Plan Review Notes
Plan Review Notes For Permit 08070177
Permit Number 08070177
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-21 14:41:56BUILDING PLAN REVIEW
 PERMIT: 08070177
 ADD: 717 S OLIVE AV
 CONT: KAST CONSTRUCTION
 TEL: (561)835-3890
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
 STRUCTURAL DRAWINGS INDICATE THE 2001 FBC AND ASCE
 7-98, PLEASE CORRECT.
  
 2) PLANS FAIL TO INDICATE THE OCCUPANCY CLASSIFICATION
 OF THE DEISEL FUEL STORAGE TANK ROOM. PLEASE SEE 302.1.
 DEISEL FUEL IS CLASSIFIED AS A CLASS II COMBUSTBLE
 LIQUID WITH A FLASH POINT BETWEEN 100-140 TABLE
 307.7(1)FOR STORAGE OR FOR USED AS CLOSED SYSTEMS
 ONLY ALLOWS 120 GALLONS AND FOOTNOTE "D" ONLY ALLOWS
 100% INCREASE FOR FIRE SPRINKLERS. THIS AMOUNT OF FUEL
 WILL CREATE A H-3 OCCUPANCY.
 307.9 EXCEPTION# 5 WILL EXEMPT FROM A H OCCUPANCY BUT
 THE MORE RESTRICTIVE REQUIREMENTS OF NFPA 37 SECTION
 63.6.1 WILL STILL APPLY.
  
 3) PLEASE PROVIDE MANUFACTURERS SPECS ON THE FUEL
 STORAGE TANK, P-1 INDICATE THIS TANK TO BE A DOUBLE
 -WALLED SYSTEM. 415.7.2.3/ 415.7.2.5.
  
 4) PLEASE SEE THE MECHANICAL COMMENT NUMBER 4 IN
 REGARDS TO HOURLY RATING OF WALLS, FLOORS AND DOORS.
 NFPA37-02 SECTION 6.3.6.1
  
 .6.3.6 ROOMS HOUSING ONLY FUEL TANKS WITH AN AGGREGATE
 CAPACITY OF MORE THAN 5000 L (1320 GAL).
  
 6.3.6.1 ROOMS CONTAINING ONLY FUEL TANKS SHALL BE
 CONSTRUCTED OF WALLS, FLOOR, AND CEILING HAVING A FIRE
 RESISTANCE RATING OF NOT LESS THAN 3 HOURS WITH THE
 WALLS BONDED TO THE FLOOR.
  
 6.3.6.1.1 IF THE WALLS OF SUCH ROOMS EXTEND TO AND ARE
 BONDED TO THE UNDERSIDE OF A CONCRETE FLOOR OR ROOF
 ABOVE THAT HAS A FIRE RESISTANCE RATING OF NOT LESS
 THAN 3 HOURS, A SEPARATE CEILING SHALL NOT BE REQUIRED
 FOR THE ROOM.
  
 5) ET P-1 ALSO INDICATES THE EMRGENCY VENTS WITHIN THE
 ROOM, 415.7.2.7 TANK VENTS FOR CLASS II LIQUIDS SHALL
 TERMINATE TO THE OUTDOOR AIR IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 6) SHEET A3 INDICATES TWO NEW EXTERIOR WALL LOUVERS,
 PLEASE SUBMIT 2 COPIES OF FLORIDA PRODUCT APPROVALS AS
 REQUIRED BY RULE 9B-72.PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.