| 2008-07-21 15:31:49 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS |
| | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THERE IS AN ELECTRICAL SHEET SUBMITTED BUT THE SCOPE |
| | OF WORK IS NOT CLEAR. INDICATE WHAT WORK IS EXISTING |
| | (IF ANY) AND WHAT IS TO BE INSTALLED UNDER THIS PERMIT. |
| | |
| | 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1 FBC, |
| | PERFORMANCE CALCULATION PROCEDURES. SEE 13-415.2B OR |
| | 13-415.2.C.1 DENSITIES.SUBMIT A LEGEND OF FIXTURE TYPES |
| | AND WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN |
| | THE CALCULATIONS |
| | |
| | 3} METHOD ?A? ENERGY CALCULATIONS WERE SUBMITTED FOR |
| | THIS PROJECT. METHOD ?A? CAN BE USED FOR ?WHOLE |
| | BUILDINGS?. AS THIS IS AN ?EXISTING BUILDING ? BY |
| | DEFINITION?, FORM ?A? IS NEITHER REQUIRED OR ALLOWED. |
| | SEE 13-101.6. ALL THAT IS REQUIRED FOR THE ELECTRICAL |
| | REVIEW IS THE BASIC PRESCRIPTIVE REQUIREMENTS. |
| | |
| | 4} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| | DEVICES.106.3.5 FBC. |
| | |
| | 5} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| | PLAN. |
| | |
| | 6} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 |
| | (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE |
| | SAME ON PLANS. |
| | |
| | 7} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 |
| | FBC AS AMENDED. |
| | |
| | 8} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER |
| | 106.1.3.FBC. |
| | |
| | 9} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS |
| | AMENDED.UNDER 471.003 FS THE CONTRACTOR OF RECORD MAY |
| | DRAW THE DESIGN IF HE IS THE INSTALLER |
| | |
| | 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14, RECEPTACLE PER 210.63.AND LIGHT PER 210.70(A) |
| | (3) IF APPLIOCABLE.. |
| | . |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |