| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | PROVIDE THE FOLLOWING FOR REVIEW |
| | |
| | 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED |
| | LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM |
| | PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY |
| | EASEMENTS INVOLVED. THE GENERATOR MAY NOT INTRUDE MORE |
| | THAN 4 (FOUR) FEET INTO A SETBACK, AND MAY NOT EXHAUST |
| | CLOSER THAN 5 (FIVE) FEET TO A DIRECT OPENING IN THE |
| | RESIDENCE. CONTACT THE WPB ZONING DEPARTMENT FOR |
| | DETAILS REGARDING SETBACKS. |
| | |
| | 2} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE |
| | THE FOLLOWING: |
| | |
| | A) GENERATOR AND TRANSFER SWITCH MANUFACTURER |
| | SPECIFICATIONS. |
| | |
| | |
| | B) RISER DIAGRAM SHOWING LOCATIONS OF ALL |
| | EQUIPMENT ELECTRICALLY. |
| | |
| | C) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE |
| | EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE |
| | STRUCTURES. |
| | |
| | D) MANUFACTURER SETBACK RECOMMENDATIONS FROM |
| | STRUCTURES |
| | |
| | G) THE INSTALLATION OF THE SLAB, PAD OR BASE IS |
| | INCIDENTAL TO THE ELECTRICAL CONTRACTOR?S SCOPE. WILL |
| | BE REQUIRED TO BE INSPECTED. PROVIDE ENGINEERING AND |
| | TIE DOWN SPECIFICATIONS FOR 140 MPH WIND LOADING. |
| | |
| | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| | IF EXEMPTIONS APPLY. |
| | |