17 |
| | INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL |
| | MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO |
| | OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION |
| | 11-4.17 (SEE FIGURE 30(A) AND FIGURE 30(E) AND TO |
| | COMPLY WITH SECTION 11-4,19 OF THE CODE. SUCH |
| | LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED |
| | FIXTURE COUNT FOR THE BUILDING. |
| | (2) THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE |
| | CORNER, DIAGONAL TO THE DOOR. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 8. SHEET A3 (NOW A4) HC LAV. BATH PLAN VIEW DETAIL: |
| | PLEASE CORRECT AND CORRELATE THE SIDE WALL MEASUREMENTS |
| | WITH THE HC LAV. ELEVATION DETAIL. WATER CLOSET SHALL |
| | BE 1'6" AND THE LAVATORY SHALL BE 1'5". PER FBC- |
| | CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION |
| | 11-4.16.2 FOR THE WATER CLOSET AND SECTION 11-4.19.3 |
| | CLEAR FLOOR SPACE. ALSO PLEASE PROVIDE THE FOLOWING |
| | INFORMATION ON THE ELEVATION DETAILS AND SHEET A1 |
| | PROPOSED FLOOR PLAN. |
| | |
| | **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRES THE |
| | FOLLOWING INFORMATION AND CLEAR FLOOR SPACES NEEDS TO |
| | BE INDICATED ON SHEET A1). |
| | 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.5 |
| | FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" HIGH. |
| | |
| | **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL |
| | REQUIRES THE FOLLOWING INFORMATION AND CLEAR FLOOR |
| | SAPCE TO BE INDICATED ON SHEET A1). |
| | 11-4.19.3 CLEAR FLOOR SPACE. 30" X 48" SHALL EXTEND A |
| | MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE |
| | 32). |
| | 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND |
| | ELECTRONICALLY CONTROLLED ARE EXAMPLES. |
| | ****NO RESPONSE, CLEAR FLOOR SPACE FOR THE W/C'S AND |
| | THE LAVS AS WELL AS THE LAV FAUCET REQUIREMENTS WERE |
| | NOT ADDRESSED. |
| | |
| | 9. SHEET A3 (NOW A4) TYPICAL BASE CABINET DETAIL |
| | INDICATES A KOHLER STAINLESS STEEL, LYRIC BAR SINK |
| | K-3288 W/GOOSENECK FAUCET K-11930 FOR ELEV. D ONLY. |
| | REUSED EXISTING SINK FOR ELEV. C ONLY. THIS DETAIL IS |
| | CONFUSING, PLEASE CLEARLY INDICATE THE ROOM NUMBER THIS |
| | SINK AND FAUCET IS BEING INSTALLED IN AND ITS LOCATION |
| | ON SHEET A1 FLOOR PLAN. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 10. SHEET A3 (NOW A4) DRINKING FOUNTAIN DETAIL: PLEASE |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE |
| | ELEVATION DETAIL AND INDICATE THE CLEAR FLOOR SPACE ON |
| | SHEET A1 PROPOSED FLOOR PLAN. |
| | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| | (ELEVATION DETAIL REQUIRES THE FOLLOWING INFORMATION): |
| | 11-4.15.2 SPOUT HIEGHT. SPOUT HEIGHT 36" TO OUTLET |
| | MAXIMUM. (DETAIL INDICATES 36" TO DRINKING FOUNTAIN RIM |
| | NOT THE SPOUT). |
| | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" CLEAR |
| | FLOOR SPACE. |
| | ****RESPONSE NOTED, BUT THE SPOUT HEIGHT AND THE CLEAR |
| | FLOOR SPACE HAVE NOT BEEN ADDRESSED. (NOTE: CLEAR FLOOR |
| | SPACE SHALL BE FORWARD APPROACH). |
| | |
| | 11. SHEET A1 PROPOSED FLOOR PLAN MENS BATH #103 |
| | INDICATES TWO (2) URINALS. PER FBC-CHAPTER 11, FLORIDA |
| | ACCESSIBILITY CODE ONE OF THE URINALS SHALL BE |
| | COMPLIANT TO THE FOLLOWING SECTIONS: |
| | |
| | **11-4.18 URINALS (ELEVATION DETAIL REQUIRED WITH THE |
| | FOLLOWING INFORMATION AND INDICATE THE CLEAR FLOOR |
