Notes
Date Text
2008-09-16 08:29:36 
 ** DENIED **
  
 1) NOTE: PLANS NEED ADJUSTMENTS FOR FBC
 13-415.1.ABC.1.1, .1.2.
 CLOSET/STORAGE ROOM MISSING LIGHT FIXTURE AND CONTROL.
 MISSING OVER RIDE CONTROLS AT REAR OF STORE FOR
 OCCUPANTS ENTERING RETAIL SPACE(S).
 MISSING OCCUPANCY SENSOR/OVER RIDE FROM HALL TO REAR
 (WEST) STOCK RECEIVING AREA. THE SINGLE DEVICE AS SHOWN
 WOULD NOT PROVIDE COVERAGE WITH THE RACKING SYSTEM AS
 SHOWN ON PLANS.
 SPOKE TO KEN SNARE HE IS GOING TO VERY THE WATTAGE ON
 WALL-PACK FIXTURES AS THE FIXTURE LEGEND AND INPUT DATA
 REPORT SHOW SOME DIFFERENCES.
 MR. SNARE WILL ALSO VERIFY THE *PHOENIX* FIXTURE WHICH
 IS ON FIXTURE LEGEND HOWEVER NOT ON PLANS. THIS FIXTURE
 CAN BE REDLINED AS NOT TO BE USED WITHOUT HAVING TO
 REVISE PLANS.
 SHEET E-2.1 NEEDS TO BE RE-DONE.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  