2008-12-18 08:40:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENT FROM PREVIOUS LIST:
  
 4. IF PULLOUT VALUE FOR #10 SCREW IS 109, WITH A SAFETY
 FACTOR OF 2, SHOULDN'T IT BE DIVIDED BY TWO RATHER THAN
 MULTIPLIED BY TWO? CAPACITY WITH STRESS INCREASE FROM
 CALCULATIONS PROVIDED IS 290; IT DOES NOT SEEM LOGICAL
 WHEN PRODUCT DATA STATES 109. THIS COMMENT ALSO APPLIES
 TO SHEAR FOR #10 AND PULLOUT AND SHEAR FOR #12. PLEASE
 EXPLAIN CALCULATION.
  
 2ND ROOFTOP EQUIPMENT WIND LOAD CALC REVIEW:
  
 ALL COMMENTS WERE ADDRESSED EXCEPT FOR ITEM 4. PLEASE
 CONTACT ME TO EXPLAIN RATIONALE. IT APPEARS THAT THE
 CAPACITY OF THE SCRE HAS BEEN INCREASED BY 3/2 (109
 PULLOUT TIMES 3/2). FOR A FACTOR OF SAFETY OF 2,
 SHOULDN'T IT BE MULTIPLIED BY 1/2, REDUCING IT BY HALF?
 IT APPEARS THAT THE SCREW CAPACITY HAS BEEN INCREASED
 BY 50%.
  
 DUE TO THE URGENCY OF GETTING THIS MATTER RESOLVED,
 PLEASE SUBMIT THE CALCULATIONS VIA EMAIL FOR
 PRELIMINARY REVIEW. PLEASE FEEL FREE TO CONTACT ME IF
 YOU DISAGREE WITH THE COMMENTS.
  
 REVIEW DONE AT REQUEST OF RR (EXPEDITED)
  