| | SPACE ON SHT A1 PROPOSED FLOOR PLAN) |
| | 11-4.18.2 HEIGHT. RIM MAXIMUM 17" A.F.F. |
| | 11-4.18.3 CLEAR FLOOR SPACE. 30" X 48" |
| | 11-4.18.4 FLUSH CONTROLS. MAXIMUM 44" A.F.F. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 12. SHEET A1 PROPOSED FLOOR PLAN PLEASE PROVIDE THE |
| | FOLOWING REQUIREMENTS FOR TOILET ROOMS #103, #106, #109 |
| | AND #110 PER FBC-CHAPTER 11, FLORIDA ACCESSIBILITY CODE |
| | SECTIONS. |
| | 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR |
| | SPACE. |
| | 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE |
| | SHALL BE 180-DEGREE WITH A MINIMUM 60" UNOBSTRUCTED |
| | CLEAR FLOOR SPACE (PER 11-4.2.3). |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 13. SHEET M1 SANITARY PLUMBING RISER DOES NOT REFLECT |
| | THE FLOOR PLAN. AT A MINIMUM THE RISER DIAGRAM SHALL |
| | REFLECT THE FLOOR PLAN. PLEASE CORRECT THE FOLLOWING |
| | AND PROVIDE A PLAN VIEW OF THE UNDERGROUND PLUMBING. |
| | PER FBC- PLUMBING SECTION 701.1 SCOPE. |
| | E} NOTE: REQUIRED SERVICE SINK NEEDS TO BE INDICATED ON |
| | THE PROPOSED FLOOR PLAN ON SHEET A1 AND ON THE RISER |
| | DIAGRAM ON SHEET M1 |
| | ****NO RESPONSE, COMMENT SECTION E} NOT ADDRESSED. |
| | (RISER NOW INDICATED ON SHEET P1). |
| | |
| | 14. OK |
| | |
| | 15. SHEET M1 THE SANITARY PLUMBING RISER DIAGRAM NEEDS |
| | THE PRINTED NAME AND SIGNATURE: (OF THE PERSON |
| | DESIGNING THE RISER DIAGRAM) |
| | NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA |
| | BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED |
| | NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL |
| | SIGNATURE AND DATE ON SUCH INFORMATION. PER SECTION |
| | *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, |
| | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| | SIGNATURE AND THE DATE TO SAID DRAWINGS. PER FLORIDA |
| | STATUTES 481 AND 471 RESPECTIVELY. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 16. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3, |
| | PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER |
| | RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR |
| | BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES, |
| | VALVE LOCATIONS, LOCATIONS OF THE WATER SUPPLY LINE |
| | WITH BACKFLOW PREVENTER **608, THERMAL EXPANSION |
| | CONTROL FOR THE WATER HEATER **607.3, AND THE LOCATION |
| | OF THE WATER-HAMMER ARRESTORS WHERE QUICK CLOSING |
| | VALVES ARE UTILIZED. (EXAMPLES=WASH MACHINES, |
| | DISHWASHERS, ICE MAKERS) **604.9. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 17. THE SUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE |
| | DUE TO NOTHING ENTERED FOR WATER HEATER OR PIPING |
| | INSULATION COMPLIANCE. PER FBC- CHAPTER 13, SECTION |
| | 13-412 WATER HEATING SYSTEMS TABLE 13-142.1.ABC.3 |
| | PERFORMANCE REQUIREMENTS FOR WATER HEATING EQUIPMENT, |
| | AND TABLE 13-411.1.ABC.2 MINIMUM PIPE INSULATION. |
| | |
| | ***********NEW COMMENT*********** |
| | |
| | 1B. SHT C-1 REQUIRED PLUMBING FIXTURES. PER TABLE 403.1 |
| | A-3 ASSEMBLY SHOWS THE REQUIRED W/C COUNT TO BE 1 PER |
| | 150 FOR MALE AND 1 PER 75 FOR FEMALE WHICH COMES OUT TO |
| | 1 FOR THE MALE AND 2 FOR THE FEMALE. (TOTAL OCCUPANCY |
| | 195 DIVIDED BY 2 EQUALS 97.5 ROUNDED UP TO 98 MALE & 98 |
| | FEMALE). PLEASE CORRECT REQUIRED PLUMBING FIXTURE |
| | COUNT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |