2008-07-08 14:17:092004 FBC W/2007 REVISIONS
 INSTALL ACCORDION SHUTTERS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE ACCORDIONS ARE BEING INSTALLED ON A HIGH RISE
 BUILDING WITH A MEAN ROOF HEIGHT OF MORE THAN 60 FEET.
 SUBMIT SIGNED AND SEALED ENGINEERING FOR THE OPENING
 PRESSURES. FBC 1609.1.1
  
 3) THE WALL PRESSURES SPECIFIED 0N THE INSTALLATION
 SCHEDULE ARE INCORRECT. USE PRESSURES DETERMINED BY
 ENGINEERED CALCULATIONS. FBC 1609.1.1
  
 4) THE FASTENER SPACINGS IN THE TABLES ARE FOR 3-1/2"
 EDGE DISTANCE. THE ANCHOR SPACINGS ARE REQUIRED TO BE
 REDUCED IF EDGE DISTANCE IS LESS. SEE SHEET 11 OF
 DRAWINGS. NOTE: 2" EDGE DISTANCE IS NOT ALLOWED FOR ALL
 POINTS SOLID SET ANCHORS.
  