Plan Review Notes
Plan Review Notes For Permit 08070134
Permit Number 08070134
Review Stop B
Sequence Number 6
Notes
Date Text
2008-12-19 14:26:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 COMMENT FROM PREVIOUS LIST:
  
 4. IF PULLOUT VALUE FOR #10 SCREW IS 109, WITH A SAFETY
 FACTOR OF 2, SHOULDN'T IT BE DIVIDED BY TWO RATHER THAN
 MULTIPLIED BY TWO? CAPACITY WITH STRESS INCREASE FROM
 CALCULATIONS PROVIDED IS 290; IT DOES NOT SEEM LOGICAL
 WHEN PRODUCT DATA STATES 109. THIS COMMENT ALSO APPLIES
 TO SHEAR FOR #10 AND PULLOUT AND SHEAR FOR #12. PLEASE
 EXPLAIN CALCULATION.
  
 2ND ROOFTOP EQUIPMENT WIND LOAD CALC REVIEW:
  
 ALL COMMENTS WERE ADDRESSED EXCEPT FOR ITEM 4. PLEASE
 CONTACT ME TO EXPLAIN RATIONALE. IT APPEARS THAT THE
 CAPACITY OF THE SCRE HAS BEEN INCREASED BY 3/2 (109
 PULLOUT TIMES 3/2). FOR A FACTOR OF SAFETY OF 2,
 SHOULDN'T IT BE MULTIPLIED BY 1/2, REDUCING IT BY HALF?
 IT APPEARS THAT THE SCREW CAPACITY HAS BEEN INCREASED
 BY 50%.
  
 DUE TO THE URGENCY OF GETTING THIS MATTER RESOLVED,
 PLEASE SUBMIT THE CALCULATIONS VIA EMAIL FOR
 PRELIMINARY REVIEW. PLEASE FEEL FREE TO CONTACT ME IF
 YOU DISAGREE WITH THE COMMENTS.
  
 3RD ROOFTOP EQUIPMENT WIND LOAD CALC REVIEW:
  
 PER CONVERSATION WITH ENGINEER, THE SCREW HAS A 3.0
 FACTOR OF SAFETY. THEREFORE, THE ENGINEER FELT THAT A
 FACTOR OF SAFETY OF 2 FOR THE UNIT WAS INCLUDED THROUGH
 THE FACTOR OF SAFETY OF 3 IN THE SCREW VALUES. IT IS
 OUR OPINION THAT THIS RATIONALE IS NOT CORRECT; THERE
 IS A FACTOR OF SAFETY ON THE LOAD, AND A FACTOR OF
 SAFETY ON THE MATERIAL, AND THE TWO ARE DIFFERENT. ONE
 CANNOT SUBSTITUTE FOR THE OTHER. IT SEEMS THAT THE
 FACTOR OF SAFETY FOR THE LOAD SHOULD BE APPLIED TO THE
 LOAD VALUE, THEN DEMONSTRATED THAT THE SCREWS PROPOSED
 MEET THAT DESIGN REQUIREMENT. PLEASE EITHER REVISE THE
 CALCULATIONS ACCORDINGLY OR PROVIDE DOCUMENTATION TO
 SUPPORT YOUR ARGUMENT (CODE REFERENCES, PUBLISHED
 DOCUMENTS, NATIONALLY RECOGNIZED STANDARDS, ETC.). YOU
 ARE WELCOME TO SUBSTANTIATE THE CALCULATIONS SUBMITTED;
 ANY DOCUMENTS SUBMITTED WILL BE REVIEWED AND CONSIDERED
 PROMPTLY. DUE TO THE URGENCY, PLEASE SUBMIT VIA EMAIL.
  
 REVIEW DONE AT REQUEST OF RR (EXPEDITED)
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved