2008-08-07 17:27:57*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE REQUIRED MEANS OF EGRESS AND REUIRED FIRE
 PROTECTION FEATURES ARE TO BE IN PLACE AND CONTINUOUSLY
 MAINTAINED.
  
 3.WHEN/IF FIRE PROTECTION SYSTEMS ARE TO BE SHUT
 DOWN, THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE
 SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED TO
 SERVICE.
  
 4.PROVIDE PRECAUTIONARY MEASURES TO BE TAKEN TO
 PREVENT IGNITION OF FLAMMABLE VAPORS AND/OR LIQUIDS FOR
 LIFE SAFETY, FOR MINIMIZING PROPERTY LOSS, AND FOR
 REDUCING FIRE EXPOSURE TO ADJOINING FACILITIES FROM
 FIRE AND EXPLOSION.
  
 5.ON SHEET E-1 IN THE SHOP DRAWING NOTE, REFERENCE IS
 MADE TO THE CITY OF MIAMI BEACH.PLEASE BE ADVISED
 THAT THE CORRECT AHJ IS THE CITY OF WEST PALM BEACH.
  
 6.HOW WILL THE FUEL TANK BE REFILLED?
  
 7.PROVIDE SPEC/CUT SHEETS FOR THE PROPOSED FUEL
 TANK.
  
 8.SINCE THE WALLS ARE REQUIRED TO BE FIRE RATED, ANY
 WALL OPENING SHALL HAVE FIRE PROTECTION RATING IN
 ACCORDANCE WITH THE REQUIREMENTS OF NFPA 80, STANDARD
 FOR FIRE DOORS AND WINDOWS.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW