Plan Review Notes
Plan Review Notes For Permit 08070134
Permit Number 08070134
Review Stop B
Sequence Number 4
Notes
Date Text
2008-11-07 12:35:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. TITLE BLOCK REQUIRED IN ACCORDANCE WITH
 FAC61G15-23.002. (COFA MISSING)
  
 2. THE FIRST PAGE OF CALCS STATES THAT A 33% ALLOWABLE
 STRESS INCREASE WAS TAKEN. SEE FBC1605.3.1.1(2) AND
 CLARIFY USE OF STRESS INCREASE.
  
 3. REPORTS ARE TO USE AN INDEX SHEET IN ACCORDANCE WITH
 FAC61G15-23.002. THE CALCULATIONS SUBMITTED DO NOT HAVE
 PAGE NUMBERS AND ARE NOT OTHERWISE IDENTIFIED. PLEASE
 REVISE.
  
 4. IF PULLOUT VALUE FOR #10 SCREW IS 109, WITH A SAFETY
 FACTOR OF 2, SHOULDN'T IT BE DIVIDED BY TWO RATHER THAN
 MULTIPLIED BY TWO? CAPACITY WITH STRESS INCREASE FROM
 CALCULATIONS PROVIDED IS 290; IT DOES NOT SEEM LOGICAL
 WHEN PRODUCT DATA STATES 109. THIS COMMENT ALSO APPLIES
 TO SHEAR FOR #10 AND PULLOUT AND SHEAR FOR #12. PLEASE
 EXPLAIN CALCULATION.
  
 5. THE ENGINEER'S SEAL IS TO BE ONE ACCEPTABLE TO THE
 BOARD, FAC61G15. THE SEAL IS TO STATE "LICENSE" RATHER
 THAN "CERTIFICATE".
  
 REVIEW DONE AT REQUEST OF RR (EXPEDITED)
  