| 2008-07-10 09:22:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) THE MEN BATH #103 AND WOMEN BATH #106 REQUIRE |
| | EXHAUST FANS, PER 2004 FBC/M 402.3.1 AND TABLE 403.3. |
| | PLEASE CORRECT. (SHOW ON MECHANICAL PLAN WITH CFM'S.) |
| | |
| | 2) PLEASE SHOW ON MECHANICAL PLANS ALL THE SUPPLY AND |
| | RETURN AIR DUCT SIZES, PER 2004 FBC 106.3.5 (IF |
| | EXISTING PLEASE LABEL AS EXISTING). |
| | |
| | 3) SHOW ON MECHANICAL PLAN HOW THE AIR IN THE MAIN HALL |
| | IS RETURNING TO THE AIR HANDLER UNITS, PER 2004 FBC/M |
| | 601.4. |
| | |
| | 4) IF THE AIR HANDLER UNITS ARE EXISTING PLEASE LABEL |
| | AS EXISTING, IF NEW PROVIDE REQUIRED INFORMATION WITH |
| | EQUIPMENT SCHEDULE, AND SHOW THE LOCATION OF THE |
| | CONDENSER UNITS, PER 2004 FBC 106.3.5. |
| | |
| | 5) SHOW THE BATHROOM EXHAUST FANS (WITH CFM'S) FOR MEN |
| | BATH #109 AND WOMEN BATH #110 ON THE MECHANICAL PLAN, |
| | PER 2004 FBC/M 402.3.1 AND TABLE 403.3. |
| | |
| | 6) MECHANICAL PLAN M1 HAS A PLUMBING RISER DIAGRAM ON |
| | IT, ROLAND'S A/C IS NOT A LICENSED PLUMBING CONTRACTOR |
| | AND MAY NOT DESIGN PLUMBING RISERS. SEE F.S 471.003 |
| | (H). PLEASE REMOVE FROM MECHANICAL PLAN. |
| | |
| | 7) THE MECHANICAL PLANS NEED THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND |
| | CONTRACTORS LICENSE NUMBER ON THEM, SEE W.P.B. AMEND. |
| | 106.1.3. |
| | |
| | *** BE ADVISED THE MECHANICAL CONTRACTOR WILL NEED TO |
| | SIGN ON FOR THE MECHANICAL PERMIT BEFOR THE MECHANICAL |
| | PLANS PASS REVIEW AS HE IS THE DESIGNER, SEE FS 471.003 |
| | (H). |
| | |