| Plan Review Notes For Permit 08070180 |
| Permit Number |
08070180 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-08 14:14:15 | 2004 FBC W/2007 REVISIONS | | | INSTALL ACCORDION SHUTTERS | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. | | | | | | 2) THE ACCORDIONS ARE BEING INSTALLED ON A HIGH RISE | | | BUILDING WITH A MEAN ROOF HEIGHT OF MORE THAN 60 FEET. | | | SUBMIT SIGNED AND SEALED ENGINEERING FOR THE OPENING | | | PRESSURES. FBC 1609.1.1 | | | | | | 3) THE WALL PRESSURES SPECIFIED 0N THE INSTALLATION | | | SCHEDULE ARE INCORRECT. USE PRESSURES DETERMINED BY | | | ENGINEERED CALCULATIONS. FBC 1609.1.1 | | | | | | 4) THE FASTENER SPACINGS IN THE TABLES ARE FOR 3-1/2" | | | EDGE DISTANCE. THE ANCHOR SPACINGS ARE REQUIRED TO BE | | | REDUCED IF EDGE DISTANCE IS LESS. SEE SHEET 11 OF | | | DRAWINGS. NOTE: 2" EDGE DISTANCE IS NOT ALLOWED FOR ALL | | | POINTS SOLID SET ANCHORS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|