| Date |
Text |
| 2008-08-25 19:13:17 | *****UNSAT***** |
| | |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEW STILL NEED TO BE ADDRESSED. THE HIGHLIGHTED |
| | RESPONSES BY THE PLAN EXAMINER SUGGEST HOW EACH COMMENT |
| | CAN BE ADDRESSED: |
| | |
| | |
| | 01. DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SINCE |
| | THERE ARE NO FIRE ALARM SHEETS, ADD COMMENT TO POWER |
| | NOTE #32 (SHEET E2) . |
| | |
| | 02 FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL |
| | STATION SEVICE. SINCE THERE ARE NO FIRE ALARM SHEETS, |
| | ADD COMMENT TO POWER NOTE #7 (SHEET E2) . |
| | |
| | 03. FIRE ALARM SHALL BE CLASS A OR FULLY ADDRESSABLE. |
| | SINCE THERE ARE NO FIRE ALARM SHEETS, ADD COMMENT TO |
| | POWER NOTES (SHEET E2) . |
| | |
| | 06. PHYSICAL ADDRESS REQUIRED ON EACH SHEET. ADD |
| | ADDRESS TO THE TITLE BLOCK OF SHEET FP-1, FP-2, & FP-3 |
| | |
| | 11. ADDRESS REQUIRED ON BUILDING SHALL BE A MINIMUM OF |
| | 6" IN HEIGHT AND 1" IN WIDTH CONTRASTING WITH THE |
| | BACKGROUND FOR COMMERCIAL BUILDINGS. ON SHEET A8, |
| | DISPLAY/SHOW THE ACTUAL ADDRESS NUMBERS ON THE |
| | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS OKEECHOBEE |
| | BOULEVARD |
| | |
| | 12. KNOX BOX IS REQUIRED ON THE BUILDING FOR AFTER |
| | NORMAL BUSINESS HOURS EMERGENCY ACCESS. ON SHEET A8, |
| | DISPLAY/SHOW THE LOCATION OF THE KNOX BOX ON THE |
| | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS OKEECHOBEE |
| | BOULEVARD |
| | |
| | 13. PLEASE EXPLAIN NOTES ON SHEET FP-1 REFERENCING FLOW |
| | TEST RESULTS TAKEN BY TVA FIRE AND LIFE SAFETY. PLAN |
| | EXAMINER TO VERIFY FINDINGS REFERRING TO RESULTS |
| | OBTAINED FROM WEST PALM BEACH WATER AUTHORITY ON 3/08 |
| | OR 18/2008 |
| | |
| | 14. IF THE FIRE DEPARTMENT CONNECTION FOR THE PROJECT |
| | IS NEW, KNOX LOCKING CAPS ARE REQUIRED. ADD COMMENT TO |
| | AN APPROPIATE FP SHEET |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |
| | FIRE INSPECTIONS |
| | 561-804-4751 |